CONNECTING POWER

The DA30D requires a 10-30 VDC power

supply. A pluggable power block is provided
to connect the 24 VDC. There are three screw
terminals. Strip and connect the wire
according to the terminal block specifications
on Page 2. Connect the positive lead to the
plus (+) screw and the negative lead to the
minus (-) screw.

Please take care to observe the following points:
–  Mount the power supply close to the unit, with usually not more than

6 feet (1.8 m) of cable between the supply and the operator
interface. Ideally, the shortest length possible should be used.

–  The wire used to connect the operator interface’s power supply

should be at least 22-gage wire suitably rated for the temperatures
of the environment to which it is being installed. If a longer cable run
is used, a heavier gage wire should be used. The routing of the
cable should be kept away from large contactors, inverters, and
other devices which may generate significant electrical noise.

–  A power supply with an NEC Class 2 or Limited Power Source (LPS)

and SELV rating is to be used. This type of power supply provides
isolation to accessible circuits from hazardous voltage levels generated
by a mains power supply due to single faults. SELV is an acronym for
“safety extra-low voltage.” Safety extra-low voltage circuits shall exhibit
voltages safe to touch both under normal operating conditions and after
a single fault, such as a breakdown of a layer of basic insulation or after
the failure of a single component has occurred. A suitable disconnect
device shall be provided by the end user.

CONNECTING TO EARTH GROUND

The third pin of the power connector is chassis ground for the unit.

Your unit should be connected to earth ground. Steps should be taken
beyond connecting to earth ground to eliminate the buildup of
electrostatic charges.

The chassis ground is not connected to signal common of the unit.

Maintaining isolation between earth ground and signal common is not
required to operate your unit. But, other equipment connected to this unit
may require isolation between signal common and earth ground. 

To

maintain isolation between signal common and earth ground care must
be taken when connections are made to the unit.

 For example, a power

supply with isolation between its signal common and earth ground must
be used. Also, plugging in a USB cable may connect signal common and
earth ground.

1

1

 USB’s shield may be connected to earth ground at the host. USB’s

shield in turn may also be connected to signal common.

MODULE

 

INSTALLATION

Remove module plug and attach module to DA30D. Torque screws to

6.0 pound-force inch [96 ounce-force inch] (0.68 Nm). 

EMC

 

INSTALLATION

 

GUIDELINES

Although Red Lion Controls products are designed with a high degree

of immunity to Electromagnetic Interference (EMI), proper installation and
wiring methods must be followed to ensure compatibility in each
application. The type of the electrical noise, source or coupling method
into a unit may be different for various installations. Cable length, routing,
and shield termination are very important and can mean the difference
between a successful or troublesome installation. Listed are some EMI
guidelines for a successful installation in an industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly

connected to protective earth.

2. Use shielded cables for all Signal and Control inputs. The shield

connection should be made as short as possible. The connection point
for the shield depends somewhat upon the application. Listed below
are the recommended methods of connecting the shield, in order of
their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end

where the unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually

when the noise source frequency is over 1 MHz.

3. Never run Signal or Control cables in the same conduit or raceway with

AC power lines, conductors, feeding motors, solenoids, SCR controls,
and heaters, etc. The cables should be run through metal conduit that
is properly grounded. This is especially useful in applications where
cable runs are long and portable two-way radios are used in close
proximity or if the installation is near a commercial radio transmitter.
Also, Signal or Control cables within an enclosure should be routed as
far away as possible from contactors, control relays, transformers, and
other noisy components. 

4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI

suppression devices such as Ferrite Suppression Cores for signal and
control cables is effective. The following EMI suppression devices (or
equivalent) are recommended:

Fair-Rite part number 0443167251 (Red Lion Controls #FCOR0000)
Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion Controls #LFIL0000)

6. To protect relay contacts that control inductive loads and to minimize

radiated and conducted noise (EMI), some type of contact protection
network is normally installed across the load, the contacts or both. The
most effective location is across the load.
a. Using a snubber, which is a resistor-capacitor (RC) network or metal

oxide varistor (MOV) across an AC inductive load is very effective at
reducing EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a

transistor switch, care must be taken not to exceed the breakdown
voltage of the transistor when the load is switched. One of the most
effective ways is to place a diode across the inductive load. Most
Red Lion products with solid state outputs have internal zener diode
protection. However external diode protection at the load is always a
good design practice to limit EMI. Although the use of a snubber or
varistor could be used.
Red Lion part numbers: Snubber: SNUB0000

Varistor: ILS11500 or ILS23000

7. Care should be taken when connecting input and output devices to the

instrument. When a separate input and output common is provided,
they should not be mixed. Therefore a sensor common should NOT be
connected to an output common. This would cause EMI on the
sensitive input common, which could affect the instrument’s operation.

Visit 

www.redlion.net/emi

 for more information on EMI guidelines,

Safety and CE issues as they relate to Red Lion products.

REMOVE MODULE PLUG

WARNING: Disconnect all power 
to the unit before installing or 
removing modules.

Содержание DA30D

Страница 1: ...tual HMI The virtual HMI is programmed just like Red Lion s CR3000 series of HMIs Any standard web browser may be used to monitor or control the DA30D from a PC anywhere in the world The DAx0D is programmed with Red Lion s Crimson 3 1 software Crimson offers easy to use drag and drop communications configuration and is available as a no charge download from Red Lion s website DIMENSIONS In inches ...

Страница 2: ... COMPLIANCES CE Approved EN 61326 1 Immunity to Industrial Locations Emission CISPR 11 Class A IEC EN 61010 1 RoHS Compliant UL Hazardous File E317425 Rugged IP40 enclosure 7 CONNECTIONS High compression cage clamp terminal block Wire Strip Length 0 3 7 5 mm Wire Gage Capacity 12 to 24 AWG 3 31 to 0 20 mm2 copper wire Torque 4 4 5 3 inch lbs 0 5 0 6 N m 8 CONSTRUCTION Polycarbonate enclosure with ...

Страница 3: ...ifference between a successful or troublesome installation Listed are some EMI guidelines for a successful installation in an industrial environment 1 A unit should be mounted in a metal enclosure which is properly connected to protective earth 2 Use shielded cables for all Signal and Control inputs The shield connection should be made as short as possible The connection point for the shield depen...

Страница 4: ...D CARD Insert the SD card into the slot provided with the card oriented as shown The card is inserted properly when the end of the card is flush with the DA30D case To remove the SD card push in slightly on the card CABLES AND DRIVERS Red Lion has a wide range of cables and drivers for use with many different communication types A list of these drivers and cables along with pin outs is available f...

Страница 5: ...B 8 TxA 8 TxA CRIMSON 3 1 SOFTWARE Crimson 3 1 software is available as a no charge download from Red Lion s website The latest version of the software is always available from the website and updating your copy is free STATUS LEDS There are three status LEDs that show system status by default or they may be be user configured via System Functions using Crimson 3 1 Shown below is the default syste...

Страница 6: ...ery is correct and as shown in the diagram Re install the battery holder with battery into the DAx0D unit Enter new date and time using Crimson 3 1 software CAUTION Lithium battery Danger of explosion if battery is incorrectly replaced Replace only with the same or equivalent type recommended by the manufacturer Please note that the old battery must be disposed of in a manner that complies with yo...

Страница 7: ... 7 Effective 2018 11 02 Bulletin No DA30D A Drawing No LP1078 This page intentionally left blank ...

Страница 8: ... BY LAW COURSE OF DEALING COURSE OF PERFORMANCE USAGE OF TRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal law b The Company shall not be liable for a breach of the warranty set forth in paragraph a if i the defect is a result of Customer s failure to store install com...

Отзывы: