1.

POWER REQUIREMENTS

:

Must use a Class 2 circuit according to National Electrical Code (NEC),

NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a
Limited Power Supply (LPS) according to IEC 60950-1 or Limited-
energy circuit according to IEC 61010-1.
Power connection via removable three position terminal block.

Supply Voltage: 10 to 30 VDC, Class 2 source

2. 

BATTERY

: Lithium coin cell. Typical lifetime of 5 years, nominal.

To maintain UL rating, replacement battery must be: Red Lion CRA000

BT3V0 00000, Rayovac BR1225X-BA or Panasonic BR1225A/BN.

3. 

MEMORY

:

On Board User Memory: 512 Mbyte of non-volatile Flash memory.
Memory Card: SD slot accepts standard capacity cards up to 16 GB.

4. 

COMMUNICATION CAPABILITIES

:  

USB Device Port

: Isolated and adheres to USB specification 2.0 full

speed only using Type B connection. 

USB DEVICE PORT IS FOR

SYSTEM SET-UP AND DIAGNOSTICS AND IS NOT INTENDED FOR
PERMANENT CONNECTION.

USB Host Port

:

 

Comply with Universal Serial Bus Specification Rev

2.0. Support data transfers at (high speed, full speed). Hardware
over current protected (0.5 A max per port).

Serial Ports

: Ports are individually isolated. Format and Baud Rates for

each port are individually software programmable up to 115,200
baud.
Port to Port Isolation: 1500 Vrms for 1 minute.

Signal Isolation: 500 V.

Ethernet Port

: 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card).
Isolation from Ethernet network to operator interface: 1500 Vrms

5. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: -10 to 50 °C
Storage Temperature Range: -20 to 70 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g
Shock to IEC 68-2-27: Operational 30 g
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
Installation Category II, Pollution Degree 2 as defined in IEC/EN 60664-1. 

6. 

CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant

UL Hazardous: File #E317425
Rugged IP40 enclosure

7. 

CONNECTIONS

: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)
Wire Gage Capacity: 12 to 24 AWG (3.31 to 0.20 mm

2

) copper wire

Torque: 4.4-5.3 inch-lbs (0.5-0.6 N-m)

8. 

CONSTRUCTION

: Polycarbonate enclosure with IP40 rating. For

indoor use only.

9. 

MOUNTING REQUIREMENTS

: Snaps onto standard DIN style top hat

(T) profile mounting rails according to EN50022 – 35 x 7.5 mm and
35 x 15 mm.

10. 

WEIGHT

: 6.9 oz (195.61 g)

Input Voltage (Volts)

10 V

12 V

24 V

30 V

Typ. Power DA30D only (Watts)

4.5

5.0

5.0

5.0

Max Power DA30D only (Watts)

6.5

7.0

7.0

7.0

Max Power DA30D w/Module (W) 11.5

12.5

12.5

12.5

SPECIFICATIONS

INSTALLING

 

AND

 

POWERING

 

THE

 

DA30D

MOUNTING

 

INSTRUCTIONS

DIN rail should be mounted horizontally so that the unit’s ventilation

holes are vertical in relation to cabinet orientation. A minimum clearance
of 1 inch (25.4 mm) should be maintained above and below the unit in
order to ensure proper thermal regulation.

Figure 1 - Attach DAx0D To DIN Rail

The unit shall be installed inside a UL Listed Industrial Control Panel or

similar type of enclosure. A minimum 3.2 mm distance shall be
maintained between the hazardous live parts of the equipment and
accessible parts of the fire/electrical enclosure.

For hazardous location installation the following shall be taken into

consideration:

-  

This device is open-type and must be mounted in a suitable dust-

tight end-enclosure in accordance with articles 500 and 502 of the

National Electric Code (

NEC).

-  Must be wired using Division 2 wiring methods as specified in article

501-4(b), 502-4(b), and 503-3(b) of the NEC, NFPA 70 for
installation within the United States, or as specified in section 19-152
of Canadian Electrical Code for installation in Canada.

-  Combinations of equipment in your system are subject to investigation

by the local Authority having jurisdiction at the time of installation.

ROT

ATE

1.00"

1.00"

min. clearance

min. clearance

TOP

BOTTOM

Содержание DA30D

Страница 1: ...tual HMI The virtual HMI is programmed just like Red Lion s CR3000 series of HMIs Any standard web browser may be used to monitor or control the DA30D from a PC anywhere in the world The DAx0D is programmed with Red Lion s Crimson 3 1 software Crimson offers easy to use drag and drop communications configuration and is available as a no charge download from Red Lion s website DIMENSIONS In inches ...

Страница 2: ... COMPLIANCES CE Approved EN 61326 1 Immunity to Industrial Locations Emission CISPR 11 Class A IEC EN 61010 1 RoHS Compliant UL Hazardous File E317425 Rugged IP40 enclosure 7 CONNECTIONS High compression cage clamp terminal block Wire Strip Length 0 3 7 5 mm Wire Gage Capacity 12 to 24 AWG 3 31 to 0 20 mm2 copper wire Torque 4 4 5 3 inch lbs 0 5 0 6 N m 8 CONSTRUCTION Polycarbonate enclosure with ...

Страница 3: ...ifference between a successful or troublesome installation Listed are some EMI guidelines for a successful installation in an industrial environment 1 A unit should be mounted in a metal enclosure which is properly connected to protective earth 2 Use shielded cables for all Signal and Control inputs The shield connection should be made as short as possible The connection point for the shield depen...

Страница 4: ...D CARD Insert the SD card into the slot provided with the card oriented as shown The card is inserted properly when the end of the card is flush with the DA30D case To remove the SD card push in slightly on the card CABLES AND DRIVERS Red Lion has a wide range of cables and drivers for use with many different communication types A list of these drivers and cables along with pin outs is available f...

Страница 5: ...B 8 TxA 8 TxA CRIMSON 3 1 SOFTWARE Crimson 3 1 software is available as a no charge download from Red Lion s website The latest version of the software is always available from the website and updating your copy is free STATUS LEDS There are three status LEDs that show system status by default or they may be be user configured via System Functions using Crimson 3 1 Shown below is the default syste...

Страница 6: ...ery is correct and as shown in the diagram Re install the battery holder with battery into the DAx0D unit Enter new date and time using Crimson 3 1 software CAUTION Lithium battery Danger of explosion if battery is incorrectly replaced Replace only with the same or equivalent type recommended by the manufacturer Please note that the old battery must be disposed of in a manner that complies with yo...

Страница 7: ... 7 Effective 2018 11 02 Bulletin No DA30D A Drawing No LP1078 This page intentionally left blank ...

Страница 8: ... BY LAW COURSE OF DEALING COURSE OF PERFORMANCE USAGE OF TRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal law b The Company shall not be liable for a breach of the warranty set forth in paragraph a if i the defect is a result of Customer s failure to store install com...

Отзывы: