INPUT RANGE JUMPER

This jumper is used to select the proper input range. The input range selected 

in programming must match the jumper setting. Select a range that is high 

enough to accommodate the maximum input signal to avoid overloads. To 

access the jumper, remove the rear cover of the meter. 

Warning

: Exposed line voltage exists on the circuit boards. 

Remove all power to the meter and load circuits before accessing 

inside of the meter.

REMOVE/REPLACE THE REAR COVER

To remove the rear cover, locate the cover locking tab below the 2nd and 3rd 

input terminals. To release the tab, insert a small, flat blade screwdriver between 

the tab and the plastic wall below the terminals. Inserting the screwdriver will 

provide enough pressure to release the tab locks. To replace the cover, align the 

cover with the input terminals and press down until the cover snaps into place.

3

ADDING OPTION CARDS

The CUB5 meters can be fitted with optional output cards and/or serial 

communications cards. The details for the plug-in cards can be reviewed in the 

specification section below. The plug-in cards, that are sold separately,

 

can be 

installed initially or at a later date.

WARNING: Disconnect all power to the unit before installing 

Plug-in card.

Note

: Measurement errors may occur if signal input common is shared with 

another circuit common (ie, serial common, Dual Sinking Output option card, 

or Power Supply common) on multiple units.

SINGLE RELAY CARD

Type

: Single FORM-C relay

Isolation To Sensor & User Input Commons

: 1400 Vrms for 1 min.

Working Voltage: 150 Vrms

Contact Rating

: 1 amp @ 30 VDC resistive; 0.3 amp @ 125 VAC resistive

Life Expectancy

: 100,000 minimum operations

DUAL SINKING OUTPUT CARD

Type

: Non-isolated switched DC, N Channel open drain MOSFET

Current Rating

: 100 mA max. 

V

DS ON

: 0.7 V @ 100 mA

V

DS MAX

: 30 VDC

Offstate Leakage Current

: 0.5 mA max.

RS485 SERIAL COMMUNICATIONS CARD

Type

: RS485 multi-point balanced interface (non-isolated)

Baud Rate

: 300 to 38.4k

Data Format

: 7/8 bits; odd, even, or no parity

Bus Address

: 0 to 99; max 32 devices per line

Transmit Delay

: Selectable (refer to CUB5COM bulletin)

RS232 SERIAL COMMUNICATIONS CARD

Type

: RS232 half duplex (non-isolated)

Baud Rate

: 300 to 38.4k

Data Format

: 7/8 bits; odd, even, or no parity

USB PROGRAMMING CARD

Type

: USB virtual comms port

Connection

: Type B

Baud Rate

: 300 to 38.4k

Unit Address

: 0 to 99

o

ptional

 p

luG

-

in

 c

ardS

1.0 i

nStallinG

 

the

 M

eter

2.0 S

ettinG

 

the

 J

uMperS

INPUT RANGE JUMPER

MAIN CIRCUIT 

BOARD

20/50 mA

INPUT RANGE

JUMPER LOCATION

10 

V

INSTALLATION 

The meter meets NEMA 4X/IP65 requirements when properly installed. The 

unit is intended to be mounted into an enclosed panel. Prepare the panel cutout 

to the dimensions shown. Remove the panel latch from the unit. Slide the panel 

gasket over the rear of the unit to the back of the bezel. 

The unit should be installed fully assembled. Insert 

the unit into the panel cutout. 

While holding the unit in place, push the panel 

latch over the rear of the unit so that the tabs of the 

panel latch engage in the slots on the case. The 

panel latch should be engaged in the farthest 

forward slot possible. To achieve a proper seal, tighten the latch screws evenly 

until the unit is snug in the panel (Torque to approx. 28 to 36 in-oz [0.202 to 0.26 

N-m]). Do not over-tighten the screws.

INSTALLATION ENVIRONMENT

The unit should be installed in a location that does not exceed the operating 

temperature and provides good air circulation. Placing the unit near devices that 

generate excessive heat should be avoided.

The bezel should only be cleaned with a soft cloth and neutral soap product. 

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the 

aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the 

keypad of the unit.

2.68

[68      ]

+.6

1.30

-.0

[33      ]

-.000

+.025

-.000

+.024

+.6

-.0

PANEL 

GASKET

BEZEL

PANEL

MOUNTING SCREW

NUT FASTENER

MOUNTING CLIP

Содержание CUB 5P

Страница 1: ...n be powered from an optional Red Lion Micro Line Sensor Power Supply MLPS which attaches directly to the back of a CUB5 The MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the unit and sensors INPUT The CUB5P is a DC Process meter It features voltage and current input ranges that are selected by the user via a programming jumper and software input range selection The ranges ...

Страница 2: ...FICATIONS AND COMPLIANCES CE Approved EN 61326 1 Immunity to Industrial Locations Emission CISPR 11 Class A Safety requirements for electrical equipment for measurement control and laboratory use EN 61010 1 General Requirements EN 61010 2 030 Particular Requirements for Testing and Measuring Circuits RoHS Compliant UL Recognized Component File E179259 UL Listed File E137808 Type 4X Indoor Outdoor ...

Страница 3: ...85 SERIAL COMMUNICATIONS CARD Type RS485 multi point balanced interface non isolated Baud Rate 300 to 38 4k Data Format 7 8 bits odd even or no parity Bus Address 0 to 99 max 32 devices per line Transmit Delay Selectable refer to CUB5COM bulletin RS232 SERIAL COMMUNICATIONS CARD Type RS232 half duplex non isolated Baud Rate 300 to 38 4k Data Format 7 8 bits odd even or no parity USB PROGRAMMING CA...

Страница 4: ...2010 1 07 Red Lion Controls LFIL0000 6 To protect relay contacts that control inductive loads and to minimize radiated and conducted noise EMI some type of contact protection network is normally installed across the load the contacts or both The most effective location is across the load a Using a snubber which is a resistor capacitor RC network or metal oxide varistor MOV across an AC inductive l...

Страница 5: ...N U S A MLPS1 2 WIRE TRANSMITTER COMM INP _ MODEL INPUT POWER OUTPUT POWER 85 250 VAC 50 60Hz 14VA OPERATING TEMP 0 TO 60 C 12VDC UNREG 400mA 12V DC COMMON M3424B TERMINAL AC INPUT RED LION CONTROLS YORK PA MADE IN U S A MLPS1 2 WIRE TRANSMITTER INP COMM EXTERNAL POWER COMM COMM VDC VDC _ COMM INP MODEL INPUT POWER OUTPUT POWER 85 250 VAC 50 60Hz 14VA OPERATING TEMP 0 TO 60 C 12VDC UNREG 400mA 12V...

Страница 6: ... pressing the SEL button with Pro NO displayed This will commit any stored parameter changes to memory and return the meter to the Display Mode If power loss occurs before returning to the Display Mode verify recent parameter changes PROGRAMMING TIPS It is recommended to start with Module 1 and proceed through each module in sequence When programming is complete it is recommended to record the par...

Страница 7: ...ut Values have to be derived from the actual input signal source or simulator the Apply APLY scaling style must be used KEy APLY 0 000 INP 1 INPUT VALUE FOR SCALING POINT 1 For Key in KEY style enter the known first Input Value using the front panel buttons The Input Range selection sets the decimal location for the Input Value For Apply APLY style the meter shows the previously stored Input Value...

Страница 8: ...ow FACTORY SERVICE OPERATIONS yES NO YES NO Enables the Maximum Display Capture capability Enables the Minimum Display Capture capability The CUB5P uses stored calibration values to provide accurate voltage and current measurements Over time the electrical characteristics of the components inside the meter could slowly change therefore the stored calibration values may no longer accurately define ...

Страница 9: ...Backlight Unit Only 3 dSP dSP t SEL rSt ZErO UNItS COLOr CodE Display Intensity Level d LEV ScroL Display Scroll Enable PARAMETER MENU The yES selection allows the SEL button to toggle through the enabled displays FRONT PANEL DISPLAY SELECT ENABLE SEL This selection allows the RST button to reset the selected value s FRONT PANEL RESET ENABLE RST The yES selection allows the display to automaticall...

Страница 10: ...nced are affected by the hysteresis When the setpoint is a control output usually balanced hysteresis is used For alarm applications usually unbalanced hysteresis is used For unbalanced hysteresis modes the hysteresis functions on the low side for high acting setpoints and functions on the high side for low acting setpoints Note Hysteresis eliminates output chatter at the switch point while time d...

Страница 11: ...active when one of the optional serial communications programming cards is installed in the meter Refer to the CUB5COM bulletin for details and setup for the CUB5 RS232 or RS485 serial communications Refer to the CUB5USB bulletin for details on the CUB5 USB programming and programming requirements PARAMETER MENU button or user input manual reset serial reset command or meter power cycle When the u...

Страница 12: ...n tOF n rSt n rEn n ChC n Standby Operation Stb n Front Panel Reset Enable Front Panel Display Select Enable Display Update Time dSP t SEL rSt 3 dSP Display Intensity Level COLOr Units Indicator Selection UNItS Display Color d LEV Programming Security Code CodE rANGE dECPt 1 INP FILtr bANd USrIN INP 1 dSP 1 INP 2 U ASN LO En Min Display Enable Max Capture Delay Time Max Display Enable HI En HI t 2...

Отзывы: