16

Certification - LiFePO4 
3,800mAh cell

IECL62619:2017 & UN38.3

3,800mAh cell used in the Troppo battery is certified by 
TuV for RedEarth in the company name.

Battery Management System (BMS) Protection Settings

Battery type and number 
of cells in series

LiFePO4 (16S)

Custom BMS designed for RedEarth

BMS Over-Volt cut off

58.4V

DC

Maintain battery between 48.0 & 57.6V

DC

BMS Under-Volt cut off

40V

Battery will switch off internally - follow Flat Battery 
Restart procedure to restart the battery

Charging over-current 
protetion

78±8A

Battery will stop charging above this level

Discharge over-current 
protection 
(2 levels)

250±60A(20-400mS) & 

400±100A(10-100mS)

2 levels: 250+/-60A delay 20-400mSec; 400+/-100A delay 
10-100mSec.

Inverter capacitors - 
starting capability

14,600uF

The battery can provide the surge current needed to start 
an inverter with up to 14,600uF of capacitors on the DC 
side.

High temperature - 
discharge protection

60±5°C

Battery will not discharge if the two temperature sensors 
in the cell pack are reading above this temperature.

High temperature - charge 
protection

50±5°C

Battery will not charge if one of the two temperature 
sensors in the cell pack are reading above this 
temperature.

Low temperature - 
discharge protection

-20±5°C

Battery will stop discharging if one of the two temperature 
sensors reads below this temperature.

Low temperature - charge 
protection

0±5°C

Battery will stop charging if temperature sensors below 
this temperature - 

Required feature of all installed 

battery systems

.

Cell balancing method

Passive equalisation at 57.6V

DC

Top balancing (i.e. during charging once each row of cells 
reaches (3.65V)

Note: In our efforts towards constant product enhancement this specification is subject to change to at anytime without 
notice.

Содержание TROPPO - 4841

Страница 1: ...dearth energy www redearth energy 15 Fienta Place Darra QLD 4076 1800 733 637 Troppo 4841 Manual Version 1 17 Apr 2021 Installation and Operation Manual T R O P P O 4 8 4 1 L I T H I U M B A T T E R Y...

Страница 2: ......

Страница 3: ...y and its Use 7 VI Charging and Discharging the Troppo Battery 7 VII Battery Installation Location and Equipment 9 VIII Battery Connection and Operation 11 IX Transportation 13 X Troppo Battery Specif...

Страница 4: ...high quality industry standard Amphenol Surlok DC connectors for safe and easy connection of the DC battery cables These have a significant safety advantage over legacy systems using exposed bolted te...

Страница 5: ...maximum stacking height is 8 batteries when in RedEarth s transport box Damaged battery A damaged battery must not be used and returned to RedEarth as soon as possible or disposed of via a recycling...

Страница 6: ...PO battery has been specifically designed to be self managing This means it does not need to communicate with the inverter charger to operate There is no need for multiple communication wires between...

Страница 7: ...y available in a 48Vdc model and is sized to be installed in standard 19 inch racks RedEarth also provides its own range of purpose built 19 racks for this The TROPPO 4841 battery is certified to IEC6...

Страница 8: ...ng where the connection and control components are located Battery Weight 42 5kg Battery Dimensions 438mm wide x 725mm deep x 88mm high Package Weight with Battery 44 0kg Package Dimensions 540mm wide...

Страница 9: ...3 800mAh and a voltage of 3 2Vdc There are 16 cells in series which provides a battery voltage of 51 2V 48V nominal There are also 21 cells in parallel adding up to 336 cells for the battery and a to...

Страница 10: ...ffers a wide range of training options for our partners including regular training courses run at our Brisbane facility on site for our larger customer as well as online training options The battery s...

Страница 11: ...ltage disable float otherwise set to 53 5V Float voltage charging is not required Equalisation Voltage disable equalisation otherwise set to 53 5 VDC Avoid equalising the TROPPO battery Inverter Shut...

Страница 12: ...nt of a 48Vdc installation RACK19 can be supplied as an IP20 cabinet to house with a maximum of 8 or 20 batteries for indoor applications RACK19 can be configured with a built in Battery Breaker 160 2...

Страница 13: ...as specified in this manual the internal BMS will stop the operation of the battery if the cell temperatures move outside their specifications The temperature and humidity remain relatively constant t...

Страница 14: ...ltages closed together by charging or discharging one of the batteries before connecting in parallel 2 Switch OFF the OVERCURRENT PROTECTION MCB of all batteries 3 Next ensure the separate Main Batter...

Страница 15: ...ual This is a critical step If you are unsure of the settings required contact RedEarth as damage to batteries caused by incorrect settings of the inverter charger will affect your warranty 8 If you h...

Страница 16: ...or in pallets of batteries up to eight batteries high The batteries are shipped with The built in battery switch in the off position no voltage on the battery terminals The batteries in a partial sta...

Страница 17: ...voltage up to its maximum charge voltage in a laboratory environment 40 0 58 4VDC Nominal DC Voltage 51 2V 3 2V per cell LFP type x 16 cells in series 16S 51 2VDC Maximum Discharge Current 63A Limite...

Страница 18: ...a Physical Characteristics Battery mounting options In a standard 19 rack or horizontally vertically or on either side RedEarth can provide its pre wired RACK19 system with built in main battery break...

Страница 19: ...provide the surge current needed to start an inverter with up to 14 600uF of capacitors on the DC side High temperature discharge protection 60 5 C Battery will not discharge if the two temperature se...

Страница 20: ...ate If you are to add extra capacity the battery must be of the same type part number and specification Before adding the new battery the original battery bank and the new battery must be bought up to...

Страница 21: ...gether with the required battery cables Some parameters of the inverter charger may need to be adjusted to get the best performance from the new larger battery bank e g increase the charging current s...

Страница 22: ...instead of in parallel 2 Connecting the battery to incompatible equipment e g 12V battery charger 3 Incorrect inverter and or charger settings 4 Disassembling battery 5 Incorrect battery bank sizing...

Страница 23: ...RedEarth Energy Storage Ltd 15 Fienta Place Darra Brisbane QLD 4076 Australia RedEarth office Technical support Email 07 3279 6707 1800 733 637 0487 002 451 info redearth energy...

Страница 24: ......

Отзывы: