Charging time is dependent on the ampere hour rating of

the battery and its condition of charge.

Typical charge times for fully dis-
charged batteries using 6A model
No. A 4506 

24AH

6Hrs

40AH

10Hrs

Typical charge times for fully dis-
charged batteries using 12A model
No. A 4512

60AH

8Hrs

80AH

10Hrs

100AH

12Hrs

120AH

14Hrs

7.0 Charger Operation

Once wiring is finished switch on the unit. 
You should see the battery voltage and current draw indicated on the displays on the front panel. This refers to the voltage 

available at the battery terminals and the current flowing through the batteries. (A positive current figure indicates the 

batteries are being charged while a negative current figure indicates that the batteries are supplying power to the load(s)). 

It is common for the battery voltage to read nominally higher than the voltage rating of 24VDC. 

Whilst the battery is connected to the unit and mains power is applied, the charger will continue to charge the battery. 

The charger will charge the battery at “Boost” current (6A for A 4506 or 12A for A 4512) until 29.4V is reached, at 
which time the battery charger will continue to “Absorb” charge and then “Trickle” charge the battery in order to keep it 
topped up at 27.6V. 
LED’s on the front panel indicate when these  changes in the cycle occur.

Should mains power fail, the unit will automatically switch the connected load(s) to the battery. When mains power is 

restored the load(s) will be disconnected from the battery. LED’s on the front panel indicate when the unit is running of the 

mains or the battery.

If power is not restored before the battery voltage drops below 22V, the unit will automatically disengage the battery from 

the load. This will prevent long term blackouts from damaging the battery. 
Should the unit fail to operate in the above manner refer to troubleshooting.

8.0 Battery Isolate/Reset

The A 4506 and A 4512 battery charger models are fitted with an 100Amp breaker which is in line with the bve 

terminal. This breaker can be used as an isolator to quickly disengage the batteries without having to disconnect leads. It 

also acts as a safe guard against short circuits in the battery leads or reverse polarity connection.

9.0 Auxiliary Outputs and Alarm Contacts

24V auxiliary outputs have been provided so that external devices requiring 24V DC can be powered. Two sets of output 
terminals have been provided. The total combined load current available from these outputs is 1A maximum and is 

protected by an internal 1amp resettable fuse.

Alarm contacts have been provided for external monitoring of the battery charger. These contacts are normally open and 

close when there is a mains power fail or a low battery status is achieved.

10.0 Battery Charging Time

The table below indicates typical charging times for the shown ampere hour ratings.

Содержание A 4506

Страница 1: ...ort circuit protection Electronic reverse polarity protection 2 stage charging 2 switched 50 amp outputs Automatic boost and float voltages Precision control of boost and float voltage settings Batter...

Страница 2: ...ult condition Boost charge mode Solid orange LED Absorb charge mode Flashing orange LED Trickle charge mode Solid green LED Fault Mode Solid red LED 4 Auxiliary 24V Out Indicator This LED indicates wh...

Страница 3: ...he load s A maximum load of 50 amps per set of load terminals 8 Battery Isolate Reset This breaker can be used as an isolator to quickly disengage the batteries without having to disconnect leads It a...

Страница 4: ...nnect in parallel overnight 10 12 hours minimum prior to connecting them to the charger Failure to do this can cause a severe inbalance in the charging of the batteries causing permanent damage 12V Ba...

Страница 5: ...d load 1 ve and if required to load 2 ve and load 2 ve Note the load current is limited to 50 amps maximum per load Model A 4506 A4512 AC Fuse M205 5A 5A RISK OF ELECTRIC SHOCK OPEN BY QUALIFIED PERSO...

Страница 6: ...ur Should mains power fail the unit will automatically switch the connected load s to the battery When mains power is restored the load s will be disconnected from the battery LED s on the front panel...

Страница 7: ...y voltage Check that you have connected a lead from the battery to the terminals labelled Battery Voltage Unit will not charge battery Check connections to To battery terminals and to the battery Make...

Страница 8: ...isplay Battery Voltage 3 5 Digit LCD Battery Current 3 5 Digit LCD Trickle charge Green LED Float charge Flashing Yellow LED Boost Charge Yellow LED Mains Power Green LED Battery Power Yellow LED Low...

Отзывы: