Redback® Proudly Made In Australia
5
6.0 Battery and Load Configuration
Ensure that the power to the unit is off both at the mains and the switch at the front. Proceed to wire up the unit
according to the instructions below in figure 6.
Connect your battery to the binding posts on the back of the unit labelled (Bve and Battery –ve) using heavy gauge
cable.
Another lead needs to be connected to the battery from the terminal labelled
“Battery Voltage”
. This lead needs only
be made of medium duty wire. This lead
MUST BE CONNECTED
for the charger to operate and is used to measure the
voltage at the batteries.
Connect your load(s) to the binding posts labelled (Load 1 +ve and load 1 -ve and if required to load 2 +ve and load 2-ve).
Note: the load current is limited to 50 amps maximum per load.
Model
A 4506
A4512
AC Fuse (M205)
5A
5A
RISK OF ELECTRIC SHOCK
OPEN BY QUALIFIED
PERSONNEL ONLY
!
CAUTION
Manufactured in Australia
By Altronic Distributors Pty. Ltd.
www.altronics.com.au
LOAD 2 (-VE)
LOAD 1 (+VE)
(max load current 50A)
LOAD 2 (+VE)
(max load current 50A)
BATTERY (-VE)
BATTERY (+VE)
240V AC
LOAD 1 (-VE)
Please Note:
Unit suitable for use with Sealed Lead Acid (SLA)
batteries only.
NOTE: Only use batteries of the same make and capacity.
24V SYSTEM ONLY
Battery
Isolate/reset
Separate cable to run to battery
for accurate voltage indication
.
THIS MUST BE
CONNECTED FOR
CORRECT OPERATION
Battery
Voltage
+ –
24V Auxilliary
Outputs
(Total maximum
Load = 1 Amp)
Out
1
Out
2
- +
- +
Mains
Fail
Low
Batt.
Contacts close
on Alarm
Conditions
WATERPROOF
100A
+
-
24V BATTERY
BANK
LOAD 2
+
-
LOAD 1
+
-
Fig 6