8.0 24V OUTPUT CONNECTIONS

The A 4574 is fitted with four sets of 24V switched outputs for driving external devices such as strobes, sirens and attenu-
ators. Each output has a maximum current draw of 120mA. When connecting devices which require more than 24V DC @ 
120mA then an external supply and relays will be required. 
In the illustration of figure 3 a high current school bell is to be activated by the Bell 24V switched output. As the current 
draw of the Bell is more than 120mA, a relay board is used to switch an external power supply. The Altronics S 4444 24V 
Relay Board as shown is an inexpensive and easily installed option designed for this purpose. 24V DC strobes such as the 
Altronics S 5423, S 5430 and S 5435 strobes also draw more than 120mA so they are connected in the same fashion as 
shown in figure 3.

Switched 24V Out:

These contacts are for connection of override relays in remote volume controls. An override relay is necessary where
attenuators are used so that the alert tone, evac tone or message is broadcast at full volume regardless of the volume 
setting on the individual volume control (attenuator). 
The override relay can be set to “NORMAL” mode when connection is made between the N/O (normally open) contact 
and the GND connection. In this configuration 24V appears when any of the alert tone, evac tone, voice over message or 
paging functions are activated. 
The override relay can be set to “FAILSAFE” mode when connection is made between the N/C (normally closed) contact 
and the GND connection. In this configuration 24V is removed when any of the alert tone, evac tone, voice over message 
or paging functions are  activated. 

Alert 24V Out:

These contacts are for switched 24V outputs whenever the alert tones is activated. This may be used to run external 
systems such as strobes in unusually noisy environments. These operate in the same manner as the switched 24V out 
contacts i.e. connection between the N/O contact and the GND contact will operate in NORMAL mode and connection 
between the N/C contact and the GND will operate in FAILSAFE mode. 

Evac 24V Out:

These contacts are for switched 24V outputs whenever the evac tones is activated. This may be used to run external 
systems such as strobes in unusually noisy environments. These operate in the same manner as the switched 24V out 
contacts i.e. connection between the N/O contact and the GND contact will operate in NORMAL mode and connection 
between the N/C contact and the GND will operate in FAILSAFE mode. 

Bell 24V Out:

These contacts are for operating an external relay used to operate something like a lunch bell etc. 
These operate in the same manner as the switched 24V out contacts i.e.: connection between the N/O contact and the 
GND contact will operate in NORMAL mode and connection between the N/C contact and GND will operate in FAILSAFE 
mode. 

Fig 3.

L

R

Audio

 Out

24V 

DC IN 

www.redbackaudio.com.au

Manufactured in Australia 

By Altronic Distributors Pty. Ltd.

   1  2  3   4  5  6  7  8

 

DIP 

Switch 

Settings

DIP Switches

+

-

Volume

Bell

Voice

Over

Alert/

Evac

5

0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1

6

0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1

7

0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1

8

0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1

Delay

(Sec.)

O

FF

30

60

90

120

150

180

210

240

270

300

330

360

390

420

450

AUTO ALERT TO EVAC SWITCHOVER TIMER SETTINGS. 0 = OFF. 1 = ON.

SW

+_

24V 

DC In

Bell

Alert

Cancel

Evac

Contacts

N/O

GND

N/C

Switched

N/O

GND

N/C

N/O

GND

N/C

N/O

GND

N/C

24V Outputs

 (Outputs limited to 120mA)

Evac

Alert

Bell

Interface

1 2

3

4 5

6

7 8

ON

4

Momentary operation 

of Alert & Evac contacts

Bell - Repeatedly plays until

Not Used

OFF

1
2

Bell - Plays Once after

SW

3

 

Continuous operation 

of Alert & Evac contacts

Not Used

Activation

Cancel Activated

Attenuator fitted

with over ride relay.

(such as Altronics A 2260)

24V Strobes for

visual warning

(such as Altronics

S 5430 and S 5435)

24V Bell

(eg school bell, lunch bell etc)

+24V
GND

24V Relay Board

(Altronics S 4444)

N/C1

N/C2

N/O2

N/O1

COM1

COM2

External 

24V DC Supply

+24V
GND

+24V
GND

24V Relay Board

(Altronics S 4444)

N/C1

N/C2

N/O2

N/O1

COM1

COM2

External 

24V DC Supply

+24V
GND

Содержание A 2078B

Страница 1: ...instructions carefully from front to back prior to installation They include important setup instructions Failure to follow these instructions may prevent the unit from working as designed Distributed...

Страница 2: ...ion Switch This switch is used to cancel the Alert Evac or Bell tones Press for 2 seconds to activate 5 Micro SD Card This is used to store the MP3 audio files for the Alert Evac Bell and Message play...

Страница 3: ...Alert tone is activated The terminals provided can be used for Normal or Failsafe modes see section 8 0 for more details Bell 24V Out This is a 24V DC output which is activated when the Bell tone is...

Страница 4: ...s etc These contacts can be set to either continuous or momentary operation via dip switch 1 refer to secton 7 0 In continuous mode the alert tone will continue while the alert contact is triggered In...

Страница 5: ...same manner as the switched 24V out contacts i e connection between the N O contact and the GND contact will operate in NORMAL mode and connection between the N C contact and the GND will operate in...

Страница 6: ...in MP3 format they cannot be Wav files or AAC files NOTE only one MP3 file can be in each folder There is also a folder labelled LIBRARY which contains a host of sample MP3 files The Voice folder cont...

Страница 7: ...ed a PC or laptop equipped with a Micro SD card reader to do this If a Micro SD slot is not available then the Altronics D 0371A USB Memory Card Reader or similar would be suitable not supplied Step b...

Страница 8: ...ted and replaced by the MP3 file you want to play when you activate the Alert mode The MP3 file name is not important But it is important that there is only one MP3 file in the Alert folder Check the...

Страница 9: ...d to the Alert 24V and Evac 24V outputs of the A 4574 The cancel LED is not connected A mimimum of seven wires can be used if the ground connections of the Alert and Evac 24V outputs are linked and if...

Страница 10: ...he Alert Evac and Bell 24V outputs and the grounds of the Alert Evac Chime and cancel switches are linked together see Fig 10 Fig 10 13 0 Troubleshooting E v a c A l e r t C h i m e C a n c e l A 4574...

Страница 11: ...s Make sure the Alert Evac and Bell folders on the Micro SD card have MP3 files in them MP3 Audio files not playing Make sure they are in MP3 format Make sure Micro SD card inserted properly Check MP3...

Страница 12: ...ice OUTPUT LEVEL 0dBm DISTORTION 0 01 FREQ RESPONSE 140Hz 20kHz SIGNAL TO NOISE RATIO Alert Evac Chime 70dB typically OUTPUT CONNECTORS Audio Output RCA Stereo Socket Switched 24V DC Out Screw Termina...

Отзывы: