2.0 WIRING THE TLA

After the unit has been mechanically mounted, it is ready to be wired. All 

wiring connections are made to the rear screw terminals. When wiring the unit, 

use the numbers on the label and those embossed on the back of the case, to 

identify the position number with the proper function. 

All conductors should meet voltage and current ratings for each terminal. 

Also cabling should conform to appropriate standards of good installation, local 

codes and regulations. It is recommended that power supplied to the unit (AC 

or DC) be protected by a fuse or circuit breaker. Strip the wire, leaving 

approximately 1/4" (6 mm) bare wire exposed (stranded wires should be tinned 

with solder). Insert the wire under the clamping washer and tighten the screw 

until the wire is clamped tightly.

Caution: Unused terminals are NOT to be used as tie points. Damage to the TLA 

may result if these terminals are used.

POWER WIRING

AC Power

Primary AC power is connected to terminals #11 and #12, labeled AC. To 

reduce the chance of noise spikes entering the AC line and affecting the TLA, 

an AC feed separate from that of the load should be used to power the TLA. Be 

certain that the AC power to the TLA is relatively “clean” and within the 

variation limit. Connecting power from heavily loaded circuits or circuits that 

also power loads that cycle on and off (contacts, relays, motors, etc.), should be 

avoided.

DC Power

DC Power (18 to 36 VDC) is connected to terminals #11 and #12 labeled 

DC+ and DC- respectively.

CAUTION: Observe proper polarity when connecting DC voltages. 

Damage to the unit may occur if polarity is reversed.

SIGNAL WIRING

Thermocouple

When connecting the thermocouple, be certain that the connections are clean 

and tight. If the thermocouple probe cannot be connected directly to the TLA, 

thermocouple wire or thermocouple extension-grade wire must be used to 

extend the connection points (copper wire does not work). Always refer to the 

thermocouple manufacturer’s recommendations for mounting, temperature 

range, shielding, etc. For multi-probe temperature averaging applications, two 

or more thermocouple probes may be connected to the TLA (always use the 

same type). Paralleling a single thermocouple to more than one TLA is not 

recommended. Generally, the red wire from the thermocouple is negative and 

connected to the TLA’s common.

RTD

When connecting the RTD, be certain that the connections are clean and 

tight. RTD sensors have a higher degree of accuracy and stability than 

thermocouple sensors. Most RTD sensors available are the three wire type. The 

third wire is a sense lead for canceling the effects of lead resistance of the probe. 

Four wire RTD elements may be used by leaving one of the sense leads 

disconnected. Two wire RTD sensors may be used in either of two ways:

A) Attach the RTD to terminals #8 and #10. Install a copper sense wire of the 

same wire gauge as the RTD leads. Attach one end of the wire at the probe 

and the other end to terminal #9. Complete lead wire compensation is 

obtained. This is the preferred method.

B) Attach the RTD to terminals #8 and #10. Install a shorting wire between 

terminals #9 and #10. A temperature offset error of 2.5°C/ohm of lead 

resistance exists. The error may be compensated by programming a 

temperature offset.

Note: With extended cable runs, be sure the lead resistance is less than 15 ohms/

lead. 

RELAY CONNECTIONS

To prolong contact life and suppress electrical noise interference due to the 

switching of inductive loads, it is good installation practice to install a snubber 

across the contactor. Follow the manufacturer's instructions for installation.

Note: Snubber leakage current can cause some electromechanical devices to be 

held ON.

*Terminal numbers are model dependent. See Terminal Configurations for 

description.

REMOTE RESET WIRING

The use of shielded cable is recommended. Follow the EMC installation 

guidelines for shield connection.

Terminal #6 is the Remote Reset. Any form of mechanical switch may be 

connected to terminal #6 (REMOTE RESET) and terminal #8 (COMM.). 

Sinking open collector logic with less than 0.7 V saturation and off-state leakage 

current of less than 1 µA may also be used.

POWER

-

+

CONNECTION

NO

TC

COMM.

USER INPUT

AT

5 AMPS

250 VAC

CONTROLLER

N.O.

LOAD

FUSE

N.C.

AC/DC 

POWER

*
*
*

Thermocouple Connection

RTD Connection

POWER

COMM.

RTD

USER INPUT

RTD

PROBE

Содержание TLA

Страница 1: ...to activate according to a variety of actions Absolute HI or LO Deviation HI or LO and Band IN or OUT with adjustable hysteresis A standby feature suppresses the alarm during power up until the process stabilizes outside the alarm region The unit is constructed of a lightweight high impact plastic case with a tinted front panel The front panel meets NEMA 4X IP65 specifications when properly instal...

Страница 2: ...nel latch Panel latch can be installed for vertical or horizontal instrument stacking One piece tinted plastic bezel Bezel assembly with circuit boards can be removed from the case to change the output board without removing the case from the panel or disconnecting wiring Unit meets NEMA 4X IP65 requirements for indoor use when properly installed Flame resistant Installation Category II Pollution ...

Страница 3: ...ded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter Also Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays transformers and other noisy components 4 Long cable runs are more susceptible to EMI pi...

Страница 4: ... ventilation to ensure that the maximum operating temperature range is not exceeded Caution Disconnect power to the unit and to the output control circuits to eliminate the potential shock hazard when removing the bezel assembly Unit Removal Procedure To remove a unit from the panel first loosen the panel latch screws Insert flat blade screwdrivers between the latch and the case on either side of ...

Страница 5: ...ging applications two or more thermocouple probes may be connected to the TLA always use the same type Paralleling a single thermocouple to more than one TLA is not recommended Generally the red wire from the thermocouple is negative and connected to the TLA s common RTD When connecting the RTD be certain that the connections are clean and tight RTD sensors have a higher degree of accuracy and sta...

Страница 6: ...ode In this mode the process temperature is displayed in the main top display and the limit setpoint is displayed in the secondary bottom display When changes to the parameter configurations are needed the P button is pressed and the TLA will enter into the Parameter Mode PARAMETER CONFIGURATION BASIC STARTUP For basic start up it is important to verify or change Input Parameter Module 1 IN parame...

Страница 7: ...egree resolution If changed be sure to check all parameters FLtr Digital Input Filtering and Display Update Select the relative degree of input signal filtering and display update rate The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes Therefore the influence on step response time is minimal If the signal is varying too greatly due to m...

Страница 8: ...n low acting with positive alarm value d LO deviation high acting with negative value d HI or band inside acting b IN is selected for the alarm action the indicator is OFF when the alarm output is ON See the Alarms section for complete details of each action If changed check alarm values The alarm values are either absolute values or relative to the limit setpoint value deviation and band alarms A...

Страница 9: ...r this flag perform calibration procedure as noted in the Calibration section Alternatively stepping through one of the calibration procedures clears the error flag but does NOT validate the calibration accuracy in any manner USER PARAMETER VALUE CHART TLA Number _____________ MNEMONIC PARAMETER USER SETTING Limit Setpoint Alarm 2 Value Password Alarm 1 Value Input Parameters MNEMONIC PARAMETER US...

Страница 10: ... ON OFF Energized High Trip Action Low Trip Action 5 0 Alarms Optional The alarm action figures describe the status of the alarm output and the front panel indicator for various over under temperature conditions The alarm output wave form is shown with the output in the automatic reset mode Select the alarm action with care in some configurations the front panel indicator LED might be OFF while th...

Страница 11: ...e The TLA display should equal the calibrated probe temperature Tolerance is 1ºC 4 Calibrate the cold junction temperature if out of tolerance RTD Ohms Reading Check 1 Connect RTD simulator with an accuracy of 0 1 ohm or better capable of operating with less than 150 µA to terminals 8 9 10 2 Configure Input Parameters Module 1 for linear ohms rLin input under tYPE 3 Compare the TLA read out with t...

Страница 12: ...rm up period before starting this procedure Do not use thermocouple wire for the millivolt or RTD ohms calibration This procedure may be aborted by disconnecting power to the TLA before exiting the configuration mode The existing calibration settings remain in affect Note After completing any of the calibration sequences the TLA defaults the input sensor type to thermocouple type J tc J Be sure to...

Страница 13: ...ISPLAY 1 Input is below range of TLA 2 Temperature below range of input probe 3 Defective or incorrect transmitter or probe 4 Excessive low temperature for probe 5 Loss of setup parameters OLOL OR ULUL IN LOWER DISPLAY 1 Signal input exceeds allowable range by 5 1 Check remote signal source 1 Check input parameters 2 Change to input sensor with a lower temperature range 3 Replace transmitter or pr...

Страница 14: ...t Board RBDLA210 AL1 LIMIT E B 0 7 8 4 MD1797 A2 A1 OUT EX P OUTPUT BOARD POWER CPU BOARD SUPPLY BOARD OUTPUT BOARD CONNECTOR BEZEL DISPLAY BOARD ASSEMBLY BEZEL BOARD LATCH DISPLAY BOARD CONNECTOR 9 0 Terminal Configurations 50 60 HZ 8VA 14 12 85 250 VAC AC 1 A2 N O 13 COMM COMM A1 N O LIMIT RELAY ALARM RELAYS 4 N O 5 AC 11 2 3 6 REMOTE RESET 9 TC 10 RTD 8 7 COMM 50 60 HZ 9VA AC 24V 10 DC 18 36V 7...

Страница 15: ...15 This page intentionally left blank ...

Страница 16: ...h Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warranties expressed or implied are created with respect to The Company s products except those...

Отзывы: