background image

2

SETTING THE CARD ADDRESS

Each FlexCard contains a four position DIP switch, that is used to set the 

FlexCard address. The address selection must be unique for each FlexCard 

inserted in the PAX2 host. The address is used only for internal data exchange 

between the FlexCard and the host. The address of each FlexCard 

MUST

 be 

set to match the PAX2 host slot location in which the card will be installed. A 

four position dip switch is used to select the address using a binary format. The 

switch settings for address 1, 2, and 3 are shown. 

Note

SET THE ADDRESS PRIOR TO INSTALLING THE CARD.

 

Binary Bit Weights:  8 4 2 1 (Switch 1 to 4)

Address 1

Address 2

Address 3

1 2 3 4

ON

ON

ON

1 2 3 4

1 2 3 4

TOP VIEW

INSTALLATION  

  

CAUTION

: The option card and main circuit board contain static 

sensitive components. Before handling the cards, discharge 

static charges from your body by touching a grounded bare 

metal object. Ideally, handle the cards at a static controlled 

clean workstation. Also, only handle the cards by the edges. 

Dirt, oil or other contaminants that may contact the cards can 

adversely affect circuit operation.

  

WARNING

: Exposed line voltage will be present on the circuit 

boards when power is applied. Remove all power to the unit 

AND load circuits before accessing the unit.

To Install:

1. Remove the main assembly from the rear of the case by squeezing both 

finger tabs on the rear cover at the same time, and pulling the assembly out 

of the case. Or use a small screwdriver to depress the finger tab latches and 

pull the main assembly out of the case. When handling the main circuit 

board assembly, hold it by the rear cover. Do not remove the rear cover from 

the main circuit board.

2. Install applicable standard option cards (PAXCDS, PAXCDC, PAXCDL) 

before continuing.

3. Determine the option slot location in which the FlexCard will be installed.  

The FlexCard may be installed in any available option card slot. Note that 

after the FlexCard top terminal case knock-out is removed from the PAX2 

case (Reference Step 8), only another FlexCard with top terminals should 

be installed in the option slot location.

4. Set the FlexCard Card Address DIP switch to match the option card slot 

position in which it will be installed. Attach the appropriate slot location 

label to the rear of the top terminal block and then remove the top terminal 

block from the FlexCard. 

5. Align the FlexCard rear terminals with the rear cover slot position (address) 

that the FlexCard is being installed.

6. Align the option card connector with the appropriate main circuit board 

FlexCard connector. 

7. Verify that the tab on the option card rests in the alignment slot on the main 

assembly display board.

8. A knock-out on the top of the PAX2 case will need to be removed to allow 

the FlexCard top terminal block connection to be made later. Locate the 

 shaped knock-out, positioned at the installed FlexCard option slot 

location. Carefully remove the knock-out, being careful not to remove 

additional (unused) knock-outs. Trim knock-out (gates) that remain on the 

case.

9. Slide the assembly back into the case. Be sure the rear cover latches, at the 

finger tab, engage in the case.

10. Make output wiring connections to the top terminal block. Install the top 

terminal block by aligning it with the option card and option slot knock-out 

hole. Firmly press the top terminal block to engage the terminal block 

latches. Terminal block should not pull off without depressing the terminal 

block latches. Do not apply power to the controller if the top terminal block 

is not in place.

Finger

Tab

Finger

Tab

Slot #

Alignment

Slots

Standard Card

Connectors

Main

Circuit

Board

1

2

3

FlexBus

Connectors

OUTPUT CONNECTIONS (Top Terminal Block)  

+Vou

t

OUT 

1

OUT 

2

OUT 

3

OUT 

4

CO

MM

PCB Edge Fingers on Card

Removable Terminal Block

(Install through access slot

in top of case)

(front of meter)

1

2

3

4

5

6

6

5

4

3

2

1

COMM

OUT

+Vout

COMM

-

+

LOAD

LOAD

INTERNAL POWER

EXTERNAL POWER

30 VDC

MAX

OUT

Top Terminal Block

Slot ID Label

Rear Terminal Block

Содержание PX2FCA

Страница 1: ... ensures that proper heater current is present when the control output is ON and little or no current is present when the output is OFF This provides indication of a shorted or open heater circuit A direct readout of process heater current can also be displayed if desired Heater current limit values and input scaling are programmed through the host PAX2 meter controller ORDERING INFORMATION MODEL ...

Страница 2: ...e option card slot Note that after the FlexCard top terminal case knock out is removed from the PAX2 case Reference Step 8 only another FlexCard with top terminals should be installed in the option slot location 4 Set the FlexCard Card Address DIP switch to match the option card slot position in which it will be installed Attach the appropriate slot location label to the rear of the top terminal b...

Страница 3: ...iv Input Resistance 5 Ω Accuracy 2 0 full scale 5 to 100 of range Frequency 50 to 400 Hz Overload 200 mA continuous Output on time delay for break alarm 1 second No Connection CT CT No Connection TO HEATER CONTROL LINE CURRENT TRANSFORMER NEUTRAL 120 240 V F1 F2 F3 F4 Rear Terminal Block Voltage Input F1 Current Input Input No Connection F2 F3 F4 0 20 mA Rear Terminal Block Voltage Input Current I...

Страница 4: ...d Red Lion Controls harmless from defend and indemnify RLC against damages claims and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalti...

Отзывы: