WIRING OVERVIEW 

All conductors should meet voltage and current ratings for each terminal. Also, 

cabling should conform to appropriate standards of good installation, local codes 

and regulations. It is recommended that power supplied to the unit be protected 

by a fuse or circuit breaker. As depicted in the drawing of the Model PAXLHV, 

all connections are made on the terminal block located at the rear of the unit.

3.0 w

iring

 

The

 m

eTer

1

2

8

5

POWER

SUPPLY

WAVE

SHAPING

CIRCUIT

PROCES

S

CIRCUITR

Y

CALIBRATION

ADJUSTMENT

+V

1M

DISPLAY

INPU

T

POWE

R

COMMON

(NEUTRAL)

600VAC

(HOT)

The PAX Lite AC Voltage Monitor incorporates a built-in precision 
voltage divider that provides direct measurement from 0 to 600 VAC.

BLOCK DIAGRAM

3.1  POWER WIRING

1

2

AC

AC

115/230

AC Power

Terminal 1: VAC
Terminal 2: VAC

Primary AC  power  is  connected  to  terminal  1  and  2 

(Marked  AC  Power, 

located on the left-hand side of the terminal block)

. For best results, the AC 

power  should  be  relatively  “Clean”  and  within  the  specified  ±10%  variation 

limit.  Drawing  power  from  heavily  loaded  circuits  or  from  circuits  that  also 

power loads that cycle on and off, should be avoided.

Input  connections  are  made  on  terminal  5  and  8.  When  powering  the 

PAXLHV with the same voltage that is being measured, terminal 5 (COMM.) 

should be connected to neutral for the most stable reading on the display. If an 

unstable display results from measuring a voltage that is isolated from the supply 

voltage, reversing the supply voltage connections may correct this condition.

EMC INSTALLATION GUIDELINES

Although  this  meter  is  designed  with  a  high  degree  of  immunity  to 

Electromagnetic  Interference  (EMI),  proper  installation  and  wiring  methods 

must be followed to ensure compatibility in each application. The type of the 

electrical noise, source or coupling method into the meter may be different for 

various  installations.  Cable  length,  routing  and  shield  termination  are  very 

important and can mean the difference between a successful or a troublesome 

installation. Listed below are some EMC guidelines for successful installation 

in an industrial environment.

1. The meter should be mounted in a metal enclosure, that is properly connected 

to protective earth.

2. Use shielded (screened) cables for all Signal and Control inputs. The shield 

(screen)  pigtail  connection  should  be  made  as  short  as  possible.  The 

connection  point  for  the  shield  depends  somewhat  upon  the  application. 

Listed below are the recommended methods of connecting the shield, in order 

of their effectiveness.

a. Connect the shield only at the panel where the meter is mounted to earth 

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually when 

the noise source frequency is above 1 MHz.

c. Connect the shield to common of the meter and leave the other end of the 

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC 

power  lines,  conductors  feeding  motors,  solenoids,  SCR  controls,  and 

heaters,  etc.  The  cables  should  be  run  in  metal  conduit  that  is  properly 

grounded. This is especially useful in applications where cable runs are long 

and portable two-way radios are used in close proximity or if the installation 

is near a commercial radio transmitter.

4. Signal or Control cables within an enclosure should be routed as far as possible 

from contactors, control relays, transformers, and other noisy components.

5.  In  extremely  high  EMI  environments,  the  use  of  external  EMI  suppression 

devices, such as ferrite suppression cores, is effective. Install them on Signal 

and Control cables as close to the unit as possible. Loop the cable through the 

core several times or use multiple cores on each cable for additional protection. 

Install line filters on the power input cable to the unit to suppress power line 

interference.  Install  them  near  the  power  entry  point  of  the  enclosure.  The 

following EMI suppression devices (or equivalent) are recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC #FCOR0000)

TDK # ZCAT3035-1330A

Steward #28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC #LFIL0000)

Schaffner # FN670-1.8/07

Corcom #1VB3

Corcom #1VR3

Note: Reference manufacturer's instructions when installing a line filter.

6. Long cable runs are more susceptible to EMI pickup than short cable runs. 

Therefore, keep cable runs as short as possible. 

3.2  INPUT SIGNAL WIRING

Voltage Input

Terminal 5: Common
Terminal 8: 600 VAC

5

8

V

600V MAX. AC

COMMO

N

600 VAC

Neutra

l

Содержание PAX Lite PAXLHV

Страница 1: ... is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired DEFINITION OF TERMS INSTALLATION CATEGORY overvoltage category I Signal level special equipment or parts of equipment telecommunication electronic etc with smaller transient overvoltages than Installation Category overvoltage category II INSTALLATION CATEGORY overvoltage category II Loca...

Страница 2: ...ut Meter Part Numbers Accessories Part Number PAXLBK30 Units Label Kit Accessory PAXLBK Accessories TYPE PART NUMBERS DESCRIPTION MODEL NO Ordering Information 2 General Meter Specifications 3 Accessories 3 Installing the Meter 4 Setting the Switches 4 Wiring the Meter 5 ...

Страница 3: ...9 20041018 Issued by Underwriters Laboratories Inc IEC 61010 1 EN 61010 1 Safety requirements for electrical equipment for measurement control and laboratory use Part 1 IP65 Enclosure rating Face only IEC 529 ELECTROMAGNETIC COMPATIBILITY Emissions and Immunity to EN 61326 Electrical Equipment for Measurement Control and Laboratory use Notes 1 Criterion A Normal operation within specified limits 2...

Страница 4: ...to the back of the bezel The unit should be installed fully assembled Insert the unit into the panel cutout While holding the unit in place push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case The panel latch should be engaged in the farthest forward slot possible To achieve a proper seal tighten the latch screws evenly until the unit i...

Страница 5: ... properly connected to protective earth 2 Use shielded screened cables for all Signal and Control inputs The shield screen pigtail connection should be made as short as possible The connection point for the shield depends somewhat upon the application Listed below are the recommended methods of connecting the shield in order of their effectiveness a Connect the shield only at the panel where the m...

Страница 6: ...6 This page intentionally left blank ...

Страница 7: ...7 This page intentionally left blank ...

Страница 8: ...uyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warranties expressed or implied are created with respect to The Company s products except those ex...

Отзывы: