  HIGH DENSITY ANALOG OUTPUT MODULE FOR THE 

GRAPHITE SERIES

  AVAILABLE OUTPUTS INCLUDE 0 to 5 VDC, 0 to 10 VDC, 

±10 VDC, AND 0/4-20 mA DC

  OUTPUTS ARE ISOLATED FROM EACH OTHER AND FROM 

THE BACKPLANE

  OUTPUTS ARE SOFTWARE CONFIGURED AND FULLY 

SCALABLE

  CAN BE USED IN CONJUNCTION WITH ANY GRAPHITE 

SERIES MODULES

GENERAL DESCRIPTION

The model GMOUT is an analog output module designed for use with the 

Graphite Series. The module provides four isolated outputs that are independently 

programmable for output ranges of 0-5V, 0-10V, +/-10V, 0-20mA, or 4-20mA. 

Internal scaling is provided to accommodate virtually any application.

The modules connect and communicate via proprietary USB connection to 

the various Graphite devices. The Graphite devices, equipped with serial ports 

as well as an Ethernet port(s), allows the system to share data with PCs, PLCs, 

and SCADA systems. The maximum number of modules various for each 

Graphite device, see specific models for details. 

Once programmed, the module will continue to operate/control independent 

of the Graphite device as long as power is applied. Remove power from the host 

device before installing or replacing any modules.

CONFIGURATION

The Graphite Series is configured with Windows

®

 compatible Crimson 

software. The software is an easy to use, graphical interface that provides a 

means of communication configuration, as well as commissioning and 

calibration of new systems.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

manual or on equipment must be observed to ensure personal safety and to 

prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired. 

Do not use the module to directly command motors, valves, or other actuators 

not equipped with safeguards. To do so can be potentially harmful to persons or 

equipment in the event of a fault to the module.

MODEL GMOUT - GRAPHITE™ SERIES 4-CHANNEL 

 

ANALOG OUTPUT MODULE

Bulletin No.  GMOUT-C
Drawing No.  LP0920
Released  07/14

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

4.65

(118)

1.25 (32)

2.97 (76)

DIMENSIONS  In inches (mm)

C

US LISTED

UL

R

IND. CONT. EQ.

34AD

FOR USE IN HAZARDOUS LOCATIONS: 

Class I, Division 2, Groups A, B, C, and D 

Class II, Division 2, Groups F and G 

Class III, Division 2

C

US

UL

R

LISTED

IND.CONT. EQ.

3PWL

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 

EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF 

OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 

COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, 

DIVISION 2

Содержание Graphite Series

Страница 1: ...y to use graphical interface that provides a means of communication configuration as well as commissioning and calibration of new systems SAFETY SUMMARY All safety related regulations local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a ...

Страница 2: ...wer supply 500 V 50 60 Hz for 1 minute between any of the outputs and the Host power supply input 6 ENVIRONMENTAL CONDITIONS Operating Temperature Range 40 to 75 C limited to host Storage Temperature Range 40 to 85 C Operating and Storage Humidity 85 max relative humidity non condensing from 40 to 75 C Altitude Up to 2000 meters 7 CERTIFICATIONS AND COMPLIANCES CE Approved EN 61326 1 to Industrial...

Страница 3: ...s short as possible 5 In extremely high EMI environments the use of external EMI suppression devices such as Ferrite Suppression Cores for signal and control cables is effective The following EMI suppression devices or equivalent are recommended Fair Rite part number 0443167251 RLC part number FCOR0000 TDK part number ZCAT3035 1330A Steward part number 28B2029 0A0 Line Filters for input power cabl...

Страница 4: ...r any affirmation promise or representation with respect to the products The customer agrees to hold Red Lion Controls harmless from defend and indemnify RLC against damages claims and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its e...

Отзывы: