2
SPECIFICATIONS
1.
POWER
: Derived from system backplane. (CSOUT draws 180 mA max. load
on power input of MASTER). Modules may be hot-swapped (replaced while
powered up).
2.
LEDs
:
STS
- Status LED shows module condition.
ALM
- Alarm LED is lit when an internal alarm condition exists.
3.
MEMORY
: Non-volatile memory retains all programmable parameters.
MASTER also stores the parameters in order to reprogram modules that
are replaced.
4.
COMMUNICATIONS
: Provided by the CS Master
5.
OUTPUTS
:
Channels
: 4 independent outputs
Response Time
: 25 msec max. to within 99% of final value
Output Range
: software selectable
OUTPUT RANGE
ACCURACY *
18 to 28
°
C
10 to 75% RH
ACCURACY *
0 to 50
°
C
0 to 85% RH
COMPLIANCE
RESOLUTION
0 to 5 VDC
0.2% of span
0.4% of span
10K
min.
1/30,000
0 to 10 VDC
0.1% of span
0.2% of span
10K
min.
1/60,000
-10 to +10 VDC
0.1% of span
0.2% of span
10K
min.
1/60,000
0 to 20 mA
0.1% of span
0.2% of span
500
max.
1/60,000
4 to 20 mA
0.1% of span
0.2% of span
500
max.
1/48,000
* The accuracy is specified after 20 minutes warmup; in a non-condensing
environment; and includes linearity errors.
6.
ISOLATION LEVEL
: The outputs are isolated from each other, and are
isolated from the power supply. 500 V @ 50/60 Hz for 1 minute between any
of the outputs and the CS Master power supply input.
7.
ENVIRONMENTAL CONDITIONS
:
Operating Temperature Range
: 0 to +50 °C
Storage Temperature Range
: -40 to +85 °C
Operating and Storage Humidity
: 85% max relative humidity, non-
condensing, from 0 to +50 °C
Vibration According to IEC 68-2-6
: Operational 10 to 150 Hz, 0.075 mm
amplitude in X, Y, Z direction 1 g.
Shock According to IEC 68-2-27
: Operational 25 g, 11 msec in 3 directions.
Altitude
: Up to 2000 meters
8.
CERTIFICATIONS AND COMPLIANCES
:
SAFETY
Check each module’s specifications to determine system compliance.
UL Listed, File #E302106, UL508, CSA 22.2 No. 14-M05 and File #E179259,
UL61010-1, CAN/CSA-C22.2 No. 61010-1; and File #E317425, ANSI/ISA
12.12.01-2007, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: 2006: Electrical Equipment for
Measurement, Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic discharge
EN 61000-4-2 Criterion B
4kV contact discharge
8kV air discharge
Electromagnetic RF fields
EN 61000-4-3 Criterion A
10V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
1 V/m (2 GHz to 2.7 GHz)
Fast transients (burst)
EN 61000-4-4 Criterion B
power 2kV
I/O signal 1kV
Surge
EN 61000-4-5 Criterion B
power 1 kV L to L, 2 kV L to G
signal 1 kV
RF conducted interference
EN 61000-4-6 Criterion A
3 Vrms
Emissions:
Emissions
EN55011
Class A
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-
recovers.
3. Power supplied from back plane via Master Module.
9.
CONSTRUCTION
: Case body is burgundy high impact plastic. For indoor
use only. Installation Category II, Pollution Degree 2.
10.
CONNECTIONS
: Removable wire clamp screw terminal blocks.
Wire Gage: 28-16 AWG terminal gage wire
Torque: 1.96-2.23 inch/lbs (0.22-0.25 N-m)
11.
MOUNTING
: Snaps on to standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
12.
WEIGHT
: 7 oz (198.4 g)
PORT 3
ETHERNET
B
ISOLATED
A
POWER
SUPPLY
+
-
24VDC
CSMSTR - MASTER
CSOUT400 - ANALOG OUTPUT MODULE
PORT 2
A
COMMUNICATIONS
A
PORT 1
PROGRAMMING
POWER
SUPPLY
C
OUTPUT
CHANNEL 1
4-20mA
0-5V
+/-10V
0-20mA
ISOLATED
V+
V-
I+
I-
0-10V
V-
+/-10V
E
OUTPUT
0-20mA
4-20mA
I+
I-
ISOLATED
CHANNEL 3
0-5V
0-10V
V+
I-
4-20mA
F
ISOLATED
CHANNEL 4
OUTPUT
0-10V
0-20mA
+/-10V
I+
V-
0-5V
V+
V-
+/-10V
D
OUTPUT
0-20mA
4-20mA
I+
I-
ISOLATED
CHANNEL 2
0-5V
0-10V
V+
BLOCK DIAGRAM
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR
AREA IS KNOWN TO BE NON-HAZARDOUS.