SENDING COMMANDS & DATA TO THE GEMINI 5200

When sending commands to the Gemini 5200, a command string must be

constructed. The command string may consist of command codes, value
identifiers, and numerical data. Below is a list of commands and value identifiers
that are used when communicating with the Gemini 5200

COMMAND DESCRIPTION

N (4EH)

Address command; followed by a unit address number 1-15
and one of the following commands.

P (50H)

Transmit per Print Options command.

R (52H)

Reset command; operates on Output(s) assigned to
the channel being reset.

T (54H)

Transmit Value command; operates on display values,
Presets and Scale Factors.

V (56H)

Change Value command; operates on Scale Factors,
and Presets.

D (44H)

Change Display command; operates on display values (E -G).

VALUE IDENTIFIER

DESCRIPTION

MNEMONIC

A (41H)

Preset 1

(PS1)

B (42H)

Preset 2

(PS2)

C (43H)

Scale Factor A

(SFA)

D (44H)

Scale Factor B

(SFB)

E (45H)

Rate A

(CTA)

F (46H)

Rate B

(CTB)

G (47H)

Display C

(CTC)

The command string is constructed by using the above commands and value

identifiers, along with the data values that are required. Data values may or may
not contain the decimal point if a decimal point is programmed into the Gemini
5200. The Gemini 5200 will accept the decimal points, however, it does not
interpret them in any way. Leading zeros can be eliminated, however, all trailing
zeros must be present. For example, if a Scale Factor of 1.0000 is to be sent, the
data value can be transmitted as 1.0000 or 10000. If a “1” is transmitted, the Scale
Factor will be changed to 0.0001.

The Address command is used to allow a command to be directed to a specific

unit in the Serial Communications Loop. Whenever the unit address is zero,
transmission of the Address command is not required. This is done for
applications which do not require more than one Gemini. For applications that
require several units, it is recommended that each unit in the loop be given a
separate address. If they are given the same address, a command such as the
Transmit Value Command, will cause all the units to respond at the same time,
resulting in erroneous data.

The command string is constructed in a specific logical sequence. The Gemini

5200 will not accept command strings that do not follow this sequence. Only one
operation can be performed per command string. Below is the procedure to be
used when constructing a command string.

1. If the Gemini 5200, to which the command is to be sent, is assigned an address

other than zero, the first two characters of the command string must consist of
the Address Command (N) and the address number of the unit (1-15).

2. The next character/s in the command string is the actual command that the

Gemini 5200 is to perform and the value identifier if it pertains to the
command. (A command such as the Transmit per Print Options, “P”,
command does not require a Value Identifier.)

3. If the change command is being used, the next characters in the command

string is the numerical data value.

4. The last character in the command string is the command terminator (*). This

character must be sent in order to tell the Geminis that the command string is
complete, so that they can begin processing the command.

Below are some typical examples of properly constructed command strings.

(EX. 1) Change Preset 1 on the Gemini 5200 with address of 2 to 00123.4.

COMMAND STRING: N2VA1234*

(EX. 2) Have the Gemini 5200, with address of 3, transmit the Rate B value.

COMMAND STRING: N3TF*

(EX. 3) Reset the Rate B outputs of the Gemini 5200 with address of 0.

COMMAND STRING: RF*

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание Astro Line Series

Страница 1: ...THE ASTRO LINE SERIES GEMINI 5200 INSTRUCTION MANUAL Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 2: ...t indication and control requirements The Gemini 5200 which you have purchased has the same high quality workmanship and advanced technological capabilities that have made Red Lion Controls the leader...

Страница 3: ...cale Factors A B 18 20 E Gemini 5200 Programming Example Speed Ratio Application 21 22 IV GEMINI 5200 20 MA CURRENT LOOP COMMUNICATIONS 23 A Communication Format 23 B Sending Commands Data To The Gemi...

Страница 4: ...observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a manner not specified by the manufacturer the protection provide...

Страница 5: ...Rate A or Rate B then the 3 key is pushed to display the Scale Factor for that value Once the Scale Factor is displayed changing the digits can be accomplished by repeatedly pressing the key beneath t...

Страница 6: ...alue is not entered it will time out and the unit will continue to use its previous setting As with the other functions you must press E to record the changes For the data entry modes if you do not pr...

Страница 7: ...B set to 1 0000 1 000500 Preset 1 set to 500 2 001000 Preset 2 set to 1000 DUAL RATE WITH SPEED RATIO FACTORY SETTINGS Keys Struck Display Description 4 1 41 2 Personality selected as DUAL RATE W SPEE...

Страница 8: ...WITH SPEED DRAW FACTORY SETTINGS Keys Struck Display Description 4 1 41 4 Personality selected as DUAL RATE W SPEED DRAW 4 2 42 3 Reset Rate A B outputs 4 3 43 1 Rate B Conversion Factor is Rate Per...

Страница 9: ...cing flexibility DIAGNOSTICS SELF TEST WATCHDOG TIMER The security of the Gemini 5200 is further enhanced by its self test diagnostic and watchdog timer capabilities The diagnostics are concerned with...

Страница 10: ...eft of the sixth digit and above the polarity annunciator This LED will turn on if the capacity of the display 6 digits is exceeded or if the following conditions occur Upon power up the display will...

Страница 11: ...key and the E key is pushed to load the factory settings The factory settings are listed on page 5 and 6 41 1 DUAL RATE INDICATION In this mode the Gemini 5200 operates as two independent rate indica...

Страница 12: ...that corresponds to the mode identifier The right most decimal point digit 1 is never turned on A sign in front of the mode identifier will inhibit leading zero blanking The absence of a sign will ena...

Страница 13: ...t 1 Value serves as the boundary point When the rate value is less than Preset 1 Output 1 is not activated normal phase When the rate value is greater than or equal to the Preset Output 1 is activated...

Страница 14: ...igits will be shown Refer to Programming The Presets Scale Factors And Timed Output Values section for more details about entering Timed Output 2 will be terminated if the unit is manually reset The T...

Страница 15: ...point digit 1 is never turned on A sign in front of the mode identifier will inhibit leading zero blanking The absence of a sign will enable leading zero blanking 65 1 0 65 2 0 0 65 3 0 0 0 LEADING ZE...

Страница 16: ...ly being displayed is accessed by pressing the 3 key To access the Scale Factor of the other rate display value the key would be pushed to change the display to the other value then the 3 key would be...

Страница 17: ...manner updating according to the Minimum Update Time and its input frequency It will not synchronize with the channel that timed out and has an update period of 16 seconds The Display C channel howev...

Страница 18: ...INT LEADING ZERO BLANKING There are six basic modes of decimal point placement for the Display C indicator of the Gemini 5200 The decimal point is placed to the right of the display digit that corresp...

Страница 19: ...channel 51 2 3 6 Output 1 will activate when the rate or display value is below or equal to the Preset 1 value If each output is assigned to a different channel 51 1 4 5 Output 1 will activate when t...

Страница 20: ...hen in boundary mode the Preset 2 Value serves as the boundary point When the rate or display value is less than Preset 2 Output 2 is not activated normal phase When the rate or display value is great...

Страница 21: ...l end its measurement period when it receives the next negative going edge 63 1 0 5 Sec minimum 1 Sec maximum 63 2 1 Sec minimum 2 Secs maximum 63 3 2 Secs minimum 4 Secs maximum 63 4 4 Secs minimum 8...

Страница 22: ...66 3 exception that manual reset is disabled 66 4 PRESET VALUES Whenever the rate or display value equals the Preset Value an output action will occur This action depends on the previously programmed...

Страница 23: ...CHANNELS Since both of the rolls have the same circumference and have gears with the same number of teeth the scaling parameters obtained will apply to both Rate channels A B The unit of display for...

Страница 24: ...mode 6 to assign both outputs to Display C STEP 6 Enter function code 52 Output 1 Termination Mode Select and enter mode 6 for boundary operation Note Since Output 1 is not being used in timed output...

Страница 25: ...splay information or as involved as using a host computer to automatically set up Presets and Scale Factors of a number of Geminis With the Communications Option the following functions can be perform...

Страница 26: ...n of the Address command is not required This is done for applications which do not require more than one Gemini For applications that require several units it is recommended that each unit in the loo...

Страница 27: ...ses with the count rate During this time only one additional command may be sent to the Gemini 5200 This may be done 80 msec after the transmission of the Change Value command After the second command...

Страница 28: ...totheendoftheabovecharacterstring An example of a typical serial transmission 3 CTB 1234 56 CR LF If the Print Request terminal initiates the transmission a 400 msec delay is inserted before the trans...

Страница 29: ...de of the Gemini 5200 A list of the DIP switch positions and their functions are shown in Figure 4 BR0 BR1 BAUD RATE Set up is shown in Figure 4 When changing the Baud Rate the unit should be powered...

Страница 30: ...ations lines are run to an Industrial computer located in the production offices OTHER GEMINIS OR RLC PRODUCTS WITH 20 MA CURRENT LOOP CAN BE CONNECTED IN THE SAME LOOP The drawing below shows the Cur...

Страница 31: ...ing commands to the Gemini the 2Ah must terminate the command NO CARRIAGE RETURNS 0Dh OR LINE FEED 0Ah CHARACTERS SHOULD BE SENT TO THE GEMINI If they are sent the Gemini will not respond to the next...

Страница 32: ...ntended to be mounted into an enclosed panel with a gasket to provide a water tight seal The unit meets NEMA 4 IP65 requirements for indoor use when properly installed Two mounting clips and screws ar...

Страница 33: ...nected to earth ground protective earth 2 Shielded screened cables for Signal and Control inputs with shield drain wire connected to earth ground at the mounting panel only Belden 8451 2 conductor 22...

Страница 34: ...oisy components 5 In very electrically noisy environments the use of external EMI suppression devices suchasferritesuppressioncores iseffective InstallthemonSignaland Control cables as close to the un...

Страница 35: ...t is good installation practice to install a snubber across the contactor Follow the manufacturer s instructions for installation Note Snubber leakage current can cause some electro mechanical devices...

Страница 36: ...BLOCK DIAGRAM Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 37: ...CONNECTIONS CONFIGURATION SWITCH SET UPS FOR VARIOUS SENSOR OUTPUTS See Note 5 Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 38: ...vary in proportion to the variations in the DC OUT terminal voltage which are caused by line voltage and load changes 4 When shielded cable is used the shield should be connected to COMM at the counte...

Страница 39: ...n count ON or OFF time 50 usec LO FRQ Connects damping capacitor for switch contact debounce Limits count speed to 100 cps max Min count pulse ON or OFF time 5 msec See Note 2 S4 HI BIAS Sets input tr...

Страница 40: ...to 100 Hz max and input pulse widths to 5 msec min Lo Bias Input trigger levels VIL 1 5 V VIH 3 75 V Hi Bias Input trigger levels VIL 5 5 V VIH 7 5 V Note Bias levels given are 10 12 VDC They vary pro...

Страница 41: ...0 to 50 C Storage Temperature 40 to 70 C Operating and Storage Humidity 85 max relative humidity non condensing from 0 C to 50 C Altitude Up to 2000 meters 14 CERTIFICATIONS AND COMPLIANCES SAFETY IEC...

Страница 42: ...perly connected or power 1 Check all wiring verify power brown out P ON DISPLAY 1 Data error on power up 1a Press E key b Check all function codes E ON THE DISPLAY 1 Data error detected by processor 1...

Страница 43: ...and wiring for noise sources 4 Incorrect scaling 4 Review scaling parameters Appendix F OUTPUT WILL NOT RESET 1 Front panel reset disabled 1 Check rear panel DIP switch 2 Reset disabled 2 Check funct...

Страница 44: ...play 3 Reset Rate A B Outputs 43 RATE B CONVERSION FACTOR 1 Rate Per Second x1 2 Rate Per Minute x60 3 Rate Per Hour x3600 44 RATE B MINIMUM UPDATE TIME 1 0 5 sec minimum 1 sec maximum 2 1 sec minimum...

Страница 45: ...T 1 TERMINATION MODES Normal Phase Output normally OFF turns ON at preset Reverse Phase Output normally ON turns OFF at preset 3 Terminate at Manual Reset 4 Terminate at Manual Reset End 5 Terminate a...

Страница 46: ...ond x1 2 Rate Per Minute x60 3 Rate Per Hour x3600 63 RATE A MINIMUM UPDATE TIME 1 0 5 sec minimum 1 sec maximum 2 1 sec minimum 2 sec maximum 3 2 sec minimum 4 sec maximum 4 4 sec minimum 8 sec maxim...

Страница 47: ...nnected to Comm Reset Button RST Terminal Enabled Front panel reset can be independently disabled by using the Input Configuration DIP switch Reset Button RST Terminal Disabled This mode has no affect...

Страница 48: ...CTUATION MODES 1 Reset Rate A Output s Reset only affects the output s and does not 2 Reset Rate B Output s change the rate display 3 Reset Rate A B Outputs 4 Reset Display C Output s 5 Reset Display...

Страница 49: ...t 1 to Rate A Output 2 to Display C 6 Outputs 1 2 to Display C 52 OUTPUT 1 TERMINATION MODES Normal Phase Output normally OFF turns ON at preset Reverse Phase Output normally ON turns OFF at preset 3...

Страница 50: ...ute x60 3 Rate Per Hour x3600 63 RATE MINIMUM UPDATE TIME 1 0 5 sec minimum 1 sec maximum 2 1 sec minimum 2 sec maximum 3 2 sec minimum 4 sec maximum 4 4 sec minimum 8 sec maximum 5 8 sec minimum 16 s...

Страница 51: ...Terminal connected to Comm Reset Button RST Terminal Enabled Front panel reset can be independently disabled by using DIP switch Reset Button RST Terminal Disabled This mode has no affect on the RST A...

Страница 52: ...S The number of units revolutions feet 10ths of feet meters etc that would be acquired after the Number of Pulses has occurred NUMBER OF PULSES The Number of pulses required to achieve the number of D...

Страница 53: ...lays For example if the Gemini 5200 was set up in mode 41 2 Dual Rate with Speed Ratio and the rate indicators were programmed to indicate rate with no decimal point With actual rates of 1 5 PPS for R...

Страница 54: ...Factor SF In order to acquire the maximum amount of significant digits for the Scale Factor Formula 2 is used and a Scale Multiplier value of 0 1 is selected SF KT SCM SF 0 144643 0 1 1 4464 The Scale...

Страница 55: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 56: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 57: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 58: ...Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 59: ...52 Gemini 5200 No GEM52060 Yes GEM52160 Gemini 5200 Relay Board RLYBD002 For Information on Pricing NEMA Enclosures Base Mount Kits Panel Adapter Kits refer to the Red Lion Controls Catalog or contact...

Страница 60: ...This page is intentionally left blank Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 61: ...This page is intentionally left blank Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 62: ...This page is intentionally left blank Buy www ValinOnline com Phone 844 385 3099 Email CustomerService valin com...

Страница 63: ...and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matter...

Отзывы: