-46-
APPENDIX “E” - PROGRAMMABLE FUNCTIONS
Programming of the IMS is divided into modular steps. Each module is a
short sequence of data entries. The front panel buttons
“UP”
and
“DOWN”
,
(shown as “arrows” on the front panel)
are used to change the data and
set-ups, while the
“P”
button is used to
save
or
enter
the data. After pressing
“P”
which gains entry into the programming mode, the programming
modules are identified by the message
“Pro”
and a number in the display.
“UP”
and
“DOWN”
are used to select the desired programming module and
“P”
is used to enter it. All of the subsequent programming steps follow the
same procedure. The rear terminal labeled
“PGM. DIS.”
must be
ungrounded to gain access to programming. The following table lists the
programming steps.
“Pro 0” - RETURN TO MEASUREMENT MODE
“Pro 1” - SCALE UNIT BY APPLYING SIGNAL
“dECPNt”
-
Enter decimal point for scaled display
“round”
-
Enter rounding factor and trailing zeros for scaled display
“SCALE”
-
*
“dSP 1”
-
Enter display reading for scaling point #1
“INP 1”
-
Apply signal level for scaling point #1
“dSP 2”
-
Enter display reading for scaling point #2
“INP 2”
-
Apply signal level for scaling point #2
“SEGt”
-
*
“Pro 2” - SCALE UNIT BY KEY-IN SIGNAL LEVEL
“dECPNt”
-
Enter decimal point for scaled display
“round”
-
Enter rounding factor and trailing zeros for scaled display
“SCALE”
-
*
“dSP 1”
-
Enter display reading for scaling point #1
“INP 1”
-
Enter signal level for scaling point #1
“dSP 2”
-
Enter display reading for scaling point #2
“INP 2”
-
Enter signal level for scaling point #2
“SEGt”
-
*
*
- Entire sequence for this modular step is not shown (see respective programming
module for further details).
**
- This sequence may be subject to being locked-out due to other programmed sequences.
“Pro 3” - PROGRAM FUNCTIONS ACCESSIBLE WITH FRONT
PANEL LOCKOUT ENGAGED
“dSP AL”
-
Enable display alarms
“ENt AL”
-
Enable enter alarms
**
“dSPHYS”
-
Enable display hysteresis
“ENtHYS”
-
Enable enter hysteresis
**
“rSt AL”
-
Enable reset latched alarms
“dSPbUF”
-
Enable display of peak/valley readings
“rStbUF”
-
Enable reset of peak/valley readings
**
“SELdSP”
-
Enable switching display between input and total
“rSttOt”
-
Enable reset total
“tArE”
-
Enable re-zero (tare) of input signal
“Pro 4” - PROGRAM DIGITAL FILTERING AND REMOTE INPUT
FUNCTION
“FILter”
-
Enter level of digital filtering
0
-
no digital filtering
1
-
normal filtering
2
-
increased filtering
3
-
maximum filtering
“E1-CON”
-
Enter function of remote input
0
-
re-zero input
1
-
reset total
2
-
reset and gate totalizer
3
-
gate totalizer
4
-
display hold
5
-
reset peak/valley
6
-
reset peak and start peak indicator
7
-
reset valley and start valley indicator
8
-
reset latched alarms
9
-
reset all alarms
10
-
toggle display between input and total
11
-
re-zero input and totalize the tared values
12
-
display hold with tare
13
-
instrument reading synchronization
14
-
print request
“E2-CON”
-
Same functions as E1-CON