red lion APLPT Скачать руководство пользователя страница 6

For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com

6

BREAD BAKING APPLICATION

Loaves of bread are being baked in a continuous baking oven. It has been

determined that 10 minutes and 30 seconds is normally required for a loaf to
progress through the oven (this provides enough time for the loaves to be
baked). An RPGC, with 60 PPR, is attached to one of the conveyor belt shafts.
When the conveyor belt moves at the 10 min.-30 sec. rate, the shaft turns at 35
RPM. An APLPT5 is used to display the value of 10 min. and 30 sec. Using
the formula, the required DIP switch settings are obtained.

PPS = 60 PPR x 35 RPM = 2100 PPM ÷ 60

DMIT = D.R. x P.P.S.

PPS = 35

= 630 x 35

DR = 10 min. & 30 sec. (convert min. to sec.)

DMIT = 22,050

DR = (10 min. x 60) + 30

DMIT = 22,050 ÷ 10

*

DR = 630

DMIT = 2,205

* A scale multiplier of 10 is selected because a value greater than 16,383 is

required.

DIP switch 12 .  .  .  .  . -

2048

Needed  =

157

DIP switch  8 .  .  .  .  . -

128

Needed  =

29

DIP switch  5 .  .  .  .  . -

16

Needed  =

13

DIP switch  4 .  .  .  .  . -

8

Needed  =

5

DIP switch  3 .  .  .  .  . -

4

Needed  =

1

DIP switch  1 .  .  .  .  . -

1

Therefore, DIP switches 1, 3, 4, 5, 8, and 12 must be turned “ON”. Also, DIP

switch 4 on the side panel must be set “ON” to get a multiplier value of 10.

DISPLAY MULTIPLIER SELECTION PROCEDURE

The APLPT/PBLPT has a Display Multiplier Selection range from 1 to

16,383. For the minimum scaled reading, the X1 DIP switch would be set to
“ON”. For the maximum scaled reading (16,383 times the measured time
between input pulses), all of the rear panel DMIT DIP switches would be turned
“ON”. Therefore, a specific Display Multiplier Increment Total is achieved by
adding up the appropriate individual display multiplier values.

Also available are four scale multiplier (SM) values of X1, X10, X100, and

X1000, which are controlled by DIP switches 4 and 5 on the side of the unit.
The X10, X100, and X1000 scale multiplier values can be used when the
required DMIT exceeds 16,383. 

Note: Always use the smallest SM value

possible

. Below is a formula to compute the DMIT. 

Note: This same basic

formula applies to all units.

However, for the APLPT5/PBLPT5 the D.R. must

be converted to a base unit of measurement.

DMIT = D.R. x P.P.S.
DMIT = Display Multiplier Increment Total
DR = Desired Reading (In hrs., mins., sec., days, etc.)
PPS = Pulses Per Second (input)

NOTES:

1. For the APLPT5/PBLPT5, the display value must be converted to its base

units. To do this, multiply the value to the left of the dash by 60 and add it to
the value to the right of the dash.

2. If the required DMIT value exceeds 16,383, then a scale multiplier value

greater than 1 will be needed. But always use the smallest SM possible.

EXAMPLE 1 (for APLPT4):

DESIRED READING = 18 minutes
PULSES PER SECOND = 450 pulses per second
DMIT = 18 x 450 P.P.S.

= 8100

DMIT = 8100

The required DMIT does not exceed 16,383, therefore, use a value of 1 for

the S.M.

The appropriate display multiplier switches (which together add up to 8100),

are then set to “ON”. Start by selecting the first increment which is greater than
half the desired DMIT, and add subsequent increments that are more than half
the difference needed.

DMIT = 8100

DIP switch 13 .  .  .  .  . -

4096

Needed  =

4004

DIP switch 12 .  .  .  .  . -

2048

Needed  =

1956

DIP switch 11 .  .  .  .  . -

1024

Needed  =

932

DIP switch 10 .  .  .  .  . -

512

Needed  =

420

DIP switch  9 .  .  .  .  . -

256

Needed  =

164

DIP switch  8 .  .  .  .  . -

128

Needed  =

36

DIP switch  6 .  .  .  .  . -

32

Needed  =

4

DIP switch  3 .  .  .  .  . -

4

Therefore, DIP switches 3, 6, 8, 9, 10, 11, 12, and 13 would be set to “ON”.

Note: If the desired reading is 18.0, the SM can be set for a value of 10. (To get

the D.P. required, the unit must be powered down, then switches 7 and 8 set
appropriately, then powered back up.)

EXAMPLE 2 (for APLPT5):

DESIRED READING = 2 hours and 23 minutes (2-23)
PULSES PER SECOND = 230 pulses per second

First convert the D.R. to its base units.

D.R. = 2 (hours) x 60 + 23

DMIT = 143 x 230 PPS

= 120 + 23

= 32,890

= 143

DMIT = 32,890 ÷ 10

*

DMIT = 3,289

Since the required DMIT does exceed 16,383, a value of 10 is used for the S.M.

DMIT = 3289

DIP switch 12 .  .  .  .  . -

2048

Needed  =

1241

DIP switch 11 .  .  .  .  . -

1024

Needed  =

217

DIP switch  8 .  .  .  .  . -

128

Needed  =

89

DIP switch  7 .  .  .  .  . -

64

Needed  =

25

DIP switch  5 .  .  .  .  . -

16

Needed  =

9

DIP switch  4 .  .  .  .  . -

8

Needed  =

1

DIP switch  1 .  .  .  .  . -

1

Therefore, DIP switches 1, 4, 5, 7, 8, 11, and 12 would be set to “ON” for a

display of 2-23. DIP switch 4 on the side panel must be set to “ON” to obtain
the S.M. value of 10.

Содержание APLPT

Страница 1: ...l DIP switch The units can accommodate magnetic pickups logic sensors and NPN open collector sensors as well as switch contact closure sensors These units have a self test feature which checks all the...

Страница 2: ...n current sink or source sensor by connecting the appropriate terminals in common S3 on the APLPT PBLPT should be turned OFF since pull up or pull down resistors are already present in the counter The...

Страница 3: ...PT4 PBLPT4 the proper DIP switches must be selected before the unit is powered up To change a decimal point location the unit must be powered down the DIP switches changed then powered up The decimal...

Страница 4: ...ction Install line filters on the power input cable to the unit to suppress power line interference Install them near the power entry point of the enclosure The following EMI suppression devices or eq...

Страница 5: ...stort and not provide a water tight seal Recommended minimum panel thickness is 1 8 After the panel cut out has been completed and deburred carefully slide the panel gasket over the rear of the unit t...

Страница 6: ...basic formula applies to all units However for the APLPT5 PBLPT5 the D R must be converted to a base unit of measurement DMIT D R x P P S DMIT Display Multiplier Increment Total DR Desired Reading In...

Страница 7: ...talog or contact your local RLC distributor APLPT DESCRIPTION MODEL NO PART NUMBERS FOR AVAILABLE SUPPLY VOLTAGES ORDERING INFORMATION PBLPT500 PBLPT400 115 230 VAC Apollo 5 Digit Process Time Module...

Страница 8: ...or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be...

Отзывы: