INSTALLATION ENVIRONMENT

The unit should be installed in a location that does not exceed the maximum

operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.

The bezel should be cleaned only with a soft cloth and neutral soap product.

Do NOT use solvents.

Continuous exposure to direct sunlight may accelerate the aging process of

the bezel.

INSTALLATION

PBLPT installation information is contained in the LDD Bulletin. Refer to

that bulletin for instructions on installing the module.

The unit meets NEMA 4/IP65 requirements for indoor use, when properly

installed. The Apollo Indicators are intended to be mounted into an enclosed
panel with a gasket to provide a water-tight seal. Two mounting clips and
screws are provided for easy installation. Consideration should be given to the
thickness of the panel. A panel which is too thin may distort and not provide a
water-tight seal. (Recommended minimum panel thickness is 1/8".)

After the panel cut-out has been completed and deburred, carefully slide the

panel gasket over the rear of the unit to the back of the bezel. Insert the unit into
the panel. As depicted in the drawing, install the screws into the narrow end of
the mounting clips.

Thread the screws into the clips until the pointed end just protrudes through

the other side. Install each of the mounting clips by inserting the wide lip of the
clips into the wide end of the hole,
located on either side of the case. Then
snap the clip onto the case.

Tighten the screws evenly to apply

uniform compression, thus providing a
water-tight seal.

CAUTION: Only minimum pressure is

required to seal panel. Do NOT
overtighten screws.

CONNECTIONS & CONFIGURATION SWITCH SET-UP FOR VARIOUS SENSOR OUTPUTS

MAGNETIC PICKUPS

SENSORS WITH CURRENT SINK OUTPUT (NPN O.C.)

[Includes ASTC, LMPC, PSAC, RPGC, (RPGB, RPGH) 

*

, LSC]

SENSORS WITH CURRENT SOURCE OUTPUT (PNP O.C.)

TWO WIRE PROXIMITY SENSORS

SENSORS WITH

A.C. INPUTS FROM TACH.

INPUT FROM CMOS & OTHER

INPUT FROM TTL

-EF OUTPUT

GENERATORS, INVERTERS,

BI-POLAR OUTPUTS

ETC.

INPUT FROM CONTACT CLOSURES

Use 2-wire shielded cable for magnetic pickup signal leads.

Содержание APLPT

Страница 1: ...l DIP switch The units can accommodate magnetic pickups logic sensors and NPN open collector sensors as well as switch contact closure sensors These units have a self test feature which checks all the...

Страница 2: ...n current sink or source sensor by connecting the appropriate terminals in common S3 on the APLPT PBLPT should be turned OFF since pull up or pull down resistors are already present in the counter The...

Страница 3: ...PT4 PBLPT4 the proper DIP switches must be selected before the unit is powered up To change a decimal point location the unit must be powered down the DIP switches changed then powered up The decimal...

Страница 4: ...ction Install line filters on the power input cable to the unit to suppress power line interference Install them near the power entry point of the enclosure The following EMI suppression devices or eq...

Страница 5: ...stort and not provide a water tight seal Recommended minimum panel thickness is 1 8 After the panel cut out has been completed and deburred carefully slide the panel gasket over the rear of the unit t...

Страница 6: ...basic formula applies to all units However for the APLPT5 PBLPT5 the D R must be converted to a base unit of measurement DMIT D R x P P S DMIT Display Multiplier Increment Total DR Desired Reading In...

Страница 7: ...talog or contact your local RLC distributor APLPT DESCRIPTION MODEL NO PART NUMBERS FOR AVAILABLE SUPPLY VOLTAGES ORDERING INFORMATION PBLPT500 PBLPT400 115 230 VAC Apollo 5 Digit Process Time Module...

Страница 8: ...or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be...

Отзывы: