2-10
N-Tron® Series 300 TX/FX Models User Guide
Installation
Revised 2015-12-04
ATEX
Installation
Requirements
This section provides guidance for an installation to meet ATEX certification requirements.
1.
The conductor size of the phase conductor must be in the range of 16-28AWG (0.08mm²-1.31mm²).
2.
Field wiring must be suitable for a minimum of 110°C.
3.
Ethernet Switches are intended for mounting in an ATEX-Certified IP54 enclosure in a pollution degree 2
environments as defined by IEC 60664-1.
4.
Temperature testing of the Ethernet Switches was conducted on the switch itself in an 85°C air circulating
oven and resulted in a Temperature Code of T4. However, end-product temperature testing shall be
considered.
5.
The end user shall provide bonding means as necessary. All bonding equipment (components) shall be
evaluated according to EN 60079-15:2010 and covered by a component certificate for the actual use. When
installing bonding components that will pass through an enclosure wall, they must have a minimum of IP54
rating equal to the enclosure. All electrical clearances must be maintained per the manufacturer’s instructions
of the bonding component or per EN 60079-15:2010.
6.
Ethernet Switch requires protection against transients. The end-product shall provide a suitable form of
protection that removes the risk of or limits transients to no more than 42V.
7.
Products are evaluated to EN 60079-0:2012 and EN 60079-15:2010.
WARNING:
Disconnect the power cable before removing the enclosure top.
AVERTISSEMENT:
Débranchez le câble d'alimentation avant de retirer le boîtier supérieur.
WARNING:
Do not operate the unit with the top cover removed.
AVERTISSEMENT :
Ne pas faire fonctionner l'unité avec le capot retiré.
II 3 G EX nA IIC Gc