UMP Replacement Instructions
Fuel Compatibilities
6
When using a Red Jacket IQ
TM
Control Unit with an UMP containing a Faradyne motor, IQ software 805-001C
(Version3.2) or newer, is required for proper operation of the system. The UMPs will have an ‘FM’ designation
printed on the UMP shell. Software upgrade kit part number is 410600-001.
Table 3. Electrical Service Information (For UMPs Containing A Faradyne Motor With End View B) - For STPs With UL,
cUL, 03ATEX0237289X, 04ATEX0330285X Or 06ATEX6050X Markings
Required power supply rating for 60 Hz, 1 phase pumps is 208 - 230 Vac. For 50 Hz, 1 phase pumps, required rating is 220 - 240 Vac. For
3 phase pumps, required rating is 380 - 415 Vac.
UMP Model No.
HP
Hz
PH
Voltage
Fluctuation
Range
Max.
Load
Amps
Locked
Rotor
Amps
Winding Resistance (Ohms)
Capacitor Kit (µF)
Min.
Max.
Black-
Orange
Red-
Orange
Black-Red
AGUMP33S1,
UMP33U1
1/3
60
1
200
250
4.0
10
8.9 - 10.8
11.5 - 13.9
20.2 - 24.5
144-224-5 (17.5)
AGUMP75S1,
UMP75U1
3/4
60
1
200
250
6.5
19
4.7 - 5.7
7.1 - 8.6
11.7 - 14.1
410164-001 (17.5)
AGUMP150S1,
UMP150U1
1-1/2
60
1
200
250
10.5
33
2.8 - 3.4
6.8 - 8.2
9.4 - 11.3
410164-002 (25)
X3AGUMP150S1,
X3UMP150U1
1/1/2
60
1
200
250
10.5
33
2.8 - 3.4
6.8 - 8.2
9.4 - 11.3
410164-002 (25)
AGUMP200S1-3,
AGUMPL200S1-3,
UMP200U1-3,
UMPL200U1-3
2
60
1
200
250
11.4
44
1.9 - 2.3
3.4 - 4.1
5.1 - 6.2
410164-003 (40)
AGUMP75S3-3,
UMP75U3-3
3/4
50
1
200
250
5.8
18
5.2 - 6.3
10.3 - 12.5
15.4 - 18.6
410164-001 (17.5)
AGUMP150S3-3,
UMP150U3-3
1-1/2
50
1
200
250
10
31
2.8 - 3.4
13.4 - 16.3
16.1 - 19.5
410164-002 (25)
X4AGUMP150S3,
X4UMP150U3
1-1/2
50
1
200
250
10
31
2.8 - 3.4
13.4 - 16.3
16.1 - 19.5
410164-002 (25)
AGUMP200S3-4,
UMP200U3-4
2
50
1
200
250
11
38
2.2 - 2.6
6.0 - 7.3
8.0 - 9.7
410164-003 (40)
Table 4. Electrical Service Information (For EN 15268 UMPs Containing A Motor With End View B) - For STPs With UL,
cUL, 03ATEX0237289X, 04ATEX0330285X, 06ATEX6050X Or 12ATEX1247797X Markings
Required power supply rating for 3 phase pumps, required rating is 380 - 415 Vac.
UMP Model No.
HP
Hz
PH
Voltage
Fluctuation
Range
Max.
Load
Amps
Locked
Rotor
Amps
Winding Resistance (Ohms)
Setting on Motor
Protection Device
Min.
Max.
Black-
Orange
Red-
Orange
Black-Red
AGUMP75S17-3,
UMP75U17-3
3/4
50
3
342
457
2.2
8.1
24.4 - 29.6
24.4 - 29.6
24.4 - 29.6
1.8
AGUMP150S17-3,
UMP150U17-3
1-1/2
50
3
342
457
3.8
14.1
12.1 - 14.7
12.1 - 14.7
12.1 - 14.7
3.8
X4AGUMP150S17,
X4UMP150U17
1-1/2
50
3
342
457
3.8
14.1
12.1 - 14.7
12.1 - 14.7
12.1 - 14.7
3.8
AGUMP200S17-4,
UMP200U17-4
2
50
3
342
457
5.0
17.7
9.9 - 12.0
9.9 - 12.0
9.9 - 12.0
4.5