UMP Replacement Instructions

Warnings and Instructions

3

Prevent Explosions and Fires

Fuels and their vapors will explode or burn, if ignited. Spilled or leaking fuels cause vapors. Even filling customer 
tanks will cause potentially dangerous vapors in the vicinity of the dispenser or island.

Working Alone

It is highly recommended that someone who is capable of rendering first aid be present during servicing. 
Familiarize yourself with Cardiopulmonary Resuscitation (CPR) methods, if you work with or around high voltages. 
This information is available from the American Red Cross. Always advise the station personnel about where you 
will be working, and caution them not to activate power while you are working on the equipment. Use the OSHA 
Lockout/Tagout procedures. If you are not familiar with this requirement, refer to OSHA documentation.

Working With Electricity Safely

Ensure that you use safe and established practices in working with electrical devices. Poorly wired devices may 
cause a fire, explosion or electrical shock. Ensure that grounding connections are properly made. Ensure that you 
do not pinch wires when replacing covers. Follow OSHA Lockout/Tagout requirements. Station employees and 
service contractors need to understand and comply with this program completely to ensure safety while the 
equipment is down. Before you start work, know the location of the Emergency Power Cutoff Switch (the E-
STOP). This switch cuts off power to all fueling equipment and submerged turbine pumps and is to be used in the 
event of an emergency. The buttons on the console at the cashier’s station WILL NOT shut off electrical power to 
the pump/dispenser.   This means that even if you press a button on the console labeled EMERGENCY STOP, 
ALL STOP, PUMP STOP, or something similar, fuel may continue to flow uncontrolled.

Hazardous Materials

Some materials may present a health hazard if not handled correctly. Ensure that you clean hands after handling 
equipment. Do not place any equipment in the mouth.

FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAU-
TIONS COULD RESULT IN PROPERTY DAMAGE, INJURY OR DEATH. 

FIRE HAZARD!

 Do 

NOT

 use 

power tools

 (Class I Division I and Class I Division II) during the installation or 

maintenance of equipment. Sparking could ignite fuel or vapors, resulting in fire.

CHEMICAL EXPOSURE HAZARD!

 

Wear

 appropriate 

safety equipment

 during installation or maintenance of 

equipment. Avoid exposure to fuel and vapors. Prolonged exposure to fuel may cause severe skin irritations and 
possible burns.

REQUIREMENTS FOR USE

• The Red Jacket is designed for use only at facilities dispensing motor fuels.

• Application of The Red Jacket must be consistent with NFPA Code 30A, OSHA regulations, and federal, state 

and local fire codes, and other applicable local regulations.

• The selection of any Veeder-Root product must be based upon physical specifications and limitations and the 

product’s compatibility with the materials to be handled. Veeder-Root makes no warranty of fitness for a 
particular purpose.

• All Veeder-Root products should be used in accordance with applicable federal, state and local laws, 

ordinances and regulations.

OPERATING PRECAUTIONS

NO SMOKING. 

Extinguish all open flames and pilot lights, such as on RV appliances.

TURN OFF

 cell phones and other electronic devices to prevent sparks which could cause an explosion or fire.

WARNING

Содержание Quick-Set AGUMP150S1

Страница 1: ...Manual No 577014 053 Revision D Replacement Instructions Red Jacket UMP Red Jacket Quick Set Submersible Pump...

Страница 2: ...f any damages and or shortages within 30 days of receipt of the shipment as stated in our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Fax Bill of Lading to V R Customer Service at 800 234 5...

Страница 3: ...gure 7 UMP Bolts And Gasket 13 Figure 8 Verifying Pigtail s Female Connector Is Seated Properly In Discharge Head 14 Tables Table 1 Maximum Specific Gravity And Maximum Viscosity 4 Table 2 Electrical...

Страница 4: ...Turn Off power to the device and associ ated accessories when servicing the unit WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION indicates...

Страница 5: ...re your employees and any service contractors read and follow the instructions Follow the Regulations Applicable information is available in National Fire Protection Association NFPA 30A Code for Moto...

Страница 6: ...er s station WILL NOT shut off electrical power to the pump dispenser This means that even if you press a button on the console labeled EMERGENCY STOP ALL STOP PUMP STOP or something similar fuel may...

Страница 7: ...ted for the following fuel compatibility 100 Diesel 100 Gasoline Gasoline and up to 10 Ethanol 15 Methanol 20 MTBE 20 ETBE 20 TAME All models of The Red Jacket with the AG prefix are UL Listed for the...

Страница 8: ...144 224 5 17 5 AGUMP75S1 UMP75U1 3 4 60 1 200 250 6 5 25 2 9 3 6 14 9 18 2 17 7 21 9 410164 001 17 5 AGUMP150S1 UMP150U1 1 1 2 60 1 200 250 10 5 37 2 0 2 5 11 6 14 2 13 5 16 8 410164 002 25 X3AGUMP15...

Страница 9: ...1 1 2 60 1 200 250 10 5 33 2 8 3 4 6 8 8 2 9 4 11 3 410164 002 25 AGUMP200S1 3 AGUMPL200S1 3 UMP200U1 3 UMPL200U1 3 2 60 1 200 250 11 4 44 1 9 2 3 3 4 4 1 5 1 6 2 410164 003 40 AGUMP75S3 3 UMP75U3 3 3...

Страница 10: ...8 505 30 5 13 9 UMP75U17 3 AGUMP75U17 3 3 4 19 1 4 489 19 483 28 12 7 UMP150U1 AGUMP150S1 1 1 2 20 1 2 519 20 5 8 524 34 15 5 X3P150U1 X3AGUMP150S1 1 1 2 21 1 4 540 21 1 2 546 35 15 8 UMP150U3 3 AGUMP...

Страница 11: ...d down line from the pump close it 2 Remove the two extractable lock down nuts and discard them see Figure 2 The springs on the lock down studs between the extractable s flange and the manifold will p...

Страница 12: ...inding occurs during removal stop and determine the cause of the binding and correct the situation before proceeding with removal For all models with the RA suffix take care not to damage the powder c...

Страница 13: ...UMP retaining bolts Use hand force to push the UMP onto the discharge head If the UMP does not seat snug against the discharge head remove the UMP and correct the problem Fasteners are not metric use...

Страница 14: ...nd in the kit Apply anti seize also found in the kit to the lock down studs prior to nut and washer installation 15 Turn the air purge screw 2 3 turns counterclockwise see Figure 2 The air purge screw...

Страница 15: ...ssure to flow into the tank or back out Functional Element screw Confirm that the packer wiring compartment cover plug with lifting eyebolt is properly torqued at 50 ft lbs 70 N m Confirm that the lif...

Страница 16: ...indexing tab of the pigtail is seated in the notch of the discharge head Figure 7 UMP Bolts And Gasket 11 Pull the pigtail connector in the discharge head out far enough to see the o ring in the sidew...

Страница 17: ...nt 15 Replace the packer o ring and discharge Quad seal after lubricating them with petroleum based jelly 16 Reinstall the extractable portion into the tank aligning the positioning dowels of the mani...

Страница 18: ...ressure at line test port 50 psi 345 kPa maximum Excessive pressure above normal test pressure of 50 55 psi 345 380 kPa may damage check valve seat and other system components 4 After completion of li...