1. 

DISPLAY

: 6-digit, 0.56" (14.2 mm), 7-segment LED. 

Decimal points are programmed by front panel keys.

2. 

POWER

AC Power

: 115/230 VAC, switch selectable. Allowable power line variation

±10%, 50/60 Hz, 6 VA. @ 100 mA max.

Isolation

: 2300 Vrms for 1 min. to input and DC Out/In.

DC Power

: 10 to 16 VDC @ 0.1 A max.

3. 

SENSOR POWER

: 9 to 17.5 VDC @ 100 mA max.

4.

KEYPAD

: 3 programming keys, the 

!

(Down Arrow) key can also function

as the front panel reset button.

5. 

INPUT

: (DIP switch selectable)

Accepts pulses from a variety of sources including NPN-OC, PNP-OC, TTL

Outputs, Magnetic Pickups and all standard Red Lion

®

sensors.

Logic

: Input trigger levels V

IL

= 1.5 V max.; V

IH

= 3.75 V min.

Current Sinking

: Internal 7.8 K

pull-up to +12 VDC, I

MAX

= 1.9 mA

Current Sourcing

: Internal 3.9 K

pull-down, 8 mA max. @ 30 VDC max.

MAGNETIC PICK-UP

:

Sensitivity

: 200 mV peak

Hysteresis

: 100 mV

Input impedance

: 3.9K

@ 60 Hz

Maximum input voltage

: ±40 V peak, 30 Vrms

6. 

INPUT FREQUENCY RANGE

Max Frequency

: 25 KHz

Min Frequency

: 0.01 Hz

Accuracy

: ±0.01%

7. 

MEMORY

: Nonvolatile E

2

PROM retains all programmable parameters and

display values.

8. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature

: 0° to 60°C

Storage Temperature

: -40° to 60°C

Operating and Storage Humidity

: 0 to 85% max. relative humidity (non-

condensing)

Vibration According to IEC 68-2-6

: Operational 5 to 150 Hz, in X, Y, Z

direction for 1.5 hours, 2g’s.

Shock According to IEC 68-2-27

: Operational 30 g (10g relay), 11 msec in

3 directions.

Altitude

: Up to 2000 meters

9. 

CERTIFICATIONS AND COMPLIANCES

:

SAFETY

UL Recognized Component, File # E179259, UL61010A-1, CSA C22.2
No. 61010-1

Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc. 

UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95

LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50

IECEE CB Scheme Test Certificate # US/8843A/UL

CB Scheme Test Report # 04ME11209-20041018

Issued by Underwriters Laboratories, Inc.

IEC 61010-1, EN 61010-1:  Safety requirements for electrical

equipment for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for

Measurement, Control and Laboratory use.

Notes:

1. Criterion A: Normal operation within specified limits.
2. EMI filter placed on the DC power supply, when DC powered: Corcom

#1VB3 or Schaffner #FN610-1/07 (RLC #LFIL0000).

10. 

CONNECTIONS

: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)
Wire Gage Capacity: 30-14 AWG copper wire.
Torque: 4.5 inch-lbs (0.51 N-m) max.

11. 

CONSTRUCTION

: This unit is rated for NEMA 4X/IP65 outdoor use.

IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.

12. 

WEIGHT

: 12 oz (340 g)

3

G

ENERAL

M

ETER

S

PECIFICATIONS

1.0 I

NSTALLING THE

M

ETER

Installation 

The PAX meets NEMA 4X/IP65 requirements when properly installed. The

unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel

gasket over the rear of the unit to the

back of the bezel. The unit should

be installed fully assembled.

Insert the unit into the panel

cutout. 

While holding the unit in place, push the panel latch over the rear of the unit

so that the tabs of the panel latch engage in the slots on the case. The panel latch
should be engaged in the farthest forward slot possible. To achieve a proper seal,
tighten the latch screws evenly until the unit is snug in the panel (Torque to
approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.

Installation Environment

The unit should be installed in a location that does not exceed the maximum

operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.

The bezel should be cleaned only with a soft cloth and neutral soap product.

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the

keypad of the unit.

PANEL CUT-OUT

Class B

EN 55011

Emissions

Emissions:

0.5 cycle

Criterion A

EN 61000-4-11

Voltage dip/interruptions

30 A/m

Criterion A

EN 61000-4-8

Power frequency magnetic fields

3 V/rms 

Criterion A

EN 61000-4-6

RF conducted interference

1 kV signal

1 kV L-L, 

Criterion A

2

EN 61000-4-5

Surge 

2 kV signal

2 kV power

Criterion A

2

EN 61000-4-4

Fast transients (burst)

2 kV L&N-E power

10 V/m

Criterion A

EN 61000-4-3

Electromagnetic RF fields

8 kV air discharge

4 kV contact discharge

Criterion A

EN 61000-4-2

Electrostatic discharge

Immunity to Industrial Locations:

Содержание PAXLR000

Страница 1: ...tches Once the programming is complete the front panel buttons can be disabled by a DIP switch setting The meter has been specifically designed for harsh industrial environments With NEMA 4X IP65 seal...

Страница 2: ...ions 3 Installing the Meter 3 Setting the Switches 4 Wiring the Meter 4 Reviewing the Front Buttons and Display 6 Scaling the Meter 6 Programming the Meter 7 ORDERING INFORMATION PAXL 0 0 R0 R0 6 Digi...

Страница 3: ...1 Criterion A Normal operation within specified limits 2 EMI filter placed on the DC power supply when DC powered Corcom 1VB3 or Schaffner FN610 1 07 RLC LFIL0000 10 CONNECTIONS High compression cage...

Страница 4: ...and shield termination are very important and can mean the difference between a successful or troublesome installation Listed below are some EMC guidelines for successful installation in an industria...

Страница 5: ...re Proximity Current Source Current Sinking Output AC Inputs From Tach Generators Etc Magnetic Pickup Emitter Follower Current Source Switch position is application dependent 3 1 POWER WIRING AC Power...

Страница 6: ...ut 15 1 2 With 0 25 pulses per gallon show whole gallons per hour To have greater accuracy multiply both Input and Display values by 10 Scaling Display 36000 Scaling Input 2 5 RATE DISPLAY OVERFLOW Th...

Страница 7: ...s on display updating refer to Input Frequency Calculation The High Update Time is the maximum amount of time before the display is forced to zero The High Update Time must be higher than the Low Upda...

Страница 8: ...sonal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by t...

Отзывы: