The Isolating Switching Amplifiers Model N-132/1-E-10 and
N-132/2-E-10 are associated apparatuses as well as a nonincendive
apparatuses for installation in non-hazardous, Class I, Division 2 or
Zone 2 hazardous (Classified) Locations and provides intrinsically
safe connections for one (or two) field devices located in Class I, II,
III, Division 1, Group A-G or Class I, Zone 0 [AEx ia] Group IIC,
hazardous locations according to NEC Article 504/505 as listed
below.
The Isolating Switching Amplifiers Model N-132/1-10,
N-132/1-01, N-132/2-10, N-132/2-01 and N-132/1(2)-01 are
associated apparatuses located in a non-hazardous location and
provide intrinsically safe connections for one (or two) field
devices located in Class I, II, III, Division 1, Group A-G or Class
I, Zone 0 [AEx ia] Group IIC, hazardous locations according to
NEC Article 504/505 as listed below.
Entity parameters for wiring configurations are as follows:
V
OC
[V]
I
SC
[mA]
P
O
[mW]
L
o
CL. I, Div.1, A,B /
Zone 0, GP. IIC
L
o
CL. I, Div.1, C-G /
Zone 0, GP. IIB
C
o
CL. I, Div.1,A,B /
Zone 0, GP. IIC
C
o
CL. I, Div.1, C-G /
Zone 0, GP. IIB
V
max
I
max
N-132/1-10, N-132/2-10,
N-132/1-01, N-132/2-01,
N-132/1-E-10, N-132/2-E-10
N-132/1(2)-01
input circuits parallel
9.6
9.6
10
20
24
48
350 mH
90 mH
1000 mH
340 mH
3.6 µF
3.6 µF
26 µF
26 µF
-
-
-
-
Notes:
1. Intrinsically safe apparatus may be switches, thermocouples, LEDs, RTDs or an FM Approved System or
Entity device connected in accordance with the manufacturer´s installation instructions.
2. For Entity concept use the appropriate parameters to ensure the following:
V
t
or V
OC
V
max
C
o
, C
a
C
i
+ C
leads
P
o
P
i
I
t
or I
SC
I
max
L
o
, L
a
L
i
+ L
leads
3. Electrical apparatus connected to an intrinsically safe system should not use or generate voltages > 250 V (U
max
).
4. Installation should be in accordance with Article 504/505 of the
National Electrical Code
, ANSI/NFPA 70 and
ANSI/ISA RP 12.06.01
5. Use a general purpose enclosure meeting the requirements of ANSI/ISA S82.02.01 for use in non-hazardous or
Class I, Division 2, hazardous (Classified) locations.
6. Use an FM Approved Dust-ignition proof enclosure appropriate for environmental protection in Class II, Division 1,
Groups E,F and G; and Class III, hazardous (Classified) locations.
7. Each channel shall be installed within a separately shielded cable or a single cable with a separate shield for each channel.
8. These modules are to be mounted on DIN rail, DIN rail with pac-Bus.
The field wiring in any case is connected to the device terminals.
9. Ambient temperature: -
20 °C … +70 °C (any mounting position)
Models N-132/1-E-10 and N-132/2-E-10
(for 24 V DC)
Models N-132/1-10, N-132/1-01, N-132/2-10 and N-132/2-01
and N-132/1(2)-01 (for 120 / 230 V AC or with power relay)
Switching Repeater
Certification drawing