8.3.4 Special Circuitry
a) Circuitry for line fault detection if the contacts at the input are de-energized
Install circuitry for line fault detection in the immediate proximity of the contact.
b) Circuitry with inductive loads at the output
Inductive loads must be connected to a freewheeling diode.
Wiring using a varistor is not recommended.
9
Parameterization and Commissioning
Before commissioning, ensure the following:
• Installation of the device according to regulations.
• Correct connection of the cables.
• No damage at the device and connection cables.
• Tight seat of the screws at the terminals.
Correct tightening torque: 0.5 to 0.6 Nm.
9.1
Replacement of the Device
• If replacing by a device with identical design, readjust the DIP switch, if necessary.
Schematic
15529E
Short-circuit detection:
1 k
O
in series
Open-circuit detection:
10 k
O
parallel
Schematic
15530E
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation before commissioning.
• Comply with national regulations.
1 k
10 k
+
-