Mounting
It is mandatory to have a galvanic connection between the blue (GND) wire and the earthed container
(or additional electrode)! With non-metal containers the connection to the BE electrode is made by
means of a direct cable connection to the blue wire of the cable.
The probe can also be installed up-side down.
Electrical version
5-wire DC
Output function for KFI-5-1...ETW
1 limit value switching point, normally open
Output function for KFI-5-2...ETW
2 limit value switching points, normally open
Operating voltage (U
B
)
15...30 V DC
Permitted residual ripple max.
5 %
Output current max. (I
e
)
100 mA
Power consumption max. (outputs no-load)
0,9 W
Permitted ambient temperature
-25...+70°C
LED-Display
Green
Protective circuit
Built-in
Degree of protection IEC 60529
IP 67
Norm
EN 60947-5-2*
Connection cable
2 m, PVC, 5 x 0,34 mm²
Technical Data
*Where applicable
For further technical data: See data sheet
BE
KFI-5-1(2)-ETW
≥
15 mm
D
¼D
IB2
M
IB1
1/3D,
min. 50 mm
IB3
Measuring area (M) non-active range 1 (IB1) non-active range 2 (IB2) non-active
range 3 (IB3)
The measuring range must not be mounted in the area of the container where
there is a change in the cross section; for example the cone.
The probe can be mounted in the centre of the container or just off to one side. For a measurement to be independent of the
filling cone, we recommend that the probe be mounted at ¼ of the diameter. The minimum distance between the end of the
measuring range and the container’s lid is 50 mm.
Connect the BE direct to the
blue wire of the cable.