CAPTIVA ZERO CLEARANCE MODEL
(continued)
Captiva Zero Clearance Timber Frame Installation
(continued)
Floor
0 mm
Sides
50 mm
Top
100 mm
Flue Outer
25 mm
CLEARANCES FROM
COMBUSTIBLES
NOTE:
If fire is to be installed off the floor with a 4 sided
trim, use the same A, B, C and D dimensions as shown with
framework included below fire to required height. Ensure
frame is suitable for fire weight.
Plasterboard to run beyond stud as shown,
and to go behind fixing flange on unit.
Min 50mm
clearance
NOTE
MODEL
A
B
C
D
600
885
680
475
1800
900
895
960
475
1800
Frameout Dimensions (in mm)
IMPORTANT
Install unit and
fluing before
plasterboard.
A
A
B
B
C
C
D
(Recommended only)
From hearth
Approx 20mm for
hearth if required.
D
(Recommended only)
HEATER
9