background image

Gas Pressure

 

Check the burner from the test point. This is located on the burner supply pipework on 
Natural Gas models and on the burner injector on L.P.G.models 
 

See appliance data badge for pressure settings 
 
Adjustment of the Burner Gas pressure 

Adjust the pressure at the gas valve if required. 

See valve picture

  

There are two adjustments, High and low setting. These are located at the front of the 
valve at the head of the blue solenoid. 
High adjustment – This is the outer Brass hexagonal nut 
Low Adjustment – This is the inner Red adjustment screw 
 
When adjusting the high setting hold the low adjuster in place otherwise both may 
turn. 
 

Front fascia panel 

Fit front fascia panel onto the fixing screws. 
 

Side reflectors 

Fit side reflectors by tilting on an angle locating base onto fascia panels and placing 
vertical. A retaining clip is already fixed to the firebox to secure reflector in place. 
 

Check the fire is operating correctly and test for spillage of combustion products. 
 
Fitting Trims to Firebox 

Fit the trims to the firebox. The trim brackets are designed to hang over the flange on 
each side of the firebox. Each flange has provision to be moved slightly in or out to 
allow the bracket to fit. The flanges have a raised square near the base of the fire. The 
Velcro pad is fixed to this by removing the backing from one side of the pad and 
pushing firmly in place. Then remove backing from the other side. Repeat on opposite 
side. Hang trim on brackets and check for level then firmly push onto Velcro pads. 
 

Optional four sided Trims 

Four sided trims are available as an optional extra with the through wall fire. 
This is for use when one or both sides of the fire has a hearth lower than the base of 
the fire. The method of fixing is the same as the standard trim. 
 

Optional glass panel for inside outside installations. 

The through wall fire can be installed through an outside wall with the glass side of 
the fire on the outside. In these situations a second glass panel must be ordered and 
fitted over the existing glass panel at the time of installation. 

Please note Real Fires do not supply any weatherproof flashings for the Through 
wall fire.  
 
Once the installation is complete, instruct the user on the operation of the fire 
and complete commissioning details in Real Fires user manual. 
  

                              

All installations must be certified 

 

Содержание Minimal Range

Страница 1: ...rth Glass side A non combustible hearth must be provided in front of the glass side of the Through wall fire unless the floor is non combustible or the fire is raised a minimum of 300mm above floor le...

Страница 2: ...replace cavity providing minimum clearances are allowed Recessed installation Standard wall linings are not suitable for recessed installation Please contact Real Fires for advice prior to installatio...

Страница 3: ...hen connected joining the two flues into one From the Y piece a single 200 250mm flue is used to the termination of the flue The flue lengths should be installed with the crimped end facing up The Fir...

Страница 4: ...er tray with the vermiculite supplied ensuring the burner tube is completely covered Place the large logs across each other in the centre of the burner and the twigs and coals around them to cover the...

Страница 5: ...o hang over the flange on each side of the firebox Each flange has provision to be moved slightly in or out to allow the bracket to fit The flanges have a raised square near the base of the fire The V...

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ...ilot ignition assembly has been omitted from the drawing It is important to ensure that the logs and coals are not too tightly placed as this will affect heat output Do not place Logs and Coals close...

Страница 10: ......

Отзывы: