background image

 
 
 
 
Installation instructions

 

Firstly the firebox and flue are installed and then the burner is installed. The burner 
may be installed at a later date when all the construction work is complete and the 
hearth is in place. 
 
The firebox is placed on the platform provided and the 10mm gas pipe is pushed 
through the hole in the firebox. The pipe is to be connected to the burner but may be 
left sealed if the burner is to be installed later. Leave enough pipe to connect the 
burner. 
 
When placing the firebox in the timber cavity it is important to ensure it is centred 
correctly

. Centre the firebox from the front flange on the firebox. Not from the 

insulation kit inside the cavity

    

 
Once the firebox is in place ensure it is level and positioned correctly. From the 
positioned fire the flue can be assembled. The flue is in 1200mm lengths with both 
inner and outer flue. Each flue length has a crimped end to join tightly to the next 
length. Each joint must be securely fixed by at least three stainless steel rivets. 
The firebox has two spigots for the two 1200mm x 150/200mm lengths flues to locate 
over. The Y piece is then connected, joining the two flues into one.  
From the Y piece a single 200/ 250mm flue is used to the termination of the flue. 
The flue lengths should be installed with the crimped end facing up. 
 
The Firebox and the flue should be secured by fixing with seismic strapping and/or 
brackets to framing. 
Flue bends are available from Real Fires if the flue needs to be offset. 
Appropriate weatherproof roof flashing/ chimney capping must be used to comply 
with NZS 5261 
 
Once the installation of the firebox and flue is complete, the building work around the 
fireplace can continue. Ensure any timber fitted around the flue and top of firebox has 
a minimum clearance of 25mm. 
  
Looking at the fire from the open side, there will be an electrical lead for the fire from 
the Right hand side of the firebox. It is intended to be connected by an electrician to a 
wall switch facing the room. 

See installation drawing 

( Please ensure the electrical lead is not left beside the firebox and overlooked . It is 
difficult to gain access once the giboard is fixed) 

 
Timber surrounds 

 If a timber surround is to be fitted ensure it meets Real Fires 

minimum requirements. 

See installation drawing 

 

Installation of Real Fires burner into firebox 

The burner is supplied boxed complete with firebox reflectors, fascia panels, 
vermiculite, logs & coals. 
 

Содержание Minimal Range

Страница 1: ...rth Glass side A non combustible hearth must be provided in front of the glass side of the Through wall fire unless the floor is non combustible or the fire is raised a minimum of 300mm above floor le...

Страница 2: ...replace cavity providing minimum clearances are allowed Recessed installation Standard wall linings are not suitable for recessed installation Please contact Real Fires for advice prior to installatio...

Страница 3: ...hen connected joining the two flues into one From the Y piece a single 200 250mm flue is used to the termination of the flue The flue lengths should be installed with the crimped end facing up The Fir...

Страница 4: ...er tray with the vermiculite supplied ensuring the burner tube is completely covered Place the large logs across each other in the centre of the burner and the twigs and coals around them to cover the...

Страница 5: ...o hang over the flange on each side of the firebox Each flange has provision to be moved slightly in or out to allow the bracket to fit The flanges have a raised square near the base of the fire The V...

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ...ilot ignition assembly has been omitted from the drawing It is important to ensure that the logs and coals are not too tightly placed as this will affect heat output Do not place Logs and Coals close...

Страница 10: ......

Отзывы: