6. Command Reference of RPCM CLI
6.9. Command
set output
This command serves to control the outlet by setting various parameters.
Help ask:
set output 0 ?
The return is:
RPCM Commands description:
set output 0-9 description - set output description
set output 0-9 name - set output name
set output 0-9 off - turn off output number 0-9
set output 0-9 on - turn on output number 0-9
set output 0-9 overcurrent - tune overcurrent limits
alarm for alarming
turn off for turning off
set output 0-9 overvoltage - set output overvoltage turn off
turn off configuration
disabled disable it
limit volts 0-65534 set limit in volts
set output 0-9 recognition - set output 0-9 recognition state
off to off
on to on
set output 0-9 recover turn on - set recover turn on after overvoltage
after overvoltage configuration
disabled disable recover turn on
seconds 0-65534 set stabilization delay before turning on
set output 0-9 survival priority - set output turn off on input overload
priority
set output 0-9 help - show this help
Type 'help' to get suggestions
6.9.1 Command
set output description
This command set an outlet description.
Example of use:
set output 0 description "Outlet 0"
The return is:
Description for Output 0 has been updated
Type 'help' to get suggestions
305