3.   once wiring has been routed into the lock cavity, connect 

wire to terminal blocks as shown in Fig. 1. If optional SCS 

and/or DSS features are being used these can also be wired 

at this time as shown in Fig. 1.

4.  Delayed Relock Feature - Should the built-in delayed relock 

feature be required for the installation, a Normally open 

Momentary switch such as an RCI 909 will need to be installed 

and connected to the two blue wires from J2 on the circuit board 

as illustrated in Fig.1. 

 

The delayed relock feature can be used to momentarily 

release the lock and keep it unlocked for a time period from 0 

to approximately 35 seconds. The time delay for this feature 

can be adjusted by carefully turning the potentiometer (R14) 

in a counterclockwise direction to increase delay time. 

Factory setting is zero seconds.

 

NOTE: on the 8320 double-door model the potentiometer in 

the right-hand wiring cavity must be turned clockwise and the 

left one counterclockwise to increase the relock delay.

 

If the delayed relock feature is not required the blue wires 

may be unplugged from the circuit board @ J2. 

 

 

NOTE: If R14 is not set to zero seconds, the lock will enter 

delayed relock mode each time power is applied even if J2 

has been removed.

2

To Ensure Instant Release - All switching devices must be wired 

in between the DC power source and the positive terminal of the 

lock in Fig 2. 

Switching the negative power supply line will not allow the lock to 

release immediately. RCI electromagnetic locks contain Mov’s for 

surge suppression and do not require any additional suppression 

to be added during installation. The installation of diodes across 

the lock input terminals will cause a delay in release.

Fig. 2 – Power Connections 

SWITCH

+

-

INCORRECT

CORRECT

+

-

SWITCH

FILTERED DC SUPPLY

FILTERED DC SUPPLY

Fig.1 – Lock Wiring

8310 & 8320 Electromagnetic Lock

Installation Instructions 

(Continued)

Delayed Relock Adjustment R14

Turn counterclockwise to increase delay

(Turn clockwise to increase delay on the right

end board of the 8320 Double lock)

Common

Normally Closed 

Normally Open

- Common Ground

 VCC Input

}

}

Lock Power from a 

filtered and regulated DC 

power supply

Optional SCS Sensor

SPDT Output contacts rated 

for maximum 2A @24VDC

J2 

J2 

Two 8310 Locks to release together using

the delayed relock feature.

Blue Wires

Momentary Switch

Both sides of an 8320 Lock to release together

using the delayed relock feature.

Left circuit board

Right circuit board

Optional Delayed Relock Wiring

Single lock to release using

the delayed relock feature.

RED - Normally Closed

GREEN - Normally Open

BLACK - Common

Optional DSS reed switch contacts rated at 

0.20A@12VDC and 0.12A @ 24VDC

Both the SCS and DSS options are shown with Door Open

Blue/White

   Wires

Blue Wires

Blue/White

   Wires

-

+

-

+

J2 

J2 

Momentary Switch

N/O 

N/O 

J2 

Momentary Switch

Blue Wires

Blue/White

   Wires

-

+

N/O 

Blue Wires

Blue/White

   Wires

Blue Wires

Blue/White

   Wires

-

+

-

+

Содержание 8310

Страница 1: ...rations available with this product a survey and assessment of the physical area in which the product will be installed must be performed 3 The door frame must be inspected and deemed structurally sound prior to installation of the electromagnetic lock The structural integrity of the mounting surfaces must be strong enough to meet or exceed the holding force of the product 4 The product must be pr...

Страница 2: ...inal of the lock in Fig 2 Switching the negative power supply line will not allow the lock to release immediately RCI electromagnetic locks contain MOV s for surge suppression and do not require any additional suppression to be added during installation The installation of diodes across the lock input terminals will cause a delay in release Fig 2 Power Connections SWITCH INCORRECT CORRECT SWITCH F...

Страница 3: ... at the bolt There should be no movement to the mounting bracket or housing of the electromagnetic lock For added safety thread locking compound has been provided for the armature plate bolt and the four captive electromagnetic lock mounting screws WARNING Improper installation maintenance inspection or usage of the product or any related accessories or parts may cause the electromagnetic lock arm...

Страница 4: ...cted releasing devices lock terminals and lock circuit board to magnet core Check delayed relock wiring and time setting Check that the momentary switch does not include a shunted light option Lock has enough holding force to lightly hold a screwdriver or set of pliers but door will not lock Check to see that armature plate is correctly aligned with the electromagnetic lock If there is improper al...

Страница 5: ...ere there is insufficient frame depth to mount the lock Available in several different sizes and finishes L Bracket Required wherever there is insufficient space on the frame header to mount the lock The lock mounts to the underside of the L bracket and the L bracket then gets mounted to the doorframe Available in several finishes Glass Door Bracket Allows an armature plate to be mounted to a glas...

Страница 6: ...ide extra mounting space in a hollow metal or wood frame where the door stop of the frame is not thick enough to allow a lock to be installed Available in several different heights and widths Spacer Bars For use when an obstruction in the door prevents the installation of the armature plate at a proper height If the armature plate needs to be lowered then a spacer bar can be used to lower the lock...

Страница 7: ...10 1000 14 10 10 1500 12 10 Total One Way Length of 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A Wire Run ft 100 20 18 16 14 14 12 12 10 150 18 16 14 12 12 12 10 200 16 14 12 12 10 10 250 16 14 12 10 10 10 300 16 12 12 10 10 400 14 12 10 500 14 10 10 750 12 10 1000 10 1500 10 Load Current 24V Load Current 12V Wire Gauge Chart courtesy of Electronic Locking Devices by John L Schum WIRE GAUGE SELECTIONS 7 ...

Страница 8: ...CATION DATE NOTES INITIAL 8310 8320 Electromagnetic Lock Installation Instructions Continued 2017 Rutherford Controls Int l dormakaba Group www rutherfordcontrols com Phone 1 800 265 6630 Fax 1 800 482 9795 E mail sales rutherfordcontrols com ...

Отзывы: