background image

SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS

Page 5

WARNING: Failure to maintain minimum
clearances between vent connectors and any
combustible material can result in a fire causing
extensive property damage, severe personal
injury or death!

To determine the appropriate power venter for the boiler/
water heater, see Table 5, Power Venter Sizes. Follow
the power venter manufacturer’s installation instructions.

Table 5 - Power Venter Sizes

COMMON VENT SYSTEMS

If an existing boiler/water heater is removed from a
common venting system, the common venting system
may then be too large for the proper venting of the
remaining appliances connected to it. At the time of
removal of an existing boiler/water heater, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining
connected to the common venting system are not in
operation.

Au moment du retrait d’une chaudière existante, les
mesures suivantes doivent être prises pour chaque
appareil toujours raccordé au système d’évacuation
commun et qui fonctionne alors que d’autres appareils
toujours raccordés au système d’évacuation ne fonction-
nent pas: système d’évacuation.

a) Seal any unused openings in the common venting

system.

Sceller toutes les ouvertures non utilisées du sys-tème
d’évacuation.

b) Visually inspect the venting system for proper size

and horizontal pitch and determine there is no block-
age or restriction, leakage, corrosion and other defi-
ciencies which could cause an unsafe condition.

Inspecter de façon visuelle le système d’évacuation
pour déterminer la grosser et l’inclinaison horizontale
qui conviennent et s’assurer que le système est ex-
empt d’obstruction, d’étranglement de fruite, de cor-
rosion et autres défaillances qui pourraient présenter
des risques.

Chimney Inspection & Sizing

A thorough inspection of the masonry chimney must be
performed to ensure that the chimney is clean, properly
constructed, lined and sized. Exterior masonry chimneys
should not be used unless properly lined to prevent
condensation and draft problems. Table 4 lists the
equivalent breeching and flue sizes required for the
boiler/water heater.

Table 4 - Equivalent Breeching & Chimney Size

          Model                     Size                      Size
           Size                         

in

                        

mm

100

  

5

127

150

  6

152

200

 

 7

178

250

 

 8

203

300

 

 8

203

350

 

 9

229

400

10

254

Note: These sizes are based on a

 20 ft

,

 

6.1 m

 

chimney height.

When more than one appliance is connected to the
same chimney flue, the flue must be large enough to
safely vent the combined output of all the appliances.

WARNING: If an appliance using any type of a
mechanical draft system operating under
positive pressure is connected to a chimney flue,
never connect any other appliances to this flue.
Doing so can result in the accumulation of
carbon monoxide which can cause severe
personal injury or death!

Vent Connections

Always use a type B or single wall galvanized metal vent
pipe the same diameter as the draft hood flue collar,
Table 4. Use the shortest, straightest vent system
possible for the installation. If horizontal runs exceed

6 ft

1.8 m they must be supported at 

6 ft

1.8 m

intervals with overhead hangers. The vent system should
be sloped up toward the chimney at a minimum rate of

1/4 in/ft

,  

20 mm/m and terminate flush with the inside

of the chimney flue. Fasten each connection with at least
3 corrosion resistant sheet metal screws.

WARNING: Never modify or alter any part of the
boiler’s draft hood. This includes the removal or
alteration of any baffles. Never install a vent pipe
of a diameter different than that of the boiler
draft hood flue collar. Failure to comply with this
warning can result in severe personal injury or
death!

Always provide a minimum clearance of 

6 in

,

152 mm

between type C vent pipe and any combustible
materials. Type B1 vent may be used, clearance
between it and any combustible material must be as
listed.

Spectrum Power Venter

Max. Pipe Length

Model

Size

FT

m

100-250

HS-1

100

31

300-400

HS-2

100

31

Содержание SB

Страница 1: ...in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the...

Страница 2: ...ter To obtain the safe dependable efficient operation and long life for which this heating boiler water heater was designed these instructions must be read understood and followed The Spectrum finned...

Страница 3: ...will support the weight of the boiler water heater NOTE The Spectrum may be installed directly on combustible flooring only if RBI supplied special floor pan is used but never on carpeting see Table 2...

Страница 4: ...n 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enclosure Where directly communicating with the outdoor...

Страница 5: ...onry chimney must be performed to ensure that the chimney is clean properly constructed lined and sized Exterior masonry chimneys should not be used unless properly lined to prevent condensation and d...

Страница 6: ...ef opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe Faire fonctionner le br leur principal pendant 5 min ensuite d terminer s...

Страница 7: ...INSTALLATION AND OPERATING INSTRUCTIONS Page 7 Figure 1 Vertical Venting with a Metal Chimney System and Inside Air Figure 2 Vertical Venting using a Masonry Chimney and Inside Air 10 FT 3 1m RIOM 51...

Страница 8: ...flow rates see Table 7 or 8 Return water temperatures below 110 F 43 C will result in heat exchanger damage from excessive condensation voiding the manufacturer s warranty see Primary Secondary Piping...

Страница 9: ...tem An expansion tank must be installed close to the boiler on the suction side of the system pump Primary Secondary Piping Boilers connected to heating systems using zone valves zone pumps or systems...

Страница 10: ...Drop T 30 F T 16 7 C Note Unit equipped with 4 pass headers see Table 8 Flow Rate 100 150 200 250 300 350 400 16 4 24 6 32 4 40 5 49 8 0 34 0 94 1 92 3 46 5 89 1 0 1 6 2 0 2 6 3 1 1 0 2 8 5 7 10 2 17...

Страница 11: ...lers furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied Notice These drawings show suggested piping configuration and valving Check wit...

Страница 12: ...lobe Valve Balance Valve Balance Valve 1 5 H 15 Rev 2 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow through all units NOTES 1 Boiler circuit piping must be sized lar...

Страница 13: ...he boiler When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device the piping system must be equipped with flow control valves or some other aut...

Страница 14: ...xchanger The cupro nickel heat exchanger allows for 100 GPM 6 3 L s 2 pass heat exchanger and 50 GPM 3 2 L s 4 pass heat exchanger SeeTable 7B Cold Water Supply The cold water supply must be piped to...

Страница 15: ...SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 15 Table 7B Spectrum Pumping Performance Requirement Table Table 7A Spectrum Heat Exchanger Selection Graph...

Страница 16: ...ay locate remote aquastat well in lower 1 3 of tank Install bulb with heat sensing compound 3 Thermal expansion tank may be required check local codes 4 When using optional factory mounted pump max pi...

Страница 17: ...00 9700 Maximum gas volume of pipe ft3 hr Pipe length in feet Table 9 Gas Pipe Capacity Nominal Iron Pipe Size in Maximum pipe capacity in ft3 hr based on 0 60 specific gravity gas at a pressure of 0...

Страница 18: ...alled to prevent increase creep of gas pressure when the units are not operating This pressure regulator supplied by others may be installed at the service entrance to each unit or a master regulator...

Страница 19: ...water pump is used adjust to maintain a minimum 12 psig 82 7 kPa system pressure Open the system bleed and drain valves one at a time to purge the air trapped in the heating system piping With the boi...

Страница 20: ...kwise to PILOT 9 Push in control knob all the way and hold in Immediately light the pilot with a match Continue to hold the control knob in for about one 1 minute after the pilot is lit Re lease knob...

Страница 21: ...el 6 Push in gas control knob slightly and turn clockwise to OFF 7 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety inf...

Страница 22: ...than 5 adjust it according to steps 1 through 4 Input Rate Natural Gas Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 2000 ft 610 m At elevations...

Страница 23: ...ine silica materials that have been identified as carcinogenic or possi bly carcinogenic to humans when inhaled AVERTISSMENT Une instqallation un r glage une r paration ou un entretien non comforme au...

Страница 24: ...dication of low water flow through the system 2 A damaged heat exchanger must be replaced and the condition that caused the damage resolved before the boiler water heater is returned to service Vent S...

Страница 25: ...SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 25 4 21 1 22 29 26 27 6 28 25 15 16 24 12 4 3 10 8 20 2 5 36 35 31 19 18 9 7 17 11 23 30 37 34 33 32 14 13 Figure 14 Replacement Parts...

Страница 26: ...Front Panel 03 0894 1 03 0895 1 03 0896 1 03 0897 1 03 0898 1 03 0899 1 03 0900 1 Combustion Chamber Side Panel Left Right 03 0901 2 2 2 2 2 2 2 2 Rear Refractory Panel 05 0035 1 05 0036 1 05 0037 1 0...

Страница 27: ...70 1257 1 70 1258 1 70 1259 1 70 1260 1 70 1261 1 70 1262 1 8 Jacket Rear Panel 03 0749 1 03 0750 1 03 0751 1 03 0752 1 03 0753 1 03 0754 1 03 0755 1 9 Draft Hood Assembly 70 1272 1 70 1273 1 70 1274...

Страница 28: ...123 1 09 0124 1 1 09 0125 1 09 0126 1 17 Jacket Top Panel 03 0741 1 03 0742 1 03 0743 1 03 0744 1 03 0745 1 03 0746 1 03 0747 1 NS Jacket Top Panel Outdoor 70 1205 1 70 1206 1 70 1207 1 70 1208 1 70 1...

Страница 29: ...ader Bronze 01 0011S 1 1 1 1 1 1 1 NS Return Header Bronze 4 Pass 01 0011 1S 1 1 1 1 1 1 1 23 Inlet Outlet Cover Outdoor 03 0734 1 1 1 1 1 1 1 24 Return Cover Outdoor 03 0737 1 1 1 1 1 1 1 NS Heat Exc...

Страница 30: ...1 1 1 1 33 High Limit Operator Knob 14 0120 1 1 1 1 1 1 34 Light Package 40 0052 1 1 1 1 1 1 35 Relay 24V AC 15 0113 1 1 1 1 1 1 36 Terminal Block 2P 48 0151 1 1 1 1 1 1 Terminal Block 4P 48 0152 1 1...

Страница 31: ...NS Power Venting Wiring 30 0787 1 1 1 1 1 1 NS Induced Draft Kit HS1 12 0009BK 1 1 1 1 Induced Draft Kit HS2 12 00010BK 1 1 NS Vent Termination Hood 4 09 0134 1 1 1 1 Vent Termination Hood 6 09 0112...

Страница 32: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...

Отзывы: