110
16 - USE
2024
Reset curve design: spring supply temperature
°F
32 to 104
104
N/A
2027
Night setback temperature
°F
2 to 90
18
N/A
2040
N/A
2041
N/A
2042
Burner 1 anti cycling: time
sec
10 to 900
180
180
2043
Burner 1 anti cycling: differential temperature
°F
0 to 36
28
28
2062
DHW post pump time
sec
10 to 255
240
N/A
2063
DHW max priority time
min
1 to 60
30
N/A
2067
DHW priority
0 = (TIME), DHW has
priority to CH during DHW
max priority time (2063)
1 = (OFF), CH always has
priority to DHW.
2 = (ON), DHW always has
priority to CH
2
N/A
2100
Display: delay to shut off
min
0 to 30
5
5
2101
MULTIBURNER Emergency mode (If sensor 1102
fail)
\
no or yES
Yes
Yes
2102
MULTIBURNER Emergency setpoint
°F
68 to 149
113
113
2103
MULTIBURNER start delay time
sec
1 to 900
180
15
2104
MULTIBURNER stop delay time
sec
1 to 900
180
15
2105
MULTIBURNER start burner diff.
°F
0 to 36
9
9
2106
MULTIBURNER stop burner diff.
°F
0 to 36
9
9
2107
MULTIBURNER calculated setpoint. Max offset
up.
°F
1 to 36
18
9
2108
MULTIBURNER calculated setpoint. Max offset
down.
°F
1 to 36
36
9
2109
MULTIBURNER next burner start rate
%
1 to 100
70
70
2110
MULTIBURNER next burner stop rate
%
1 to 100
10
10
2111
MULTIBURNER rotation interval
Days
0 to 9
6
6
2113
MULTIBURNER start modulation delay factor
min
0 to 60
5
0
2114
Burner 1 post local pump time
sec
0 to 255
240
240
2200
System test: all burners together.
\
Off, Low, Ign, High
OFF
OFF
2201
System test: Burner 1 (Master).
\
Off, Low, Ign, High
OFF
OFF
2202
System test: Burner 2.
\
Off, Low, Ign, High
OFF
OFF
2203
System test: Burner 3.
\
Off, Low, Ign, High
OFF
OFF
2204
System test: Burner 4.
\
Off, Low, Ign, High
OFF
OFF
Parameter
Parameter description
Visualization on display “N” (see Figure 16-1)
AFro
Heater is doing antifreezing protection
Supply temperature (°F)
Light fixed = Indirect water heater enabled
Blinking = indirect water heater loading
Supply temperature (°F)
Light fixed = Hot water supply enabled
Blinking = Hot water supply active
Supply temperature (°F)
16.15 - Diagnostic
During normal operation display can show
the information below:
Содержание Infinity Energy 2
Страница 3: ...3 SAFETY INSTRUCTIONS...
Страница 5: ...5 SAFETY INSTRUCTIONS...
Страница 62: ...62 10 INSTALLATION Electrical connections Figure 10 4 Electrical customer connection for IB boilers...
Страница 63: ...63 10 INSTALLATION Electrical connections Figure 10 5 Electrical customer connection for IW water heaters...
Страница 132: ...132 17 MAINTENANCE...
Страница 136: ...136 19 SPARE PARTS Spare parts...
Страница 139: ...139 19 SPARE PARTS 50 48 50 49 53 56 57 55 54 58 47 52 48 52 51 55 52 020010 03 006 199...
Страница 162: ...162 22 SEQUENCE OF OPERATION for BOILER...
Страница 163: ...163 23 SEQUENCE OF OPERATION for WATER HEATER...