Power
The ELC-08 requires 9 to 14 volts DC (connected to the Data Input) and draws a
maximum of 325ma.
Data Input / Data Output
The first ELC-08 is connected to the Elevator URC2000. Four wires are connected as
per the diagram above. The second, third, and fourth boards are each connected to the
previous board. Board four connected to board three, board three connected to board
two, and board two connected to board one. Connect 0v to 0v, D+ to D+, D- to D-, and
12v to 12v.
Fire Signal
Apply 12-24 volts DC to satisfy this input. When this voltage is removed all of the
relays on the board will power down (turn ON), making all floors accessible. If the Fire
Signal feature is not required install a jumper on the Fire Signal Bypass.