background image

Chapter 2 

Intelligent Field Panel

 

RBH Access Technologies Inc. 

Integra32

 Hardware Guide 

9

 

TCP/IP Connection 

For  TCP/IP  connections,  wire  to  the  TCP/IP  interface  as  you  would  to  the  PC,  with  a 
direct RS-232 connection.  The TCP/IP interface is programmed with an IP address and 
connected to the LAN (

contact the local system administrator for an IP address

). 

Additional controllers can be connected via the RS-485 connection terminals. 

 

 

 

 

RS485 Connection 

The IRC-2000 controller supports a two-wire RS485 interface.  Jumpers JP1 is to be set 
on the lower two pins for RS485 operation. 

The  RS485  interface  allows  the  distance  between  the  controller  and  the  PC  to  be 
extended up to 4000 feet (

1200 meters

).  RS485 requires one twisted pair shielded cable. 

Cable Specification 

Single twisted three-conductor, shielded, 18 to 22 AWG 

Maximum Cable Length 

4000 feet (1200 meters) 

 

 

 

 

 

 

 

 

 

Содержание Integra32

Страница 1: ...Integra32 Integrated Alarm Monitoring and Access Control HARDWARE MANUAL new generation building security ...

Страница 2: ...mark or service mark Disclaimer This book is provided as is without warranty of any kind either express or implied including but not limited to performance merchantability or fitness for any particular purpose Neither RBH Access Technologies Inc nor its dealers or distributors shall be liable to any person or entity with respect to any liability loss or damage caused or alleged to have been caused...

Страница 3: ...tions 16 Status LED s 17 Jumpers 17 ELEVATOR CONTROL 18 Connection Details 19 PC100 21 Connection Details 21 Status LED s 22 Jumpers 22 CHAPTER 3 INPUT OUTPUT CONNECTIONS 23 INPUTS 23 RTE Request to Exit 23 DC Door Contact 23 General Purpose 23 INPUT CIRCUIT TYPES 24 OUTPUTS 28 Lock Output 28 Handicap Output 28 Alarm Shunt Output 28 Modem Power Output 28 General Purpose Output 28 Switching Inducti...

Страница 4: ...onnection 34 IRC 2000 SPECIFICATION 36 URC 2000 SPECIFICATION 37 PC 100 SPECIFICATION 38 ELC 08 SPECIFICATION 39 CABLE SPECIFICATION 40 INDEX 41 LICENSE WARRANTY 43 APPENDIX A PC 100 INTERFACE APPLICATIONS 44 WIRING 44 DSC ALARM PANEL INTERFACE 45 BOSCH ALARM PANEL INTERFACE 46 SUMMIT ALARM PANEL INTERFACE 48 APPENDIX B DIALUP MODEM CONFIGURATION 51 REMOTE SITE MODEM 51 SERVER HOST SITE MODEM 52 M...

Страница 5: ... is used for data entry setting up the database and monitoring activity on the system Once the database is downloaded to the controllers the PC is not required for system operation Should the PC be powered down the controller will perform all access and other control functions but of course not Global functions including logging history events When the connection is restored the log will then be r...

Страница 6: ...or modem through an RS232 port TCP IP Ethernet interface or an RS485 2 wire interface like a USB 485 module can also be used to connect the panels with the software The RS 485 connection is made in parallel with the additional panels Inputs There are two common terminals for each set of four inputs one between inputs one and two another between three and four one between five and six and one betwe...

Страница 7: ...Chapter 1 Intelligent Field Panel RBH Access Technologies Inc Integra32 Hardware Guide 3 ...

Страница 8: ...nect directly to the AC earth Use 16 AWG or heavier cable and keep the length as short as possible less than 50 feet 15 meters For multiple panels always use only a single point ground reference for all panels Bring the shields of all reader and communication cables back to one location Do not connect them to the panel or the panel s housing Grounding the Integra32 system RS 485 Earth To PC RS 232...

Страница 9: ...ight is used to set the connection type modem or direct DIP Switch DIP Switch Function 1 5 Controller Address 6 7 Controller Baud Rate 8 Modem Direct PC Connection Controller Addressing Use DIP switches 1 2 3 4 and 5 to select the controller address The address is binary coded and the switch settings for all sixteen possible addresses are given below Controller Addressing Switch 1 Switch 2 Switch ...

Страница 10: ...ns on the password requirement and enables modem call back The panel will still answer a modem call with DIP switch 8 off You should initially set up the panel with DIP switch 8 off program the panel and download to it Then turn DIP switch 8 on to enable password checking Computer Modem Port Baud Rate Selection The controller s serial port baud rate is set with controller DIP switches 6 and 7 This...

Страница 11: ...ontroller can not be greater than 150 feet 45 meters or 30 feet 9 meters if the baud rate is increased to 38 400 For distances greater than 150 feet 45 meters an RS485 interface must be used RS485 is built into the IRC 2000 controller but is not part of the standard PC The PC must be fitted with either an RS485 serial card or an external RS232 to RS485 serial port converter Additional controllers ...

Страница 12: ...he modem connection is similar to the RS 232 connect with the inclusion of the DCD terminal If multiple controllers are used then the RS 485 connecter will be needed to connect the additional controllers to the modem controller Cable Specification 4 conductor shielded 18 to 22 AWG Maximum Cable Length 9600 baud 150 feet 45 meters 56000 baud 50 feet 15 meters ...

Страница 13: ...strator for an IP address Additional controllers can be connected via the RS 485 connection terminals RS485 Connection The IRC 2000 controller supports a two wire RS485 interface Jumpers JP1 is to be set on the lower two pins for RS485 operation The RS485 interface allows the distance between the controller and the PC to be extended up to 4000 feet 1200 meters RS485 requires one twisted pair shiel...

Страница 14: ...rk or distributed across multiple networks After the first controller of the network is connected to the PC additional controllers can be connected to the network via the RS485 terminals Connect the TX A terminal of one controller to the TX A terminal next one and connect the RX B terminal to the RX B terminal All of the controllers on a network are connected in parallel Controller Network Connect...

Страница 15: ...en the controller transmits data If the controller is connected directly to the PC the status LED s flash continuously Run LED The run LED LED2 flashes to indicate the controller is not communicating it is on solid when running normally and off if power is missing Diagnostic LED This LED LED1 will be on if either reader A or reader B buzzer output is on Fuses There are two 1 amp self resetting Pol...

Страница 16: ...RS485 In a multi panel network with the first panel connected to the PC via RS 232 and all other panel connected to the first panel via RS 485 set JP1 of panel 1 to RS 232 and all other JP1s to RS 485 JP2 Bias Low RS485 tuning JP3 Termination RS485 tuning JP4 Bias High RS485 tuning Leave jumpers JP2 JP3 and JP4 open Do not use these jumpers without consulting RBH ...

Страница 17: ...een three and four Seven different input types are supported including normally open normally closed one resistor and two resistor configurations Outputs Two of the four programmable outputs are dry contact relays UL rated 2A 30v dc These are designated as outputs one and three The other two outputs are solid state switches open collector to ground capable of sinking 100ma Readers Readers are conn...

Страница 18: ...Chapter 2 Intelligent Field Panel Integra32 Hardware Guide RBH Access Technologies Inc 14 ...

Страница 19: ... Do not connect them to the panel or the panel s housing DIP Switch Settings The URC 2000 s DIP switches control a number of operating parameters including the device address and serial port baud rate The controller must be powered down to accept any changes in the DIP switch settings Use DIP switches one through five to set the controller address Switches six and seven set the communication baud ...

Страница 20: ... rate is set with DIP switches 6 and 7 This setting determines the speed used to communicate with the PC All controllers connected to the software through the same port must have the same baud rate The default PC baud rate is 38 400 Controller Baud Rate Selection DIP Switch 6 DIP Switch 7 Baud Rate OFF OFF 9 600 ON OFF 28 800 OFF ON 38 400 ON ON 56 000 PC Connections RS485 Connection The URC 2000 ...

Страница 21: ...If the controller is connected directly to the PC the status LED s flash continuously Run LED The run LED LED3 flashes to indicate the controller is not communicating it is on solid when running normally and off if power is missing Fuses There are two 1 amp self resetting Polyfuses on the URC 2000 board F1 is connected to Reader Power and F2 is connected to Main Power Jumpers JP1 Bias Low RS485 tu...

Страница 22: ...t outputs per Elevator Control panel These contacts are programmed as on state de energized so that the release of the fire signal or power will place the outputs in the ON state There are red LEDs one for each relay that turn on as each relay is energized therefore indicating an off state The green LED next to the data input connector flash when communications is lost Another green LED next to th...

Страница 23: ...Chapter 2 Intelligent Field Panel RBH Access Technologies Inc Integra32 Hardware Guide 19 Connection Details ...

Страница 24: ...the diagram above The second third and fourth boards are each connected to the previous board Board four connected to board three board three connected to board two and board two connected to board one Connect 0v to 0v D to D D to D and 12v to 12v Fire Signal Apply 12 24 volts DC to satisfy this input When this voltage is removed all of the relays on the board will power down turn ON making all fl...

Страница 25: ... Technologies Inc Integra32 Hardware Guide 21 PC100 Connection Details Power The PC 100 requires 9 to 14 volts DC and draws about 150ma PC Interface The PC interface connects the PC 100 to a PC through an RS232 serial connection at 9600 baud only ...

Страница 26: ...ace The Access Panel Interface is an RS485 port that has two LEDs to show the flow of data between the PC 100 and IRC2000 and or URC2000 panels The red RX LED LED5 flashes when the controller receives data The green TX LED LED6 flashes when the controller transmits data Alarm Panel Interface The Alarm Panel Interface is an RS485 port that has two LEDs to show the flow of data between the PC 100 an...

Страница 27: ...istor normally closed 1k represents a normal state and 2k represents an abnormal state Less than twenty ohms is a short and very high resistance is an open RTE Request to Exit Inputs programmed as RTE will be connected to push buttons mounted on the door or to motion detectors mounted near the door Activating the RTE input will cause a grant access to be executed on the appropriate door The RTE ca...

Страница 28: ...seven different input circuit types ranging from no resistor for low security applications to two resistors normally closed circuits where the highest security is required Normally Closed No Resistor Loop Resistance State Short Restore Open Circuit Alarm Normally Open No Resistor Loop Resistance State Short Alarm Open Circuit Restore ...

Страница 29: ...op Resistance State Short Trouble 1k Restore Open Circuit Alarm Normally Closed Two Resistor Loop Resistance State Short Trouble 1k Restore 2k Alarm Open Circuit Trouble This circuit provides a high degree of supervision and detects both short and open circuit fault conditions Use this circuit in high security applications ...

Страница 30: ...2 Hardware Guide RBH Access Technologies Inc 26 Normally Open One Resistor Loop Resistance State Short Alarm 1k Restore Open Circuit Trouble Normally Open Two Resistor Loop Resistance State Short Trouble 1k Alarm 2k Restore Open Circuit Trouble ...

Страница 31: ...nologies Inc Integra32 Hardware Guide 27 Normally Open And Normally Closed One Resistor Loop Resistance State Short Alarm 1k Restore Open Circuit Alarm This circuit type is used where normally open and normally closed contacts are used in the same loop ...

Страница 32: ... used as general purpose outputs Lock Output The lock output is used to activate or deactivate the locking device on the door It can apply power to door strikes or remove power from magnetic locks Handicap Output This output is used to drive door operators It turns on in less than one second after the Lock Output is turned on and stays on until the Lock Output is turned off Only designated cardhol...

Страница 33: ... locks All of these devices generate extremely high voltage spikes several thousand volts when power is applied or removed and possible disruption of the operation could occur if this interference gets on to the electronic circuit board This interference can be suppressed by placing a diode 1N4004 or similar across the lock or other inductive device being switched Connect the diode cathode end wit...

Страница 34: ...tic lock or door strike Multiple outputs can be set to the same function outputs one and two can both be Lock outputs for reader A Magnetic Lock Connection Diagram For magnetic locks the relay should be configured from the PC as On State de energized for fail safe operation If power fails AC and battery the power to the magnetic lock is removed and the door is opened ...

Страница 35: ...cess Technologies Inc Integra32 Hardware Guide 31 Door Strike Connection Diagram Handicap Output Connection Diagram If this output is used with an inductive load use a back EMF diode as described on page 29 to prevent damage to other equipment ...

Страница 36: ...on to indicate the door is unlocked Door Held Open Warning The Buzzer beeps slowly Door Held Open Alarm The Buzzer beeps continuously Keypad Reader Combination The Buzzer emits a series of short beeps every second after a card is presented until a PIN is entered Access Granted The Buzzer emits one long beep and the green LED turns on for the duration of the unlock time Access Denied The Buzzer emi...

Страница 37: ...er port A single reader port can now have an In and an Out reader IRC 2000 Connection Connect the Out reader to the seven pin terminal and the In reader to the eight pin terminal Also connect the eight pin terminal to the panel s reader port For the IRC2000 connect the SIG terminal of the interface to the TAM terminal on the reader port If you are connecting to a URC2000 connect the SIG terminal t...

Страница 38: ...Chapter 3 Input Output Connections Integra32 Hardware Guide RBH Access Technologies Inc 34 URC 2000 Connection For more information on the Exit Reader Interface check TB51 Exit Reader Interface pdf ...

Страница 39: ...Specifications RBH Access Technologies Inc Integra32 Hardware Guide 35 S p e c i f i c a t i o n s ...

Страница 40: ... per System Maximum of 32 Readers per IRC 2000 2 Cardholder normal Maximum 5 000 extended Maximum 8 000 Event Log per IRC 2000 Maximum 1 400 Network Connection Type RS 232 or RS 485 Serial Port Speed 9600 28800 38400 or 56000 Real Time Clock Dallas DS1994 with battery back up Housing dimensions H 12in x W 14in x D 3 in Operating temperature 0 to 70 C 35 150 F Operating Humidity 20 to 80 RH non con...

Страница 41: ...C 2000 System Capacities URC 2000 s per System Maximum of 32 Readers per URC 2000 2 Cardholder Maximum 3 000 Event Log per URC 2000 Maximum 1 400 Network Connection Type RS 485 Serial Port Speed 9600 28800 38400 or 56000 Real Time Clock Dallas DS1994 with battery back up Board dimensions H 3in x W 6 in Operating temperature 0 to 70 C 35 150 F Operating Humidity 20 to 80 RH non condensing PC Connec...

Страница 42: ...e upgrades from the PC to PC 100 System Capacities PC 100 s per System Maximum of 1 Network Connection Type RS 232 and RS 485 Serial Port Speed 9600 28800 38400 or 56000 Real Time Clock Dallas DS1994 with battery back up Board dimensions H 4 in x W 4 in Operating temperature 0 to 70 C 35 150 F Operating Humidity 20 to 80 RH non condensing PC Connection Can be connected via RS232 RS485 or by Modem ...

Страница 43: ...t i o n Controller Power Requirements 9 14V DC Current Consumption 325ma max System Capacities ELC 08 s per URC2000 Maximum of 4 Network Connection Type RS 485 Relay Outputs 1A 30vdc Board dimensions H 3in x W 6 in Operating temperature 0 to 70 C 35 150 F Operating Humidity 20 to 80 RH non condensing ...

Страница 44: ...eet 1200 meters IRC 2000 URC 2000 to Reader 20 to 22 AWG 6 or 8 conductor stranded shielded not twisted Maximum Cable Length 22 AWG Cable 250 feet 75 meters 20 AWG Cable 500 feet 150 meters PC 100 RS232 to PC 3 or 4 conductor shielded 18 to 22 AWG Maximum Cable Length 9600 baud 150 feet 50 meters 56000 baud 50 feet 15 meters 2 Wire RS485 to panels Single twisted pair shielded 18 to 22 AWG Maximum ...

Страница 45: ...oor Contact 23 Door Held Open Alarm 32 Door Held Open Warning 32 Door Strike Connection Diagram 31 E Earth 4 15 ELC 08 Specification 39 Electronic Output Connection Diagram 29 Elevator Control 18 Connection Details 19 Jumpers 22 Status LED s 22 Exit Reader Interface 33 F Fire Signal 20 Fuses IRC 2000 11 URC 2000 17 G General Purpose Input 23 Output 28 H Handicap Output 28 Connection Diagram 31 Hig...

Страница 46: ...uest to Exit 23 RS232 Connection 7 RS485 Connection IRC 2000 9 URC 2000 16 RTE See Request to Exit Run LED 11 S Specification Cable 40 ELC 08 39 IRC 2000 36 PC 100 38 URC 2000 37 Status LED s Elevator Control 22 IRC 2000 11 URC 2000 17 Switching Inductive Devices 29 T TCP IP Connection 9 U Unlocked Mode 32 URC2000 Connection Daigram 34 Connection Details 13 DIP Switch Settings 15 Fuses 17 Jumpers ...

Страница 47: ...ghts of others RBH Access Technologies Inc shall not have any liability or responsibility to sublicenses including end users for damages of any kind including special indirect or consequential damages arising out of or resulting from any program services or materials made available hereunder or the or the modification thereof Notice 1 02 RBH Access Technologies Inc makes no claim or warranty with ...

Страница 48: ...larm panels with the Integra system Some DSC Bosch Summit Gardtec Rokonet and Paradox alarm panels can be interfaced this way Wiring The PC 100 connects to the IRC 2000 through the RS 485 Power 9 14vdc 150ma LEDs DIAG1 Interface status DIAG2 Integra status Communication Channel LEDs Each communication channel has a green transmit LED and a red receive LED Normally flashing at a rate of once a seco...

Страница 49: ... provided and report status to the Integra network when included in the list of keypads Keypad States The emulated keypads in this case are representations of partition states A partition can be armed disarmed or in alarm Panic Emergency and Fire alarms initiated by the alarm panel will be reflected on the first keypad Input States In addition to the keypads the PC100 will also emulate 256 inputs ...

Страница 50: ... with the keypad network you should notice the red LED flashing as it receives data and the green LED flashing as it responds to polls The response to polls will only occur under the following conditions 1 The keypad address is included in the list of keypads programmed in the Integra network 2 The keypad emulation box has been checked 3 The keypad address has been programmed into the alarm panel ...

Страница 51: ...Appendix 1 Specification Sheets RBH Access Technologies Inc Integra32 Hardware Guide 47 ...

Страница 52: ...ause a zone to appear open or closed The PC100 acts like an IRC panel at address 32 to the host The host can poll the PC100 to see if it is online request status write to memory and update flash memory IRC2000 panels connected along with the PC100 must be running firmware version 76 or higher for the PC100 and the IRC2000 panels to function together correctly Programming an Arm Disarm key switch W...

Страница 53: ...r the door contact is enabled by software Using Alarms Three types of alarms with A or B readers are allowed DHO alarm reader A DHO alarm reader B Forced entry reader A Forced entry reader B Reader Tamper A Reader tamper B Multiple Combinations For multiple combinations of inputs outputs and events a spare output on an IRC panel can be assigned this functionality through the use of links The outpu...

Страница 54: ...Appendix 1 Specification Sheets RBH Access Technologies Inc Integra32 Hardware Guide 50 ...

Страница 55: ...l Ready DTR or TR ON Override Verbal Result Codes ON Suppress Result Codes OFF Echo Commands OFF Carrier Detect CD OFF Normal These settings on the recommended modem would mean that all modem DIPswitches 1 3 4 7 and 8 were down except switches 2 5 6 which will be up Note PC side modem will not work with above DIP switches settings PC side modem has to be set to default settings 3 5 8 4 Check the t...

Страница 56: ...move a modem or edit modem properties You can access modem properties from Control Panel Click the Add button Figure1 Phone and modem Options window 3 You may choose to let the Install New Modem wizard auto detect your modem or select it yourself You will have to specify the COM port that you will use for that modem 4 Once the modem has been installed you may edit the settings to correspond with t...

Страница 57: ...Appendix 1 Specification Sheets RBH Access Technologies Inc Integra32 Hardware Guide 53 Figure 2 Opening modem properties from device Manager ...

Страница 58: ...chnologies Inc Integra32 Hardware Guide 54 6 Use the Properties button to set the desired modem parameters e g Max Speed of 9600 for a 56 6k modem Use parameters appropriate for the remote site that you are connecting to Figure 3 Modem properties ...

Страница 59: ...ation Sheets RBH Access Technologies Inc Integra32 Hardware Guide 55 6 Set Advanced Connection Settings as follows Include Extra Initialization Commands of N6 to further force a baud rate of 9600 Figure 4 Modem Properties ...

Страница 60: ... RBH Access Technologies Inc Integra32 Hardware Guide 56 Click on Query Modem button Figure 5 and you will see success message Figure 6 Otherwise you will see communication fails message Figure 7 Figure 5 Modem Diagnostics properties ...

Страница 61: ...Appendix 1 Specification Sheets RBH Access Technologies Inc Integra32 Hardware Guide 57 Figure 6 modem Query results Figure 7 Modem Query error message ...

Страница 62: ...s downloaded to all the panels 3 Change all Dipswitch 8s to ON 4 Re power the IRC 2000s Configure Modem COM Port on the Integra32 Server 1 Open the Network Properties window in the Integra32 Database Manager 2 Click on Port Type and select Modem Network 3 Use the Modem combo box down arrow and select the modem from those already setup under Windows 4 Set the baud rate 9600 and Phone number for the...

Страница 63: ...Appendix 1 Specification Sheets RBH Access Technologies Inc Integra32 Hardware Guide 59 Note Panel modem side 25 pin DB connector wiring diagram is incorrect Please refer to diagram below ...

Страница 64: ... RS 232 connect except that the TX RX connections are straight through instead of crossed with the inclusion of the DCD terminal If multiple controllers are used then the RS 485 connecter will be needed to connect the additional controllers to the modem controller Cable Specification 4 conductor shielded 18 to 22 AWG Maximum Cable Length 9600 baud 150 feet 45 meters 56000 baud 50 feet 15 meters ...

Отзывы: