TTDM-128
TraceTek Leak Detection
and Location Module
General Information
Please read these instructions carefully and keep them in a safe place
(preferably close to the TTDM) for future reference. These instructions
must be followed carefully to ensure proper operation.
The TTDM Alarm and Locating Module has been designed specifically for use
with TraceTek sensing cables, point sensors, sensor interface modules and
relay modules. The TTDM can directly monitor up to 1500 m (5000 ft) of
sensing cable, and large networks of remote leak detection modules.
An external disconnect device and appropriate branch circuit protection
(no more than 20 amp rating) should be provided for the TTDM. The
disconnect device should be clearly marked as such. Follow all national
and local codes and regulations applicable to the installation.
Installation Instructions
Shock hazard. Shut off power before operating enclosure door.
Installation items (not supplied)
• Wall fasteners for surface mounting (four screws)
Tools required
• Drill or hole punch for electrical conduit entries
• Phillips (cross-head) screwdriver
• Small flat-head screwdriver
Storage
Keep the module in a dry place prior to installation to avoid possible damage to internal components.
Product Information
TTDM-128
115 Vac +15%, –20%; 50/60 Hz
230 Vac ±10%; 50/60 Hz
TTDM-128-24V
24 Vac +5%, –35% 24 Vdc ±20%
Power consumption
6 VA (5 W) for TTDM-128
12 VA (10 W) for TTDM-128-24V
Installation categories
Overvoltage Category II, Pollution Degree 2
Built-in relays
Number:
Three (Service, Leak, Fault)
Type:
DPDT
Rating:
5 A at 250 Vac/24 Vdc
Temperature
Storage:
–18°C to 60°C (0°F to 140°F)
Operating: 0°C to 50°C (32°F to 122°F)
Enclosure
NEMA 12; IP 54
Approvals and Certifications
LISTED
76LJ
SIGNAL SYSTEM UNIT
Type NM
LEAK DETECTION
powered by
®