Max number of fittings allowed per MCB 

MCB Type

Rating

SPZ/SPX-HP10K

(120W Version)

SPZ/SPX-HP15K

(180W Version)

SPZ/SPX-HP20K

(240W Version)

SPZ/SPX-HP25K

(300W Version)

B

10A

4

3

2

1

B

16A

10

6

4

3

B

20A

12

7

5

4

B

25A

15

10

7

6

C

10A

8

5

4

3

C

16A

16

8

6

5

C

20A

20

10

8

6

C

25A

26

16

13

9

Содержание SPARTAN SPX-HP15K

Страница 1: ...tructions 2 Installation 3 Maintenance 4 Technical Specification 5 Trouble Shooting The SPARTAN HP series of explosion protected floodlights highbay are specialist devices certified for use in specifi...

Страница 2: ...certification nameplate on side of floodlight highbay to ascertain type of threaded cable entry on the luminaire Select suitably certified ATEX IEC Ex cable glands and stopper plugs these must be par...

Страница 3: ...ing SPARTAN Unit 1 To meet the requirements of certification a MINIMUM of 2 fixing points must be used the fixing points must be suitable for the conditions of use 2 The line diagrams below are for gu...

Страница 4: ...4 www raytecled com UK Europe Tel 44 0 1670 520055 Americas Tel 1 613 270 9990 Mounting SPARTAN Unit Highbay Application 422 16 6 353 13 9 536 21 1 457 18 1 3 0 5 1 33 1 3 172 6 8...

Страница 5: ...e cable should be connected to each terminal block connection 7 To use DALI Dimming interface connect the DALI terminals on the terminal block Wire the Mains cable into the terminal block Provision ha...

Страница 6: ...ced remove the flameproof cover to get access to the power supply Remove the power supply from the mains terminals then remove LED red and black wires 5 Disposal of packaging SPARTAN units and old LED...

Страница 7: ...nameplate on product Input Current 230Vac full load 0 7A 1 4A Consumption 150W 300W Power Factor 230Vac full load 0 97 Mains Frequency 50 60Hz Inrush Current Ipeak 50 53A t 300 s 60A t 300 s Total Ha...

Страница 8: ...number of fittings allowed per MCB MCB Type Rating SPZ SPX HP10K 120W Version SPZ SPX HP15K 180W Version SPZ SPX HP20K 240W Version SPZ SPX HP25K 300W Version B 10A 4 3 2 1 B 16A 10 6 4 3 B 20A 12 7...

Страница 9: ...0 300 300 281 2 00 300 300 300 2 50 300 300 300 5 Troubleshooting 1 Ensure the two LED boards are correctly wired to terminal block Red to Red Black to Black paired cables 2 Ensure Mains input is corr...

Страница 10: ...ent Spartan range of High Power Floodlights Notified Bodies Sira Certification Services 0518 Unit 6 Hawarden Industrial Park Hawarden Deeside CH5 3US Certificate numbers CML17ATEX1148 CML17ATEX4149 IE...

Страница 11: ...ety Requirements has been assessed by reference to the following standards IEC 60079 0 2012 IEC 60079 7 2015 IEC 60079 1 2014 IEC 60079 18 2015 IEC 60079 25 2015 IEC 60079 31 2014 IEC 60079 15 2010 An...

Страница 12: ...UK Europe T 44 0 01670 520055 hazsales raytecled com Americas T 1 613 270 9990 ushazsales raytecled com www raytecled com...