SERVICING 
PROCEDURES

General Location of Controls

Sequence of Operation

Intermittent Ignition Device (IID)

Heaters equipped with the IID system will automatical-
ly light the pilot burner first and then the main burner,
each time there is a call for heat from the tankstat.
Whenever the tankstat calling for heat, the circulator
supplied with the heater, will be energized and should
be running. 

The ignition control module will also be energized to
initiate the pilot ignition by opening the first main valve
(pilot). At the same time, the electronic spark genera-

tor in the module produces a high voltage spark pulse
output that lights the pilot burner. If the pilot burner
does not light, the module will not energize the second
main valve and the burners will not light. Ignition spark
continues only until the timed trial for ignition period
ends. 

Then, the module goes into safety shutdown or lock-
out. Lockout de-energizes the first main valve operator
and closes the first main (pilot) valve in the gas con-
trol, stopping pilot gas flow. The ignition control system
must be reset by setting the tankstat below water tem-
perature for one minute or by turning off power to the
module for one minute. 

When the pilot flame is established, flame rectification
circuit is completed between the sensor and burner
ground. The flame sensing circuit in the module
detects the flame current, shuts off the spark genera-
tor and energizes the second main valve operator
which opens the second main valve. This allows gas to
flow to the burners where it is ignited by the pilot burn-
er flame. 

When the tankstat is satisfied, the valve operators are
de-energized shutting off the pilot and main burners,
and also the circulator.

Start-up Procedures

Filling the System

Fill system with water. Purge all air from the system
using purge valve sequence. After system is purged of
air, lower system pressure. Flush system before put-
ting into operation to ensure that foreign material does
not damage pump seals.

Checking the Circulator

Before lighting the heater and after system is filled,
make sure that circulator is operating properly. Manual
gas valve should be off.

NOTE: 

Circulator motor supplied with the heater

does not require lubrication.

Ignition Module
(Auto Ignition Only)

Fig.# 8195.3

                   Circulator

Manual Reset Limit
(in heater behind panel)

Pressure
Relief Valve

Field Wiring
Compartment

Temperature Sensor
Ignition Module

(Auto Ignition Only)

Transformer
Roll-Out Sensor

Gas Valve

Fig. 8: General Location of Controls

Содержание WH 0135A

Страница 1: ...in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING If the informa...

Страница 2: ...agraph 3 of the GENERAL SPECIFICATIONS section on page 6 Fig 7 on page 12 the Wiring Diagrams on pages 14 and 15 Fig 8 on page 16 Fig 12 on page 19 Fig 15 on page 20 the TROU BLESHOOTING chart on page...

Страница 3: ...iring 13 Wiring Diagram Standing Pilot Models 0090 0135 0195 14 Wiring Diagram IID Models 0090 0135 0195 15 CONTENTS 3 SERVICING PROCEDURES 16 Sequence of Operation 16 Start up Procedures 16 Repair Se...

Страница 4: ...Read and follow water heater warnings and instructions If owners manual is missing contact the retailer or manufacturer DANGER Failure to install the draft hood and properly vent the water heater to...

Страница 5: ...ting temperature at water heater Feel water before bathing or show ering Temperature limiting valves are available see manual Table A details the relationship of water temperature and time with regar...

Страница 6: ...design certified by the and tested under the requirements of the American National Standard ANSI Z21 10 3 Each heater has been constructed and pressure tested in accordance with the requirements of S...

Страница 7: ...4 5 WH 0135 135 132 80 1 1 4 1 2 18 6 1 4 6 WH 0195 195 192 80 1 1 4 1 2 18 6 1 4 7 Recovery gph based on manufacturer s rating May be used with other tank size capacity Table B Specifications and Di...

Страница 8: ...strict air flow Heater Side Minimum Distance from Combustible Surfaces Floor Combustible Front Alcove Back 6 in Right 6 in Left 6 in Top Indoor 16 in Top Outdoor Unobstructed Flue Vent 6 in Except for...

Страница 9: ...the roof more than five feet should be securely guyed or braced to withstand snow and wind loads We recommend use of insulated vent pipe spacer through the roofs and walls Model No Sq in of Each Free...

Страница 10: ...iction leakage corrosion and other deficiencies which could cause an unsafe condition c Insofar as is practical close all building doors and windows and all doors between the space in which the applia...

Страница 11: ...5 300 400 560 0135 15 40 60 150 150 200 0195 20 35 70 100 100 400 Natural gas 1000 BTUH ft 60 specific gravity 0 5 in WC pressure drop Propane gas 2500 BTUH ft 1 53 specific gravity 0 6 in WC pressure...

Страница 12: ...Pressure Specifications Water Connections System Piping The pipe size and fittings between the heater and the tank should be at least 1 for model 0090 and 1 1 4 for models 0135 and 0195 This is based...

Страница 13: ...e and pressure gauge is standard equipment on all hot water heaters All temperature and pressure gauges are shipped loose for field instal lation in the outlet water connection see Fig 7 All fittings...

Страница 14: ...14 Wiring Diagram Standing Pilot Models 0090 0135 0195...

Страница 15: ...15 Wiring Diagram IID Models 0090 0135 0195...

Страница 16: ...y turning off power to the module for one minute When the pilot flame is established flame rectification circuit is completed between the sensor and burner ground The flame sensing circuit in the modu...

Страница 17: ...ased stop and immediately call your service technician or gas supplier If the pilot does not stay lit after several tries turn the gas control knob to OFF and call your service technician or gas suppl...

Страница 18: ...and to replace any part 18 If red reset button does not pop up when released STOP and immediately call your service technician or gas supplier If the pilot does not stay lit after several tries turn...

Страница 19: ...mell gas STOP Follow b in the safety information previously stated If you do not smell gas go to the next step 8 For Honeywell Gas Valve Turn gas control knob counter clockwise to ON For Robertshaw Ga...

Страница 20: ...95 For Automatic Ignition Systems 1 Turn on power to the ignition systems and turn gas supply off at the gas valve 2 Check ignition module as follows a Set the tankstat to high setting b Watch for con...

Страница 21: ...of burners or around outer jacket indicates a need for cleaning 1 Lift off draft hood and flue collector by removing bolts and screws 2 Remove V baffles from heat exchanger 3 Remove burner tray see Bu...

Страница 22: ...t outlet and return water headers and install header retainer nuts and torque nuts even ly 3 Replace V baffles 4 Install thermostat sensing bulbs in header wells and replace bulb retaining clips 5 Ins...

Страница 23: ...ll out switch is open 6 Manual Reset High limit is open 7 Defective ignition module or defective gas valve SOLUTION S 1 Check circuit breakers disconnect switch Make sure power is on 2 Check continuit...

Страница 24: ...Refer to installation instructions regarding combustion air requirements 2 Refer to installations instructions 3 See yellow flame section above 3 Pilot Outage Standing pilot models 4 Yellow lazy flame...

Страница 25: ...ls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing DANGER SHOCK HAZARD Make sure electri cal power to the heater is disconnected to avoid potential ser...

Страница 26: ...cement 1 Shut off electrical power to the heater 2 Shut off water supply and open drain valve to remove water in the piping at the pump level 3 Disconnect wiring and conduit connections to the pump 4...

Страница 27: ...anufactured by it but Raypak will apply any such warranty as may be provided to it by the parts manufacturer TO MAKE WARRANTY CLAIM Promptly notify the original installer supplying the model and seria...

Страница 28: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: