When this water heater system is supplying general
purpose hot water requirements for use by individuals,
a thermostatically controlled mixing valve is recom-
mended to reduce the risk of scald injury. Contact a
licensed plumber or the local plumbing authority for
further information.

Thermometer(s) should be installed so that they indi-
cate the water temperature at or near the outlet of the
storage tank.

Relief Valve

A new combination temperature and pressure (T & P)
relief valve, complying with the Standard for Relief
Valves and Automatic Gas Shut Off Devices for Hot
Water Supply Systems, ANSI Z21.22, must be
installed in the opening provided on top of the storage
tank, at the time of installation. No valve is to be placed
between the relief valve and the storage tank.

The pressure rating of the relief valve must not exceed
the 160 maximum working pressure indicated on the
water heater rating plate. The BTUH rating of the relief
valve must not be less than the BTUH input of the
heater.

Connect the outlet of the relief valve to a suitable open
drain. The discharge line must pitch downward from
the valve to allow complete draining (by gravity) of the
relief valve and discharge line. 

The discharge line should be no smaller than the out-
let of the valve. The end of the discharge line should
not be threaded or concealed, and should be protect-
ed from freezing. No valve of any type, restriction or
reducer coupling, should be installed in the discharge
line. Local codes shall govern installation of relief
valve.

Temperature & Pressure Gauge

The temperature and pressure gauge is standard
equipment on all hot water heaters. All temperature
and pressure gauges are shipped loose for field instal-
lation in the outlet water connection (see Fig. 7). All
fittings required to mount the gauge to the piping are
supplied by others.

Electrical Wiring

The electrical power supply requirement for these
heaters is 120 volts, 60 Hz. Field wiring connections
and electrical grounding must comply with the local
codes, or in the absence of local codes, with the latest
edition of the National Electrical Code, ANSI/NFPA 70. 

Provide a separate fused circuit from the main electri-
cal panel to the heater, and a disconnecting means
within sight of the heater.

Remove the control box cover and make the power
supply connections in the field wiring compartment.
(See general location of controls drawing). The pump
is supplied and factory wired to operate with the
heater. The thermostat (tankstat) is shipped loose to
be installed in the tank at the installation site.

NOTE:

If it is necessary to replace any of the

original wiring, it must be replaced with 105°C wire or
its equivalent, except 150° black wire which must be
replaced with 150° wire or its equivalent.

NOTE: 

Minimum 18 AWG, 105°C, stranded wire

must be used for all low voltage (less than 30 volts)
external connections to the unit. Solid conductors
should not be used because they can cause
excessive tension on contact points. Install conduit
as appropriate. All high voltage wires must be the
same size (105°C, stranded wire) as the ones on the
unit or larger.

WARNING: SHOCK HAZARD:

Line voltage is

present. Before servicing tankstat or heater, turn off
electrical power to the heater at the main disconnect
or circuit breaker. Failure to do so could result in
severe personal injury or death.

Содержание WH 0135A

Страница 1: ...in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING If the informa...

Страница 2: ...agraph 3 of the GENERAL SPECIFICATIONS section on page 6 Fig 7 on page 12 the Wiring Diagrams on pages 14 and 15 Fig 8 on page 16 Fig 12 on page 19 Fig 15 on page 20 the TROU BLESHOOTING chart on page...

Страница 3: ...iring 13 Wiring Diagram Standing Pilot Models 0090 0135 0195 14 Wiring Diagram IID Models 0090 0135 0195 15 CONTENTS 3 SERVICING PROCEDURES 16 Sequence of Operation 16 Start up Procedures 16 Repair Se...

Страница 4: ...Read and follow water heater warnings and instructions If owners manual is missing contact the retailer or manufacturer DANGER Failure to install the draft hood and properly vent the water heater to...

Страница 5: ...ting temperature at water heater Feel water before bathing or show ering Temperature limiting valves are available see manual Table A details the relationship of water temperature and time with regar...

Страница 6: ...design certified by the and tested under the requirements of the American National Standard ANSI Z21 10 3 Each heater has been constructed and pressure tested in accordance with the requirements of S...

Страница 7: ...4 5 WH 0135 135 132 80 1 1 4 1 2 18 6 1 4 6 WH 0195 195 192 80 1 1 4 1 2 18 6 1 4 7 Recovery gph based on manufacturer s rating May be used with other tank size capacity Table B Specifications and Di...

Страница 8: ...strict air flow Heater Side Minimum Distance from Combustible Surfaces Floor Combustible Front Alcove Back 6 in Right 6 in Left 6 in Top Indoor 16 in Top Outdoor Unobstructed Flue Vent 6 in Except for...

Страница 9: ...the roof more than five feet should be securely guyed or braced to withstand snow and wind loads We recommend use of insulated vent pipe spacer through the roofs and walls Model No Sq in of Each Free...

Страница 10: ...iction leakage corrosion and other deficiencies which could cause an unsafe condition c Insofar as is practical close all building doors and windows and all doors between the space in which the applia...

Страница 11: ...5 300 400 560 0135 15 40 60 150 150 200 0195 20 35 70 100 100 400 Natural gas 1000 BTUH ft 60 specific gravity 0 5 in WC pressure drop Propane gas 2500 BTUH ft 1 53 specific gravity 0 6 in WC pressure...

Страница 12: ...Pressure Specifications Water Connections System Piping The pipe size and fittings between the heater and the tank should be at least 1 for model 0090 and 1 1 4 for models 0135 and 0195 This is based...

Страница 13: ...e and pressure gauge is standard equipment on all hot water heaters All temperature and pressure gauges are shipped loose for field instal lation in the outlet water connection see Fig 7 All fittings...

Страница 14: ...14 Wiring Diagram Standing Pilot Models 0090 0135 0195...

Страница 15: ...15 Wiring Diagram IID Models 0090 0135 0195...

Страница 16: ...y turning off power to the module for one minute When the pilot flame is established flame rectification circuit is completed between the sensor and burner ground The flame sensing circuit in the modu...

Страница 17: ...ased stop and immediately call your service technician or gas supplier If the pilot does not stay lit after several tries turn the gas control knob to OFF and call your service technician or gas suppl...

Страница 18: ...and to replace any part 18 If red reset button does not pop up when released STOP and immediately call your service technician or gas supplier If the pilot does not stay lit after several tries turn...

Страница 19: ...mell gas STOP Follow b in the safety information previously stated If you do not smell gas go to the next step 8 For Honeywell Gas Valve Turn gas control knob counter clockwise to ON For Robertshaw Ga...

Страница 20: ...95 For Automatic Ignition Systems 1 Turn on power to the ignition systems and turn gas supply off at the gas valve 2 Check ignition module as follows a Set the tankstat to high setting b Watch for con...

Страница 21: ...of burners or around outer jacket indicates a need for cleaning 1 Lift off draft hood and flue collector by removing bolts and screws 2 Remove V baffles from heat exchanger 3 Remove burner tray see Bu...

Страница 22: ...t outlet and return water headers and install header retainer nuts and torque nuts even ly 3 Replace V baffles 4 Install thermostat sensing bulbs in header wells and replace bulb retaining clips 5 Ins...

Страница 23: ...ll out switch is open 6 Manual Reset High limit is open 7 Defective ignition module or defective gas valve SOLUTION S 1 Check circuit breakers disconnect switch Make sure power is on 2 Check continuit...

Страница 24: ...Refer to installation instructions regarding combustion air requirements 2 Refer to installations instructions 3 See yellow flame section above 3 Pilot Outage Standing pilot models 4 Yellow lazy flame...

Страница 25: ...ls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing DANGER SHOCK HAZARD Make sure electri cal power to the heater is disconnected to avoid potential ser...

Страница 26: ...cement 1 Shut off electrical power to the heater 2 Shut off water supply and open drain valve to remove water in the piping at the pump level 3 Disconnect wiring and conduit connections to the pump 4...

Страница 27: ...anufactured by it but Raypak will apply any such warranty as may be provided to it by the parts manufacturer TO MAKE WARRANTY CLAIM Promptly notify the original installer supplying the model and seria...

Страница 28: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: