32
MODE 7
(With Default Settings Shown)
ADJUST MENU
(Page 2 of 2)
Item Field
Range
Description
Setting
0 to 10°F
(0 to 6°C)
STAGE DIFFERENTIAL
Select the interstage temperature differential
between stages for proportional staging.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 8:00 min
INTERSTAGE ON DELAY
Select the amount of time that must pass
once a stage has been turned on in order
to allow the next stage to turn on.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 4:00 min
INTERSTAGE OFF DELAY
Select the amount of time that must pass
once a stage has been turned off in order
to allow the next stage to turn off.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 5:00 min
MINIMUM ON TIME
Select the minimum amount of time that
the stage contact must remain on before it
is allowed to turn off.
Note: This setting is only available when
STAGE MODE is set to P.
0:10 to 5:00 min
MINIMUM OFF TIME
Select the minimum amount of time that
the stage contact must remain off before it
is allowed to turn back on.
Note: This setting is only available when
STAGE MODE is set to P.
OFF, 0:20 to
9:55 min, On
PUMP DELAY
Select the system pump purge time after
shutting off the burner.
External Input Signal
0:10 or 2:10
EXTERNAL INPUT SIGNAL
Select the range of the external input
signal.
Offset
-10 to +10°F
(-6 to +6°C)
OFFSET
Select the amount of offset when the boiler
target is determined from an external input
signal.
°F or °C
TEMPERATURE UNITS
Select to display temperature in degrees
Fahrenheit or in degrees Celsius.
Table R: Adjust Menu, Mode 7 (page 2 of 2)