20
Plumbing
General
Heater should be located so that any water leaks will
not cause damage to any adjacent areas or structures.
Gas Supply Connections
Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve locat-
ed outside the heater jacket. All gas piping should be
tested after installation in accordance with local codes.
CAUTION:
The heater and its manual shut-off
valve must be disconnected from the gas supply
during any pressure testing of that system at test
pressures in excess of 1/2 PSIG. Dissipate test
pressure in the gas supply line before reconnecting
the heater and its manual shut-off valve to gas
supply line. FAILURE TO FOLLOW THIS
PROCEDURE MAY DAMAGE THE GAS VALVE.
OVER PRESSURED GAS VALVES ARE NOT
COVERED BY WARRANTY. The heater and its gas
connections shall be leak tested before placing the
appliance in operation. Use soapy water for leak test
do NOT use open flame.
Fig. 19: Sediment Trap
NOTE:
Do not use teflon tape on gas line pipe
thread. A flexible sealant approved for the fuel being
used is recommended.
CAUTION:
For proper operation, no more than a
30% drop in gas supply pressure from no-load to full-
load conditions is acceptable. Under no
circumstances should the pressure be outside the
listed operational range.
Содержание RAYTHERM 133
Страница 15: ...15 Fig 9 Indoor Top Installation...
Страница 24: ...24 Piping Diagram Type WH Unitemp 80 System...
Страница 28: ...28 Location of Controls 0400 WH1 WH2 WH3 0181 LOW NOx WH1...
Страница 29: ...29 Location of Controls 0824...
Страница 38: ...38 WIRING DIAGRAMS Wiring Diagram W2 WH2 133...
Страница 39: ...39 Wiring Diagram WH1 0181 0261...
Страница 40: ...40 Wiring Diagram WH1 0331 0401...
Страница 41: ...41 Wiring Diagram WH1 0514 0724...
Страница 42: ...42 Wiring Diagram WH1 0824 1826...
Страница 43: ...43 Wiring Diagram WH1 2100 2500...
Страница 44: ...44 Wiring Diagram WH1 3001 4001...
Страница 51: ...51...
Страница 52: ...52 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...