26
on-off cycling heater. The valve has a remote capillary
bulb immersed in a well, at the header outlet, to main-
tain a constant outlet water temperature. When
multiple valves are furnished, they can be staged to
give greater flexibility of control. Standard factory set-
ting is at position 5. Consult the dial setting tag
attached to the control for your desired temperature.
See Fig. 22 below.
Fig. 22: Dial Setting Tag
Fig. 23: Mechanical Modulating Valve Location—
Models 0724-1336
Fig. 24: Motorized Gas Valve Location—Model 3001
Limit Controls
High Limit
The heater is equipped with a manual reset High Limit.
Push the reset button and set the limit(s) to 30°F–40°F
above desired operating temperature. Maximum set-
ting is 200°F; other options may be available.
Flow Switch
This dual-purpose control shuts off the heater in case
of pump failure or low water condition and is strongly
recommended. It is mounted and wired in series to the
main gas valve.
Fig. 25: High Limit
NOTE:
The flow switch is a safety device and not a
control. Do not operate the heater with flows less
than the minimums stated in this manual.
Fig. 26: Flow Switch
Содержание RAYTHERM 133-4001
Страница 15: ...15 Fig 9 Indoor Top Installation...
Страница 24: ...24 Piping Diagram Type WH Unitemp 80 System...
Страница 28: ...28 Location of Controls 0400 WH1 WH2 WH3 0181 LOW NOx WH1...
Страница 29: ...29 Location of Controls 0824...
Страница 38: ...38 WIRING DIAGRAMS Wiring Diagram W2 WH2 133...
Страница 39: ...39 Wiring Diagram WH1 0181 0261...
Страница 40: ...40 Wiring Diagram WH1 0331 0401...
Страница 41: ...41 Wiring Diagram WH1 0514 0724...
Страница 42: ...42 Wiring Diagram WH1 0824 1826...
Страница 43: ...43 Wiring Diagram WH1 2100 2500...
Страница 44: ...44 Wiring Diagram WH1 3001 4001...
Страница 50: ...50...
Страница 51: ...51...
Страница 52: ...52 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...