background image

In addition, the heater shall be installed such that the 

gas  ignition  system  components  are  protected  from 

water (dripping, spraying, rain, etc.) during appliance 

operation  or  service  (circulator  replacement,  control 

replacement, etc.).

Clearances

Indoor Installations

Heater

Side

Minimum Clearance

 from Combustible 

Surfaces

Recommended

Service 

Clearance

Floor*

0”

0”

Rear

1”

 

6”

Water Side

12”

24”

Other Side

1”

24”

Top

1”

6”

Front

Open

24”

Vent

2”

2”

Table E: Clearances – Indoor Installations

TOP VIEW 

FRONT VIEW 

Venting not shown for clarity. Heater must be vented 

per instructions in this manual 

Fig. 7: Minimum Clearances from Combustible 

Surfaces – Indoor Installations

When  installed  according  to  the  listed  minimum 

clear-ances  from  combustible  construction,  these 

heaters  can  still  be  serviced  without  removing  per-

manent  structural  construction  around  the  heater. 

However,  for  ease  of  servicing,  we  recommend  a 

clearance  of  at  least  24  in.  in  front,  and  at  least  12 

in.  on  the  water  connection  side.  This  will  allow  the 

heater  to  be  serviced  in  its  installed  location  without 

movement or removal of the heater.

Service  clearances  less  than  the  minimums  may 

require removal of the heater to service either the heat 

exchanger or the burner tray. In either case, the heat-

er must be installed in a manner that will enable the 

heater to be serviced without removing any structure 

around the heater.

Outdoor Installations

These heaters are design-certified for outdoor instal-

la-tion.  Heaters  must  not  be  installed  under  an 

overhang that is less than 3 ft from the top of the heat-

er.  Three  sides  must  be  open  in  the  area  under  the 

overhang. Roof water drainage must be diverted away 

from heaters installed under overhangs.

Heater

Side

Min. Clearance 

from Combustible

 Surfaces

Recommended

Service 

Clearance

Front

Open

24”

Rear

12”

6”

Water Side

36”

36”

Other Side

36”

36”

Top

Unobstructed

36”

Vent

N/A

N/A

Table F:  Clearances – Outdoor Installations

These  clearances  are  required  when  the  outdoor 

vent cap is used. If installing the heater outdoors 

with  a  vent  stack,  the  indoor  clearances  may  be 

utilized.

The  combustion  air  intake  hood  MUST  be  used  for 

outdoor installations. The hood is shipped loose and 

installed on the side of the heater over the filter box 

at the jobsite.

* DO NOT install on carpeting.

11

APPROVED 

UNCONTROLLED DOCUMENT IF PRINTED 

 

Содержание Raypak Delta Limited 1259B

Страница 1: ...GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s inst...

Страница 2: ...n page 31 for vent and intake pipe material certified standards Updated the Horizontal Through the Wall Venting Category III Installation section adding a third point on page 31 Updated the Periodical...

Страница 3: ...eating 16 Gas Supply 18 Electrical Power Connections 21 Field Wiring Connection 22 Venting 25 Changing the Flue Outlet 27 Venting Installation Tips 27 Venting Configurations 28 Outdoor Installation 32...

Страница 4: ...creating airborne dust and avoid inhaling airborne fibers When cleaning spills use wet sweeping or High Efficiency Particulate Air HEPA filtered vacuum to minimize airborne dust Use feasible engineeri...

Страница 5: ...s will not be accepted and will be replaced in kind only per Raypak s standard warran ties Model Identification The model identification number and heater serial number are found on the heater rating...

Страница 6: ...L FLUE CONNECTION Component Locations Fig 1 Component Locations Back Fig 2 Component Locations Left Side Panels removed for clarity Fig 3 Component Locations Front 6 APPROVED UNCONTROLLED DOCUMENT IF...

Страница 7: ...o Burners per Valve Stages Fire at Stage 1 1A 2 3 4 1 2 3 4 1 2 3 4 399B 8 1 100 499B 5 5 1 1 2 50 100 649B 7 6 1 1 2 54 100 749B 8 7 1 1 2 53 100 899B 6 6 6 1 2 1 2 3 66 100 989B 6 5 1 1 2 54 100 125...

Страница 8: ...ermometer NOTE When this water heater is supplying general purpose hot water for use by individuals a thermostatically controlled mixing valve for reducing point of use water temperature is recommende...

Страница 9: ...Hotter water increases the risk of scalding There is a hot water scald potential if the thermostat is set too high Fig 4 Temperature Control Equipment Base The heater should be mounted on a level str...

Страница 10: ...side of opening 1 ft 30 cm above opening 3 ft 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above paved sidewalk or paved dri...

Страница 11: ...vement or removal of the heater Service clearances less than the minimums may require removal of the heater to service either the heat exchanger or the burner tray In either case the heat er must be i...

Страница 12: ...t hand side standard to the right hand side 1 Remove the four screws and the dust cover from the right hand side of the heater 2 Remove the four screws and the air filter bracket from the left hand si...

Страница 13: ...area of a 1 in 2 per 3 000 BTUH 740 mm2 per kW of the total input rating of all equipment located in the enclosure and b Not less than the sum of the areas of all vent connectors in the confined spac...

Страница 14: ...the location of the opening s shall not interfere with the intended purpose of the opening s for ventilation air referred to in 1 This opening s can be ducted to a point not more than 18 in 450 mm nor...

Страница 15: ...CAUTION Damaging internal condensation may occur if the heater inlet water temperature does not exceed 105 F 41 C within 7 minutes of start up Models 399B 899B Models 989B 2339B 15 APPROVED UNCONTROLL...

Страница 16: ...ess than 20 gpm Temperature Pressure Gauge The temperature and pressure gauge is factory mount ed in the in out header Hydronic Heating Pump Selection In order to ensure proper performance of your hea...

Страница 17: ...water during the cooling cycle It is highly recommend ed that the piping be insulated Air Separation Expansion Tank All heaters should be equipped with a properly sized expansion tank and air separato...

Страница 18: ...ing control must be set no higher than 130F for scale free operation For operating tempera tures above 130F a water softener must be utilized Model No Soft 0 4 grains per gallon Medium 5 15 grains per...

Страница 19: ...s line pipe thread A pipe compound rated for use with natural and propane gases is recommended Apply sparingly only on male pipe ends leaving the two end threads bare Table I Maximum Equivalent Pipe L...

Страница 20: ...manifold risers 5 Remove the pipe cap from the right hand end of the main gas line 6 Reinstall the pipe cap on the left hand end of the main gas line 7 Remove plastic cap from the right hand side pan...

Страница 21: ...r its equivalent Field Connected Controllers It is strongly recommended that all individually pow ered control modules and the heater should be supplied from the same power source Check the Power Sour...

Страница 22: ...facturers instructions 6 Conduit should not be used as the earth ground Field Wiring Connection 22 NOTE A grounding electrode conductor shall be used to connect the equipment grounding conductors the...

Страница 23: ...23 Fig 20 2 Stage Wiring Connections Fig 21 3 Stage Wiring Connections Fig 22 4 Stage Wiring Connection APPROVED UNCONTROLLED DOCUMENT IF PRINTED...

Страница 24: ...at er is a Model 1529B you will jumper stages two three and four Then your heater will either be on at full fire or it will be off 2 For 2 stage controller connections connect each stage of the contro...

Страница 25: ...e is acceptable as shown in the NFGC The weights on the damper should be adjusted per the damper manufacturer s instructions for proper operation Appliance Categories Heaters are divided into four cat...

Страница 26: ...less Steel Gas Tight Vertical Natural Draft Venting I B Vent From Outside Building Horizontal Through the Wall Venting III Stainless Steel Gas Tight Galvanized Steel PVC ABS CPVC Use insulated vent pi...

Страница 27: ...de including normal snow line 9 Multiple sidewall vent installations require a 4 ft clearance between the ends of vent caps located on the same horizontal plane Changing the Flue Outlet Follow these i...

Страница 28: ...cap terminal adequately sized must be used to evacuate the flue products from the heaters The maximum and minimum venting length for Cate gory I appliances shall be determined per the NFGC U S or B14...

Страница 29: ...ng connected to the common venting system placed in operation while the other appliances remaining connected to the common venting system are not in operation 1 Seal any unused opening in the common v...

Страница 30: ...C U S or B149 Canada CAT III CERTIFIED INSULATED EXHAUST VENTING Fig 26 Horizontal Through the Wall Venting Category III Requires optional vent tee The total length of the horizontal through the wall...

Страница 31: ...e vent terminal 2 The vent must be insulated through the length of the horizontal run 3 The horizontal portions of the venting system shall be adequately supported to prevent sagging For installations...

Страница 32: ...vents offered by Heat Fab Inc 800 772 0739 Protech System Inc 800 766 3473 Z Flex 800 654 5600 or American Metal Products 800 423 4270 Pipe joints must be positively sealed Follow the vent manufacture...

Страница 33: ...tays energized for more than 5 seconds 11 Power is output from terminal J5 24V of the CPW board to all of the safeties All safeties are verified to ensure that it is safe to operate the heater The saf...

Страница 34: ...24 VAC safety connector 33 24 VAC is now sent to the pressure switch P Switch terminal on the ignition module 34 Once the pressure switch signal is received at the ignition module the hot surface ign...

Страница 35: ...VAC signal is sent to pin P3 16 of J 5 on the CPW board 14 24 VAC power now leaves pin P3 16 of J 5 on the CPW board and is sent to the auto reset high limit optional If closed the power now goes to...

Страница 36: ...remote sensor is now trying to sense the flame If the flame is not sensed within 4 seconds the ignition module will shut down the gas valve and retry the hot surface igniter During ignition retry the...

Страница 37: ...oses and the igniter is energized To ensure safe operation the gas valve cannot open until the igniter is verified The main burner is automatically lit when the device is powered and pre purged The he...

Страница 38: ...high gas pressure switch optional connection mounts down stream of the stage 1 gas valve If the gas pressure regulator fails the high gas pressure sheets supplied with your heater paperwork See the G...

Страница 39: ...Wiring Diagram Models 399B 1259B 39 APPROVED UNCONTROLLED DOCUMENT IF PRINTED...

Страница 40: ...Wiring Diagram Models 1529B 2339B 40 APPROVED UNCONTROLLED DOCUMENT IF PRINTED...

Страница 41: ...l your gas supplier from a neigh bor s telephone Follow the gas supplier s instructions WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage p...

Страница 42: ...e other safety control damage or failure Start Up Blower Adjustment 1 Turn off power 2 Unplug cap at pressure switches and connect ma nometer s to the tee 3 Close all manual firing valves 4 Turn power...

Страница 43: ...t the burner sections on either side of it The burner sections on either side of the supervised section pilot are electrically interlocked with the supervised ignition system so as they are not energi...

Страница 44: ...o heater Fig 36 Leak Test This completes leak testing for a single Delta Limited manifold riser Repeat steps 1 8 for each riser Post Start Up Check Check off steps as completed 1 Verify that the heate...

Страница 45: ...ve 7 Wait 5 minutes to clear out any gas Then smell for gas especially near the floor If you then smell gas STOP Follow the steps in the safety infor ma tion on the front cover of this manual If you d...

Страница 46: ...00 627 2975 Inside California Replace gas valve Are the gas valve settings correct Replace fan relay Replace fan Replace air pressure switch Correct the air settings or you may have to clean burners h...

Страница 47: ...remove any obstruction to the flow of combustion or ventilation air to heater 5 Follow pre start up check in the Start up section 6 Visually inspect burner flame It should be light blue Remove and vi...

Страница 48: ...ull fire Carbon di oxide should be 7 5 to 8 5 at full fire for natu ral gas and between 9 2 to 9 8 for propane gas Carbon monoxide should be 150 ppm 5 Check coils for 60 cycle hum or buzz Check for le...

Страница 49: ...ed ar eas this may also experience deterioration Products causing contaminated combustion air spray cans containing chloro fluorocarbons permanent wave solutions chlorinated waxes cleaners chlorine ba...

Страница 50: ...ENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if requested with transportation charges prepaid and all applicable warra...

Страница 51: ...toff _______________Test Category _________ sketch vent on reverse side Number of Tanks and Size Qty____ _______Gallons Vent Material __________________ Plumbing Size _______________ Vent Termination...

Страница 52: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A APPROVED UNCONTROLLED DOCUMENT IF PRINTED...

Отзывы: