24
Fig. 23: Wiring Location
Fig. 24: Locator Dimples for Optional Components
Fig. 25: Low Voltage Field Wiring
closure (including a remote thermostat) across these
terminals will enable the MVB unit to run. Caution
should be used to ensure neither of the terminals
becomes connected to ground.
Wiring the Outdoor Sensor
1. There is no connection required if an outdoor sen-
sor is not used in this installation.
2. If using an Outdoor Sensor (option B-32), connect
the sensor wires to the terminals marked OUT-
DOOR SENSOR (see Fig. 25). Caution should be
used to ensure neither of these terminals
becomes connected to ground.
3. Use a minimum 18 AWG wire for runs of up to 150
feet.
4. Mount the outdoor sensor on an exterior surface of
the building, preferably on the north side in an
area that will not be affected by direct sunlight and
that will be exposed to varying weather conditions.
NOTE:
A grounding electrode conductor shall be
used to connect the equipment grounding
conductors, the equipment enclosures, and the
grounded service conductor to the grounding
electrode.
Field Wiring Connection
CAUTION:
Label all wires prior to disconnection
when servicing controls. Wiring errors can cause im-
proper and dangerous operation. Verify proper
operation after servicing.
DANGER: SHOCK HAZARD
Make sure electrical power to the heater is discon-
nected to avoid potential serious injury or damage to
components.
Wiring the Enable/Disable
Connect the Enable/Disable wiring to the field wiring
terminal (shown in Fig. 25). Alternately, any dry contact
Содержание MVB 1104A
Страница 44: ...44 WIRING DIAGRAM Models 504A 2004A...
Страница 58: ...58...
Страница 62: ...62...
Страница 63: ...63...
Страница 64: ...64 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...