background image

Catalog No.:  2000.312D 

Effective:  11-15-07 

Replaces:  1-1-07 

Hi Delta – Type H 

Models 992B-2342B 

Model 

           

 

 

 

 

SPECIFICATIONS 

 

 

 

 

Approx. 

 MBTUH 

Firing

A

H

K

T

W

Amp. Shipping 

Model Input Output 

Stages

Width  NPT

   

 

Draw* Wt. (Lbs.) 

992B 990  832 

3

57-1/8

2-1/2 10 10 16-13/16

<12

900

1262B 1260  1058 

68-1/2

2-1/2 12 10

20-9/16 

<12 1010 

1532B 1530  1285 

79-7/8

2-1/2 12 10

24-3/8 

<12 1225 

1802B 1800  1512 

91-1/8

2-1/2 14 10

28-1/8 

<12 1350 

2002B 1999  1679 

4  102-1/2 2-1/2 14 10 31-15/16

<12 1450 

2072B 2070  1739 

4  102-1/2 2-1/2 14 10 31-15/16

<12 1450 

2342B 2340  1966 

4  113-7/8 2-1/2 16 10 35-11/16

<12 1520 

Dimensions are in inches. 

* Without pump 

RATES OF FLOW AND PRESSURE DROPS 

 

20°F 

T

30°F 

T

Min. Flow 

Max. Flow

Model GPM

P (ft) GPM

P (ft) GPM 

P (ft) 

T  GPM

P (ft)

T

992B

84

5.6

56

2.5

42 1.5 40 

132

14.0

13

1262B

107 10.0  71 

4.5 53 2.6 40 

132 

15.5 

16

1532B

130 

16.0 

86 

7.1 65 4.1 40 

132 

16.5 

20

1802B

N/A N/A 102 

10.8 76  6.0 40 132 18.0 23

2002B

N/A N/A 113 

14.0 85  8.1 40 132 19.5 26

2072B

N/A N/A 117 

15.0 88  8.7 40 132 19.5 27

2342B

N/A N/A 132 

21.0 99 12.0 40 132 21.0 30

Basis is 30 GPM or 40°F 

T for minimum flow, 132 GPM for maximum flow. 

NOTE:  Pump location 
varies based on model 
and application

 

NOTES:  1.  Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer. 
 

2.  Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 - 13” WC.

 

Raypak, Inc.  

ƒ

  2151 Eastman Avenue, Oxnard, CA  93030  

ƒ

  (805) 278-5300  

ƒ

  Fax (800) 872-9725  

ƒ

  www.raypak.com 

Отзывы: