OPERATING THE WATER HEATER
FOR YOUR SAFETY READ BEFORE LIGHTING
TO FILL THE WATER HEATER
Water Heating Applications
Open all building
hot water tap(s) (don‟t forget the showers) and supply cock(s) and valve(s) in the system.
Open the isolation valves fully on the cold, flow / return and hot water branches to the storage tank(s).
Open the cold water isolation valve on the cold water line to the storage tank(s). Air will be forced out of the
taps.
Close each tap as water flows freely from it.
Check the pipe work for leaks.
Mechanical/Process Heating Applications
If a header tank is fitted, ensure it is filled with water.
Open the isolation valve on the inlet line to the water heater.
Bleed air from the system at all high points to ensure that the entire system is filled with water.
Check the pipe work for leaks.
TO TURN ON THE WATER HEATER
Warning:
If you smell gas do not attempt to turn on the water heater.
The power supply to the water heater must not be switched on until the system is filled with water.
Fill the system with water (refer
to “
To Fill the Water Heater
” on page
39
)
Open the gas isolation valve fully at the inlet to the water heater.
Switch on the electrical supply at the water heaters isolation switch.
NOTE
: If the water heater is correctly
installed, this will also activate
the circulating pump.
The water heater will operate automatically when a call for heat occurs.
TO TURN OFF THE WATER HEATER
If it is necessary to turn off the water heater on completion of the installation, such as on a building site or where
the premises are vacant, then:
Switch off the electrical supply at the water heaters isolation switch.
NOTE
: If the water heater is correctly
installed, this will also shut down the circulating pump.
Close the gas isolation valve at the inlet to the water heater.
Close the cold water isolation valve at the inlet to the water heater.
Close the isolation valves on the cold and hot water branches to shut down an individual water heater in a bank
(water heating applications only).
TO RESET THE WATER HEATER
If the system water temperature is abnormally low, the ignition system may have
„locked out‟. A lockout condition is
indicated by the reset button being illuminated. If this occurs, the ignition system can be reset as follows:
Wait five (5) minutes for any unburnt gas to escape which may be present from a previous failed ignition
attempt.
Press and hold the reset button for approximately 1 second (the reset button light should extinguish).
If the water heater still fails to operate, call your nearest Rheem Service Department or Accredited Service Agent to
arrange for an inspection.
Содержание B0507
Страница 26: ...CONNECTIONS ELECTRICAL 26 Wiring Diagram for Typical BMS System Interface ...
Страница 28: ...CONNECTIONS ELECTRICAL 28 WIRING DIAGRAMS ON OFF MODELS 1000MJ NG ...
Страница 29: ...CONNECTIONS ELECTRICAL 29 ON OFF MODELS 1000MJ LPG ...
Страница 30: ...CONNECTIONS ELECTRICAL 30 ON OFF MODELS 1000MJ ...
Страница 31: ...CONNECTIONS ELECTRICAL 31 MODULATING MODELS 1000MJ NG DRAWING No 96159611B ...
Страница 32: ...CONNECTIONS ELECTRICAL 32 MODULATING MODELS 1000MJ LPG DRAWING No 96159610C ...
Страница 33: ...CONNECTIONS ELECTRICAL 33 MODULATING MODELS 1000MJ DRAWING No 96159613B ...
Страница 55: ...55 This page is intentionally blank ...