TEMPERATURE CONTROL
36
dn2
REGULATOR 2 PROTECTIVE DEVICE (folder with “rE2” label)
Delay time in activating the regulator relay after switch-on of
instrument.
0...250
1
do2
Delay after switch off. The indicated time must elapse between
switch-off of the regulator relay and the successive switch-on.
0...250
0
di2
Delay between switch-ons. The indicated time must elapse
between two successive switch-ons of the regulator
0...250
0
dE2
Delay before switch-off. The indicated time must elapse between
switch-off request and the switch-off of the regulator.
PLEASE NOTE: for parameters dn2, do2, di2, dE2 0= not active
0...250
0
On2
On time (regulator 2).
Regulator activation time in the event of faulty probe. If set to “1”
with OF1 at “0” the compressor is always on, while at OF2 >0 it
functions always in duty cycle mode.
0...250
0
OF2
OFF time (regulator 2). Regulator in disabled state time in the
event of a faulty probe. If set to “1” with On2 at “0” the regulator
is always off, while at On2 >0 it functions always in duty cycle
mode.
0...250
1
LOC
DISPLAY (folder with “diS” label)
(keyboard) LOCk (set and keys). Keyboard locking. However, you
can enter parameter programming
modify them along with the status of this parameter in order to
allow keyboard locking. y = yes; n = no
n/y
n
PA1
PAssword 1. When enabled (value other than 0) it constitutes the
access key for level 1 parameters
0...250
0
ndt
number display type. View with decimal point. y = yes; n = no
n/y
n
CA1
CAlibration 1.Calibration 1. Positive or negative temperature value
added to the value read by probe 1,
-30.0...30.0
0
dro
display read-out. Select °C or °F for displaying the temperature
read by the probe
°C/°F
°C
H00 (1) (!)
CONFIGURATION (folder with “CnF” label)
Probe type selection, PTC or NTC.
PtC/ntC
PtC
H01
Outputs link 0 = independents; 1 = related; 2 = Neutral Zone;
0/1/2
1
H10
delay time in activating the outputs after switch-on WARNING! If
set = 0 it is not active; if set 0 output will not be activated before
this time
0...250
0
rEL
reLease firmware. Device version: read only parameter.
/
/
tAb
tAble of parameters. Reserved: read only parameter.
/
/
UL
COPY CARD (folder with “Fpr”label)
Up load. Programming parameter transfer from instrument to
Copy Card.
/
/
dL
Down load. Programming parameter transfer from Copy Card to
/
/
Содержание B0147
Страница 23: ...CONNECTIONS ELECTRICAL 23 WIRING DIAGRAM 147 ON OFF MODELS...
Страница 24: ...CONNECTIONS ELECTRICAL 24 WIRING DIAGRAM 147 HI LO MODELS...
Страница 41: ...41 This page is intentionally blank...
Страница 42: ...42 This page is intentionally blank...