24
Operation
In the POOL or SPA modes, the actual water temperature
is displayed along with the desired water temperature
(SETPOINT). When the water temperature is above the
setpoint, “Water Temp” will alternate with “No Demand.”
When the water temperature is below the setpoint and the
heater is firing, “Water Temp” will alternate with “Heating.”
To adjust the setpoint temperature, make sure the control
is in the appropriate mode (POOL or SPA) and push the
UP or DOWN buttons.
By default, the setpoint range is 50-104°F (10-40°C). See
MAX Settings on
page 25
to increase the MAX setting,
if necessary.
Figure 31. Alternating Display During Heating
Program Mode Button (SW1)
Figure 32. Thermostat Program Button (SW1)
Service Menu and Fault History
To access the Service Menu and fault history, press the
Mode and UP buttons simultaneously for 3 to 5 seconds.
The heater will continue to operate while in the Service
Menu. The first screen displayed is the Flame Strength
indicator, which indicates the pilot flame current using a bar
graph and numerical display. A signal of less than 4 bars
indicates a weak flame signal and may require service.
Refer to the Troubleshooting section for possible causes
and corrections.
Figure 33. Flame Strength Indicator
Press the DOWN button. The Supply Voltage screen
indicates the voltage supplied to the control board. Normal
readings range from 24 to 29 volts.
Figure 34. Supply Voltage Indicator
Press the DOWN button. The Run Time indicates the total
hours of operation for the pool heater, as measured by the
amount of time that the main gas valve has been powered.
The Cycle count indicates the number of on/off cycles of
the heater, as measured by the number of times the pilot
valve has been powered.
Figure 35. Run Time/Cycles
Press the DOWN button. The Fault History displays up to
ten faults in memory. The order of the faults begins with
“Fault Last,” which is the most recent fault, and proceeds
through ten most recent messages in chronological order.
The second line of the display shows the fault message.
If there are no faults in the history buffer, the second line
reads “All Faults Clear.”
Figure 36. Fault History Indicator
Program Button
1. Remove the four screws holding the control cover,
and swing the panel down so the back side of the
board is visible. Locate the Program Mode button
(SW1). See
Figure 32
. Press and hold the button
for 5-7 seconds until SET FACTORY DEFAULTS
appears on the display. Release the program button.
2. Press the MODE button sequentially until the desired
program event is reached. There are 5 different
events that can be programmed. They appear in the
sequence listed in
Figure 37
.
RELEASED
For Reference Only