OUTDOOR INSTALLATIONS
Raypak Hi Delta Heaters are design certified
for outdoor installation. Heaters must not be installed under an overhang that
is less than three (3) feet from the top of the heater. Three (3) sides must be open in the area under the overhang. Roof water
drainage must be diverted away from heaters installed under overhangs.
TABLE 2
OUTDOOR INSTALLATION MINIMUM CLEARANCES
Heater Model
Heater Side
120-322
Rear
12"
Right
36”
Left
36"
Top
Unobstructed
Vent
N/A
These clearances required where the outdoor vent cap is used. If installing the heater outdoors with a vent stack, the
indoor clearances may be used.
10
FRONT VIEW
SIDE VIEW
Fig # 9400