17
5.2. P-156 Control Adjustments
The P-156 has a digital control system. The pool heater
(chauffe-piscine) touchpad, located on the upper front
panel of the heater, allows the user to select either POOL
or SPA operation, and to adjust the setpoint temperature.
The LCD display window indicates the mode (OFF, SPA,
POOL) and the actual water temperature. A manual power
switch provided below the touchpad turns the control
power ON or OFF.
Figure 20. Digital Control Adjustment
5.2.1. MENU/SET Button
The MENU/SET button is used to select POOL or
SPA operation. It allows the user to turn the heater off
electronically. The LCD remains energized and displays
OFF, while continues to show the actual water temperature.
5.2.2. Temp Buttons
If the heater is in POOL or SPA mode, the desired water
temperature (SETPOINT) will be displayed and may be
adjusted using the UP or DOWN buttons.
5.2.3. Operation
In the POOL or SPA modes, the actual water temperature
is displayed along with the desired water temperature
(SETPOINT). When the water temperature is above the
setpoint, “Water Temp” will alternate with “No Demand.”
When the water temperature is below the setpoint and the
heater is firing, “Water Temp” will alternate with “Heating.”
To adjust the setpoint temperature, make sure the control
is in the appropriate mode (POOL or SPA) and push the UP
or DOWN buttons.
Figure 21. Alternating Display During Heating
5.3. P-156 Thermostat Operation
Program Mode Button (SW1)
Figure 22. Thermostat Program Button (SW1)
5.3.1. Service Menu and Fault History
To access the Service Menu and fault history, press the
MENU/SET and UP buttons simultaneously for 3 to 5
seconds. The heater will continue to operate while in the
Service Menu. The first screen displayed is the Flame
Strength indicator, which indicates the pilot flame current
using a bar graph and numerical display. A signal of less
than 4 bars indicates a weak flame signal and may require
service. Refer to the Troubleshooting section for possible
causes and corrections.
Figure 23. Flame Strength Indicator
Press the DOWN button. The Supply Voltage screen
indicates the voltage supplied to the control board. Normal
readings range from 24 to 29 volts.
Figure 24. Supply Voltage Indicator
Press the DOWN button. The Run Time indicates the total
hours of operation for the pool heater, as measured by the
amount of time that the main gas valve has been powered.
The Cycle count indicates the number of on/off cycles of
the heater, as measured by the number of times the pilot
valve has been powered.
Содержание 106
Страница 23: ...23 6 WIRING DIAGRAMS Figure 35 P 106 Heater Wiring Figure 36 P 156 Heater Wiring...
Страница 31: ...31 1 M 1 C 5 M OPTIONAL 9 C 8 H 10 H 11 H 12 H 13 H 14 H OPTIONAL 15 H 16 H 17 H 9 H 1 P 2 P 3 P 4 P 5 P 1 H...
Страница 32: ...32 Natural 1 30mm 0 4 999 ft Propane 1 84mm 0 1 999 ft FOR ALTITUDES ABOVE THOSE LISTED CONSULT THE FACTORY...
Страница 34: ...34 NOTES...
Страница 35: ...35 NOTES...
Страница 36: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...