Raypak 106 Скачать руководство пользователя страница 17

17

5.2.  P-156 Control Adjustments

The P-156 has a digital control system. The pool heater 

(chauffe-piscine)  touchpad,  located  on  the  upper  front 

panel of the heater, allows the user to select either POOL 

or SPA operation, and to adjust the setpoint temperature.  

The LCD display window indicates the mode (OFF, SPA, 

POOL) and the actual water temperature. A manual power 

switch  provided  below  the  touchpad  turns  the  control 

power ON or OFF. 

Figure 20.  Digital Control Adjustment

5.2.1.  MENU/SET Button

The  MENU/SET  button  is  used  to  select  POOL  or 

SPA  operation.  It  allows  the  user  to  turn  the  heater  off 

electronically.  The  LCD  remains  energized  and  displays 

OFF, while continues to show the actual water temperature.

5.2.2.  Temp Buttons

If the heater is in POOL or SPA mode, the desired water 

temperature  (SETPOINT)  will  be  displayed  and  may  be 

adjusted using the UP or DOWN buttons.  

5.2.3.  Operation

In the POOL or SPA modes, the actual water temperature 

is  displayed  along  with  the  desired  water  temperature 

(SETPOINT).  When  the  water  temperature  is  above  the 

setpoint, “Water Temp” will alternate with “No Demand.”  

When the water temperature is below the setpoint and the 

heater is firing, “Water Temp” will alternate with “Heating.” 
To adjust the setpoint temperature, make sure the control 

is in the appropriate mode (POOL or SPA) and push the UP 

or DOWN buttons. 

Figure 21.  Alternating Display During Heating

5.3.  P-156 Thermostat Operation

Program Mode Button (SW1)

Figure 22.  Thermostat Program Button (SW1)

5.3.1.  Service Menu and Fault History

To access the Service Menu and fault history, press the 

MENU/SET  and  UP  buttons  simultaneously  for  3  to  5 

seconds. The heater will continue to operate while in the 

Service  Menu.  The  first  screen  displayed  is  the  Flame 

Strength indicator, which indicates the pilot flame current 

using a bar graph and numerical display. A signal of less 

than 4 bars indicates a weak flame signal and may require 

service. Refer to the Troubleshooting  section for possible 

causes and corrections.

Figure 23.  Flame Strength Indicator

Press  the  DOWN  button.  The  Supply  Voltage  screen 

indicates the voltage supplied to the control board.  Normal 

readings range from 24 to 29 volts.

Figure 24.  Supply Voltage Indicator

Press the DOWN button. The Run Time indicates the total 

hours of operation for the pool heater, as measured by the 

amount of time that the main gas valve has been powered.  

The Cycle count indicates the number of on/off cycles of 

the heater, as measured by the number of times the pilot 

valve has been powered.

Содержание 106

Страница 1: ...ic Above Ground Pool Spa Heater Chauffe Piscine English French A AAVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incendie ou d...

Страница 2: ...g changes Manual updated to the new format style Removed California Proposition 65 warning on pages 4 and 7 Replaced analog electronic with 106 156 on section 3 3 1 page 6 Replaced analog digital with...

Страница 3: ...n 10 4 5 Indoor Installation 10 4 6 Combustion and Ventilation Air Indoor Units Only 11 4 7 Gas Connections 12 4 8 Electrical Connections 15 4 9 240 Volt Installation Instructions 15 5 CONTROLS 16 5 1...

Страница 4: ...cal laws rules regulations or customs A AWARNING The heater shall not be located in an area where water sprinklers or other devices may cause water to spray through the cabinet louvers and into the he...

Страница 5: ...builder accredited pool shop or chemical supplier for the correct levels for your water 2 1 Automatic Chlorinators and Chemical Feeders All chemicals must be introduced and completely diluted into th...

Страница 6: ...mperatures by as much as 4 F 2 C 5 Persons with a medical history of heart disease circulatory problems diabetes or blood pressure problems should obtain a physician s advice before using spas or hot...

Страница 7: ...n the installation of this type of heating equipment and related system components Installation and service personnel may be required by some states to be licensed If your state is such be sure your c...

Страница 8: ...t will enable the heater to be serviced without removing any structure around the heater It is possible to reduce the clearances to combustible surfaces by protecting these surfaces as shown in table...

Страница 9: ...9 Figure 5 Florida Building Code Tie Down Method Amp Draw 120 Volt 240 Volt 4 2 Figure 4 Heater Dimensions...

Страница 10: ...the flue products exit the heater must be a minimum of 4 1 2 m below 4 1 2 m horizontally from or 1 0 3 m above any door window or gravity inlet into any building The top surface of the heater shall...

Страница 11: ...d the likelihood of condensate production in the vent Category I A heater which operates with a non positive vent static pressure and with a vent gas temperature that avoids excessive condensate produ...

Страница 12: ...ter A ACAUTION The heater and its manual shut off valve must be disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa The heater a...

Страница 13: ...m 459 140 m Table capacities are based upon use of sch 40 black iron pipe For capacities using other materials consult local code Natural Gas 1000 BTU FT3 0 60 Specific Gravity 0 5 WC Pressure Drop Ga...

Страница 14: ...d be slightly warmer than inlet and comfort able to the touch If pipe is hot close bypass if cold open bypass 4 7 10 Pressure Relief Valve Installation To conform to local building codes it may be nec...

Страница 15: ...directly from the GFCI power source It is preferred to make connection to the load pump side of the time clock A AWARNING Risk of electrical shock More than one disconnect switch may be required to d...

Страница 16: ...t The switch functions as a means for turning the heater On or Off The thermostat is fitted with a means of limiting the upper temperature limit below the maximum level The knob stop adjustment ring s...

Страница 17: ...er is firing Water Temp will alternate with Heating To adjust the setpoint temperature make sure the control is in the appropriate mode POOL or SPA and push the UP or DOWN buttons Figure 21 Alternatin...

Страница 18: ...he digital display Press and hold both UP and DOWN buttons for 5 7 seconds until Faults Cleared appears This operation resets the Fault History file to 0 and clears all the stored faults Fahrenheit or...

Страница 19: ...C Flame w o CFH Board is sensing flame when both main and pilot valves are commanded shut PV Output Fault Pilot gas valve output is not in commanded state MV Output Fault Main gas valve output is not...

Страница 20: ...g in the POOL Mode Heating in the SPA Mode Remote Mode Figure 28 Remote Control Menu Remote Operation 5 4 3 Activating the Remote To activate or deactivate the remote function follow these steps 1 Pre...

Страница 21: ...f the remote control see Activating the Remote on page 20 5 5 2 3 Wire Remote Control Using Three Position Switch Pool Off Spa or Low Off High 1 This application assumes that both heating functions po...

Страница 22: ...e only slightly warmer than the inlet It should not be hot With the heater on remove the door and make a visual check of the burner PILOT Figure 33 IID Pilot Location 5 6 1 Cold Weather Operation Mode...

Страница 23: ...23 6 WIRING DIAGRAMS Figure 35 P 106 Heater Wiring Figure 36 P 156 Heater Wiring...

Страница 24: ...djust the pressure switch to compensate for the no flow static head If it is necessary to adjust the water pressure switch utilize the following procedure A ACAUTION Do not adjust the pressure switch...

Страница 25: ...7 1 7 Burner Tray Removal 1 Shut off main electrical power switch to heater 2 Shut off gas upstream of heater 3 Remove front door 4 Disconnect gas line from gas valve 5 Remove 3 screws holding the an...

Страница 26: ...xchanger ream tubes and immerse heat exchanger in non inhibited de scale solvent for severe scale build up 7 1 12 De sooting Procedure A ACAUTION Soot may be combustible Wet sooted surfaces completely...

Страница 27: ...nd 110 F 40 5 C and 43 3 C If no movement replace Air starvation Refer to installation instructions Improper venting Follow recommended installation instructions Insects or debris clogging burner inta...

Страница 28: ...o pressure then there is not enough moving water in the system or the gauge is broken Attempt to make the pump run at its normal flow rate Does the pilot spark after performing the above steps 1 The s...

Страница 29: ...stance k 261 1 199 0 153 1 118 8 93 0 73 3 58 3 51 0 If okay replace Circuit Board Sensor Failure Inspect thermister wires and connector at Terminal P1 Check resistance value of the thermister Referen...

Страница 30: ...S 3 S 2 M 3 M 4 M 1 J 2 J 2 J 3 J 4 J 4 J 1 V 2 V 3 V 4 V 11 M 12 M 1 B 10 S 5 S 6 S 7 S 8 S 9 S 9 S 3 B 6 C 8 C 9 C 2 H 3 H 4 H 5 H 6 H 6 H 7 H 7 H 2 C 3 C 10 M 9 M 8 M 5 V 5 C 4 S 7 C 4 C 10 C 9 IL...

Страница 31: ...31 1 M 1 C 5 M OPTIONAL 9 C 8 H 10 H 11 H 12 H 13 H 14 H OPTIONAL 15 H 16 H 17 H 9 H 1 P 2 P 3 P 4 P 5 P 1 H...

Страница 32: ...32 Natural 1 30mm 0 4 999 ft Propane 1 84mm 0 1 999 ft FOR ALTITUDES ABOVE THOSE LISTED CONSULT THE FACTORY...

Страница 33: ...4891F S SHEETMETAL 1 S Jacket Top 014892F 014893F 2 S Jacket Left 014894F 014895F 3 S Jacket Right 014896F 014897F 4 S Jacket Upper Front 014898F 014898F 5 S Jacket Lower Rear 014899F 014899F 6 S Flue...

Страница 34: ...34 NOTES...

Страница 35: ...35 NOTES...

Страница 36: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Отзывы: