16
3.1.10 Trace boiler
The trace boiler setting is included to ensure that the heating cable temper-
ature does not exceed the boiler temperature. The boiler temperature is
measured with the external temperature sensor. The HWAT-ECO memo-
rizes the highest measured temperature over the last 24 hours. With the
up/down arrow keys the setting can be altered between OFF and ON with a
selected temperature difference from 5°C to max 15°C between boiler tem-
perature and maintain temperature. Press Enter to confirm your choice. If
the boiler temperature is too low the maximum temperature is lowered to
the boiler temperature minus the trace temperature. In this case the trace
boiler LED will be on.
Finishing “Quick install”
Press Enter to start the unit.
With ESC it is possible to retrace all menu items to check the settings.
After starting the unit the display shows date, time, temperature setting
and a * to indicate that the unit is unlocked.
Back to “Quick install”
The Setup menu (see next chapter) has a Reinitialise menu to start over
again.
Previous settings are returned to default factory settings, except time and
date.
Note:
A menu can be consulted if further detailed settings (eg. Master/slave,
BMS, etc.) are required. You must press a key to access the menu inside
the HWAT-ECO. (Pressing ESC shows the current preferred cable tempera-
ture.) Pressing another key shows the main menu. There are 6 main
menus: Language, Time and Date, Setup, Timer program, Holiday and Info.
22-6-2001 09:13
Maintain
*
Tyco C 9278e HWAT-ECO 22.02.2002 14:12 Page 16
Содержание HWAT-ECO
Страница 2: ...3 148 mm 1 2 A B C Tyco C 9278e HWAT ECO 22 02 2002 14 12 Page 2 ...
Страница 28: ...28 Fig 10 Example Fig 11 Tyco C 9278e HWAT ECO 22 02 2002 14 12 Page 28 ...
Страница 29: ...29 Fig 12 Tyco C 9278e HWAT ECO 22 02 2002 14 12 Page 29 ...
Страница 97: ...Fig 10 Exemple Fig 11 97 Tyco C 9278f HWAT ECO 22 02 2002 14 10 Page 97 ...
Страница 98: ...Fig 12 98 Tyco C 9278f HWAT ECO 22 02 2002 14 10 Page 98 ...