PRODUCT DIMENSIONS

Controller Dimensions

Limiter dimensions

INSTALLATION

Ensure all personnel involved in installation, servicing, 

and programming are qualified and familiar with electrical 

equipment, their ratings and proper practices and codes.

Installation Location

Considerations should include expected atmospheric 

conditions, accessibility for maintenance, testing and ambient 

temperature. The conditions at the place of installation may 

affect load current ratings.

Operator Safety Considerations

Caution: 

Some wiring configurations will use more than one 

power source and all must be de-energized prior to performing 

any maintenance on a control circuit. 

Warning: 

The HTC-915 control module must be protected by 

external over current and disconnect devices.

Mounting Procedures

The HTC-915-CONT and HTC-915-LIM are designed for 

installation on a standard 35 mm x 7.5 mm (EN50022 

compatible) DIN rail.

Pollution Degree 2

Altitude 0-2000m

MAINTENANCE

Operator Maintenance

The HTC-915 control system is designed to be a maintenance 

free product.

Replaceable Parts

There are no user-serviceable parts in the HTC-915 series 

controller or accessories. The unit is designed to be easily 

changed out in the field in a matter of minutes.

Any HTC-915 system component appearing inoperative 

should be returned to the nearest nVent office.

Cleaning

If the HTC-915 components require cleaning, a damp cloth 

may be used to wipe the units. This should only be done while 

the units are disconnected from their power source. Do not 

use any harsh chemicals or solvents, as this may damage the 

housing or finish.

ELECTRICAL CONNECTION

Connections are made via screw connections suitable to 

accept cable diameters between 0.5 and 2.5 mm2 (24 to 

12 Awg). Either solid or stranded wires may be used.

Do not rely on the controller as a disconnect device!

Installation notes

•  If contact with live parts is possible while working on the 

unit, it must be completely isolated from the mains supply. 

Be aware that the unit might have cables connected to it 

which are powered from different sources.

•  Magnetic or electric fields, eg: from transformers, mobile 

phones or electrostatic discharge must be avoided in the 

vicinity of the instrument.

•  Route input, output and supply lines separately.
•  Arrange sensor cable extensions as twisted and screened 

cables. Do not run them close to power cables. The shield, 

if any, shall be earthed on the controller’s side only.

•   Fluctuations in the supply signals are only permissible 

within the specified tolerances.

75

45

105

915 SERIES

LIMITER

POWE R

ALAR M

HEATER

CURRENT

Tx /Rx

RESET

TRIP

75

90

105

SHIF T

TEST

BACK

ENTER

MONITOR

ALARM

CONFI G

ALAR M

OUTPU T

915 SERIES HEA T-TRACING CONTROLLER

Tx

Rx

North America

Tel +1.800.545.6258
Fax +1.800.527.5703
[email protected]

Europe, Middle East, Africa

Tel +32.16.213.511
Fax +32.16.213.603
[email protected]

Asia Pacific

Tel +86.21.2412.1688
Fax +86.21.5426.2937
[email protected]

Latin America

Tel +1.713.868.4800
Fax +1.713.868.2333
[email protected]

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change 
specifications without notice.
Raychem-IM-HTC915-INSTALL092-EN-1811

nVent.com

Содержание HTC-915

Страница 1: ...HTC 915 Universal heat tracing control system ...

Страница 2: ...rrent IEC 60417 5031 2002 10 Direct current ELECTRICAL PROPERTIES Connection terminals and cabling Screw type terminals All terminals suitable for stranded and solid core connection cables having a cross section between 0 5 and 2 5 mm2 24 to 12 AWG The 915 HTC and 915 Alarm Relay connector outputs 240V require ferrules on the connecting wires if stranded wires are used The wires shall handle a min...

Страница 3: ...s available COMMUNICATIONS Protocol Modbus RTU or ASCII Topology Multidrop daisychain Cable Single shielded twisted pair 0 5 mm2 24 AWG or larger Length Typical 2 7 km max 9600 Baud Quantity Up to 32 devices Address Programmable For technical support call nVent or write an E mail to thermal info nvent com FUNCTIONAL OVERVIEW The nVent RAYCHEM HTC 915 is a full featured temperature control system f...

Страница 4: ... shown by the text above that key Quick Notes on Operation Basic rules for efficient Console use use the SHIFT key followed by the appropriate function key ALARM MONITOR or CONFIG to select the operating mode use Í and to move around in the menu use Ë to enter a new menu enter a new value or select a menu item use Á to exit the current menu or cancel an edit Key Function SHIFT Press to activate a ...

Страница 5: ...ed to hit the SHIFT key before pressing the CONFIG button to confirm the removal of the limiter Changing the Configuration To change the Controller configuration Position the desired parameter menu item in the display Press the Ë key to initiate an edit session If the console is locked you are prompted to enter the passcode The present setting will flash on the display to indicate that you are edi...

Страница 6: ...the limit temperature minus the unit hysteresis The limiter can be reset using one of the following methods 1 From the control panel on the HTC 915 CONT by pressing alarm and SHIFT RESET assuming presence of the digital communication between controller and limiter 2 Via pushing and holding the RESET key on the limiter unit for t 2 seconds 3 Remotely via the external input of the HTC 915 and a remo...

Страница 7: ...Parity n a None Tx Deley 0 06 secs n a Parameter may only appear if certain features are enabled Values shown in brackets are the Factory defaults if the settings are enabled This information defines the default 915 Series Control Module configuration as set by the Factory for firmware V1 0X These settings are subject to change without notice It is the user s responsibility to verify that all conf...

Страница 8: ...vents as this may damage the housing or finish ELECTRICAL CONNECTION Connections are made via screw connections suitable to accept cable diameters between 0 5 and 2 5 mm2 24 to 12 Awg Either solid or stranded wires may be used Do not rely on the controller as a disconnect device Installation notes If contact with live parts is possible while working on the unit it must be completely isolated from ...

Отзывы: