CONNECTION DIAGRAM 

TERMINAL ASSIGNMENTS

SHIF T

TEST

BACK

ENTER

MONITOR

ALARM

CONFI G

ALAR M

OUTPU T

915 SERIES HEA T-TRACING CONTROLLER

Tx

Rx

1   2   3   4   5   6    7   8 9  10 11 12 13 14 15 16  

30 29 28 27 26 25 24 23  22    21    20    19    18    17  

Gr

ound fault C

T input

1 t

o 0.001 A

Load C

T input 100 t

o 0.1 A

SSR out

Alarm output

NO or NC

Contr

ol r

ela

y output

100 t

o 250 V

ac / 277 V

ac.

(+10 / –10%)

- +

Connection t

o limiter

RS 485 comm

Ext input

TS2

(optional)

TS1

Alarm output relay

CE/EAC: Relay contact rated 3 A/250 Vac, 50/60 Hz  
CSA: Relay contact rated 3A/277Vac, 50/60 Hz 
Output is user programmable to open or to close on alarm. 

Power output 

12 Vdc, 200 mA max. 

TEMPERATURE SENSOR

Type 

100 Ω platinum Pt 100, 3-wire, α = 0.00385 Ω/°C. Can be extended with a three core 

shielded cable of maximum 20 Ω lead resistance per conductor. 

Quantity 

2 RTD inputs available 

COMMUNICATIONS

Protocol 

Modbus RTU or ASCII 

Topology 

Multidrop/daisychain 

Cable 

Single shielded twisted pair, 0.5 mm

2

 (24 AWG) or larger 

Length 

Typical 2.7 km max @ 9600 Baud 

Quantity 

Up to 32 devices 

Address 

Programmable 

For technical support call nVent or write an E-mail to [email protected]

FUNCTIONAL OVERVIEW

The nVent RAYCHEM HTC-915 is a full featured temperature control system for 

heattracing applications.

Power supply

100 to 250V

±10% at 50/60Hz

(also used

for voltage

measurements)

2 three wire

PT100 inputs

HTC-915

Controller

Digital

communication

Configuration

and set-up

Software (RS485)

Control

Relay output

(250V/277V/3A)

Current

Transformer

Load current

Control

Solid state output

(0 – 12Vdc)

Alarm output

(relay 250V/277V/3A)

Configurable to open

or to close on alarm

Current

Transformer

Earth leakage current

Scrolling display

Current

Transformer

Load current

3-wire PT100

input

HTC-915

Limiter

Alarm output

(relay 250V/277V/3A)

NC opening on alarm

Trip

Relay output

(250V/277V/3A)

nVent.com  |  3

Содержание HTC-915

Страница 1: ...HTC 915 Universal heat tracing control system ...

Страница 2: ...rrent IEC 60417 5031 2002 10 Direct current ELECTRICAL PROPERTIES Connection terminals and cabling Screw type terminals All terminals suitable for stranded and solid core connection cables having a cross section between 0 5 and 2 5 mm2 24 to 12 AWG The 915 HTC and 915 Alarm Relay connector outputs 240V require ferrules on the connecting wires if stranded wires are used The wires shall handle a min...

Страница 3: ...s available COMMUNICATIONS Protocol Modbus RTU or ASCII Topology Multidrop daisychain Cable Single shielded twisted pair 0 5 mm2 24 AWG or larger Length Typical 2 7 km max 9600 Baud Quantity Up to 32 devices Address Programmable For technical support call nVent or write an E mail to thermal info nvent com FUNCTIONAL OVERVIEW The nVent RAYCHEM HTC 915 is a full featured temperature control system f...

Страница 4: ... shown by the text above that key Quick Notes on Operation Basic rules for efficient Console use use the SHIFT key followed by the appropriate function key ALARM MONITOR or CONFIG to select the operating mode use Í and to move around in the menu use Ë to enter a new menu enter a new value or select a menu item use Á to exit the current menu or cancel an edit Key Function SHIFT Press to activate a ...

Страница 5: ...ed to hit the SHIFT key before pressing the CONFIG button to confirm the removal of the limiter Changing the Configuration To change the Controller configuration Position the desired parameter menu item in the display Press the Ë key to initiate an edit session If the console is locked you are prompted to enter the passcode The present setting will flash on the display to indicate that you are edi...

Страница 6: ...the limit temperature minus the unit hysteresis The limiter can be reset using one of the following methods 1 From the control panel on the HTC 915 CONT by pressing alarm and SHIFT RESET assuming presence of the digital communication between controller and limiter 2 Via pushing and holding the RESET key on the limiter unit for t 2 seconds 3 Remotely via the external input of the HTC 915 and a remo...

Страница 7: ...Parity n a None Tx Deley 0 06 secs n a Parameter may only appear if certain features are enabled Values shown in brackets are the Factory defaults if the settings are enabled This information defines the default 915 Series Control Module configuration as set by the Factory for firmware V1 0X These settings are subject to change without notice It is the user s responsibility to verify that all conf...

Страница 8: ...vents as this may damage the housing or finish ELECTRICAL CONNECTION Connections are made via screw connections suitable to accept cable diameters between 0 5 and 2 5 mm2 24 to 12 Awg Either solid or stranded wires may be used Do not rely on the controller as a disconnect device Installation notes If contact with live parts is possible while working on the unit it must be completely isolated from ...